CTY OF C/S - MUNICIPAL AIRPORT | H07 | C | 06/21/2023 | WITNESSED ESCALATOR SAFETY AND STEP INDEX TESTS W/ SCHINDLER -- MINIMUM BRAKE TORQUE 150 FT/LBS, ACTUAL 190 FT/LBS -- / SAFETY TESTING INCOMPLETE AND MORE ITEMS MAY ARISE DURING COMPLETION OF TESTING / DEMARCATION LIGHTS AT TOP AND BOTTOM NOT WORKING / NEED SKIRT BRUSHES INSTALLED / INDEX TESTING NEEDS TO BE REDONE WITH A DIFFERENT PMT TOOL, NOT GETTING ACCURATE READING WITH PMT TOOL USED ON SITE / SKIRTS NEED ADJUSTED TO NO MORE THAN 4.8MM GAP BETWEEN STEPS / CHAINS NEED LUBED AND CHECKED FOR ADJUSTMENT / CONTACT PPRBD TO COMPLETE TESTING WHEN READY / PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL TESTING IS COMPLETED / ESCALATOR SHUT DOWN AFTER INSPECTION | DUSTINS | DUSTINS | | H07 | C | 7778408 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 06/21/2023 | WITNESSED AT H01 -- HOLD PERMIT TO OPERATE UNTIL WITNESS TESTING COMPLETE (Receipt #1963552) | DUSTINS | DUSTINS | | H01 | C | 7778375 |
CTY OF C/S - MUNICIPAL AIRPORT | H05 | C | 09/23/2022 | OUT OF SERVICE -- INFORMED FACILITIES OF REMOVED FROM SERVICE REGULATIONS. MAINLINE DISCONNECT AND CONTROLLER ARE LOCKED OUT AND SEALS APPLIED --/ PROVIDE PERMANENT BARRICADES AT BOTH ENDS | MIKEM | MIKEM | | H05 | C | 7528510 |
CTY OF C/S - MUNICIPAL AIRPORT | H05 | C | 09/21/2021 | ESCALATOR HAS BEEN DORMANT FOR MORE THAN 5 YEARS - OWNER NEEDS TO BE NOTIFIED REGARDING PROCESS TO EITHER PUT BACK INTO SERVICE OR REMOVE FROM SERVICE PER STATE REGS | ROBERTV | ROBERTV | | H05 | C | 7115277 |
CTY OF C/S - MUNICIPAL AIRPORT | H05 | C | 09/09/2020 | OUT OF SERVICE | ERIC | ERIC | | H05 | C | 6700384 |
CTY OF C/S - MUNICIPAL AIRPORT | H05 | C | 09/30/2019 | OUT OF SERVICE | ERIC | ERIC | | H05 | C | 6352248 |
CTY OF C/S - MUNICIPAL AIRPORT | H05 | C | 09/04/2018 | OUT OF SERVICE | ERIC | ERIC | | H05 | C | 5954312 |
CTY OF C/S - MUNICIPAL AIRPORT | H05 | C | 09/26/2017 | STILL OUT OF SERVICE | ROBERTV | ROBERTV | | H05 | C | 5637553 |
CTY OF C/S - MUNICIPAL AIRPORT | H05 | C | 03/10/2017 | STILL OUT OF SERVICE | ROBERTV | ROBERTV | | H05 | C | 5438043 |
CTY OF C/S - MUNICIPAL AIRPORT | H05 | C | 03/08/2016 | ESCALATOR TO REMAIN OUT OF SERVICE UNTIL PREVIOUS ITEMS ARE ADDRESSED, MAIN BREAKER HAS BEEN SHUT OFF AND TAGGED (Receipt #1316846) | ROBERTV | ROBERTV | | H05 | C | 5149758 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/22/2015 | ESCALATOR TO REMAIN OUT OF SERVICE UNTIL PREVIOUS ITEMS ARE ADDRESSED | ROBERTV | ROBERTV | | H02 | C | 5041995 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/05/2015 | WITNESSED 2/15 (Receipt #1248823) | ERIC | ERIC | | H01 | C | 4911690 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 02/11/2015 | WITNESSED ANNUAL SAFETY INSPECTION AND INDEX TESTING. DEMARCATION LIGHTS NOT WORKING, INDEX TESTING FAILED, NEED SKIRT BRUSHES INSTALLED, 1 CHIPPED STEP TREAD. ESCALATORS TO REMAIN OUT OF SERVICE UNTIL INDEX TEST PASSES. | ERIC | ERIC | | HE16 | C | 4901029 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/29/2014 | NOT BEING USED | ERIC | ERIC | | H02 | C | 4824890 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/12/2014 | NOT IN SERVICE (Receipt #1183587) | ERIC | ERIC | | H01 | C | 4701556 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/11/2013 | NOT IN USE | ERIC | ERIC | | H02 | C | 4602877 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/08/2013 | MKE. (Receipt #1115805) | ERIC | ERIC | | H01 | C | 4484109 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/06/2012 | NOT IN USE | ERIC | ERIC | | H02 | C | 4376603 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/01/2012 | OUT OF SERVICE (Receipt #1030542) | ERIC | ERIC | | H01 | C | 4277440 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/21/2011 | STILL OUT OF SERVICE. WAITING FOR DECISION ON HO5 STATUS FROM MANAGEMENT | ERIC | ERIC | | H02 | C | 4210612 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/08/2011 | MKE. NEED ANNUAL SAFETY INSPECTION AND INDEX TESTING OR HAVE ESCALATOR RED TAGGED AND PUT OUT OF SERVICE (Receipt #962961) | ERIC | ERIC | | H01 | C | 4119823 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/09/2010 | MKE. NEED ANNUAL SAFETY INSPECTION AND INDEX TEST | ERIC | ERIC | | H02 | C | 4036925 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/16/2010 | MKE. NOT IN SERVICE (Receipt #900502) | ERIC | ERIC | | H01 | C | 3954679 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 11/19/2009 | NO INDEX TESTING DONE, UNIT NOT IN SERVICE | ERIC | ERIC | | HE16 | C | 3914110 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/10/2009 | MKE. UNIT SHUT DOWN BUT STILL USED WHEN NEEDED | ERIC | ERIC | | H02 | C | 3882924 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/13/2009 | MONTGOMERY (Receipt #850035) | ERIC | ERIC | | H01 | C | 3812369 |
CTY OF C/S - MUNICIPAL AIRPORT | HE16 | C | 11/21/2008 | WITNESSED ANNUAL SAFETY TEST. NO DEFICIENCIES NOTED | ERIC | ERIC | | HE16 | C | 3774472 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/30/2008 | montgomery--east terminal unit 6 --unit shut down --still need annual | JOHNW | JOHNW | | H02 | C | 3748737 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/24/2008 | MONTGOMERY --- TURNED OFF | LES | LES | | H01 | C | 1978330 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/28/2007 | MONTGOMERY--LIMITED USE | JOHNW | JOHNW | | H02 | C | 1978322 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/29/2007 | NEED ANNUAL INSPECTION | JOHNW | JOHNW | | H01 | C | 1978315 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/15/2006 | MONTGOMERY --- NOT IN USE | LES | LES | | H02 | C | 1978308 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/24/2006 | NOT USED | LES | LES | | H01 | C | 1978301 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/13/2005 | NOT IN USE AT THIS TIME | JOHNW | JOHNW | | H02 | C | 1978294 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/29/2005 | MONTGOMERY -- NOT IN USE AT THIS TIME | JOHNW | JOHNW | | H01 | C | 1978288 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/09/2004 | MONTGOMERY --- NOT IN USE | LES | LES | | H02 | C | 1978280 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/08/2004 | NOT IN USE --- MONTGOMERY | LES | LES | | H01 | C | 1978273 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 10/09/2003 | | LES | LES | | H02 | C | 1978267 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/12/2003 | NOT IN USE - LOCKED OUT | LES | LES | | H01 | C | 1978258 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/18/2002 | NOT IN USE | LES | LES | | H02 | C | 1978251 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/07/2002 | SPACE NOT OCCUPIED | LES | LES | | H01 | C | 1978245 |
CTY OF C/S - MUNICIPAL AIRPORT | H02 | C | 09/07/2001 | SPACE NOT OCCUPIED -- SHUT DOWN | LES | LES | | H02 | C | 1978238 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 03/20/2001 | NOT IN USE | LES | LES | | H01 | C | 1978231 |
CTY OF C/S - MUNICIPAL AIRPORT | H01 | C | 02/06/2001 | INITIAL INSPECTION --- PERMIT ISSUED -- UP ESCALATOR | LES | LES | | H01 | C | 1978224 |