PINE CONSTRUCTION, INC. | B= | C | 05/16/2003 | | TERRYB | TERRYB | | B= | C | 2227334 |
PINE CONSTRUCTION, INC. | B= | P | 07/11/2002 | Temp CO: NEW TCO... | ROLF | ROLF | | B= | P | 2227326 |
PINE CONSTRUCTION, INC. | B= | P | 06/11/2002 | 1)Need elec final 2)Restroom signs 3)Insulate drains 4)Install handicap hardware 5)Seal penetrations in 1hr wall 6)fill gap at top of 1hr wall | RICK | RICK | | B= | P | 2227314 |
PINE CONSTRUCTION, INC. | BFR | C | 06/11/2002 | | RICK | RICK | | BFR | C | 2227320 |
PINE CONSTRUCTION, INC. | BFR | P | 05/21/2002 | platforms | TERRYB | TERRYB | | BFR | P | 2227309 |
PINE CONSTRUCTION, INC. | BFR | P | 05/02/2002 | | TERRYB | TERRYB | | BFR | P | 2227303 |
WHITNEY ELECTRIC CO | E= | C | 06/13/2002 | contractor putting on location plaques as I left, could not find the card to sign | TERRY | TERRY | | E= | C | 2227489 |
WHITNEY ELECTRIC CO | E= | P | 06/11/2002 | Ok for opening per electrical only, still need building and plumbing permission for TCO, bonding electrode conductor to be brought to the main waterline entry point, arc shields for all outlets in wood, install disconnects and pull wire for stage temp power, put identification tags on service disconnects (1 of 2, location of other, etc) | TERRY | TERRY | | E= | P | 2227483 |
WHITNEY ELECTRIC CO | E= | R | 06/10/2002 | city is still putting power to building | TERRY | TERRY | | E= | R | 2227477 |
WHITNEY ELECTRIC CO | ER | C | 06/07/2002 | all suspended ceilings ok'd | TERRY | TERRY | | ER | C | 2227472 |
WHITNEY ELECTRIC CO | E= | R | 06/07/2002 | NOT READY | TERRY | TERRY | | E= | R | 2227466 |
WHITNEY ELECTRIC CO | ES | C | 06/05/2002 | 800A 4w/oh Whitney Electric (service for restaurant) Johny Nowland, CT metered, ok'd to energize, needs drop and meter | TERRY | TERRY | | ES | C | 2227461 |
WHITNEY ELECTRIC CO | ES | R | 06/04/2002 | put neutral bar in Ct can, change bond wires, redo nipples from ct can, redo ground wire point of grounding | TERRY | TERRY | | ES | R | 2227455 |
WHITNEY ELECTRIC CO | ER | P | 05/23/2002 | stage area rough ok'd | TERRY | TERRY | | ER | P | 2227449 |
WHITNEY ELECTRIC CO | ER | P | 04/29/2002 | all walls minus the stage area | TERRY | TERRY | | ER | P | 2227441 |
COBB MECHANICAL CONTRACTORS, INC. | H= | C | 06/11/2002 | FINAL PENDING RECEIPT OF A BALANCE REPORT ON HOOD AND MUA UNIT. BALANCE REPORT RECEIVED 6/13/02 LS. | LYNNS | LYNNS | | H= | C | 2227435 |
COBB MECHANICAL CONTRACTORS, INC. | H= | P | 06/10/2002 | No power to building to diminstrate interlock. Need balance report and information on 25/50 insulation in return plenum. | LYNNS | LYNNS | | H= | P | 2227423 |
COBB MECHANICAL CONTRACTORS, INC. | HD | C | 06/06/2002 | Rough duct complete. | LYNNS | LYNNS | | HD | C | 2227404 |
COBB MECHANICAL CONTRACTORS, INC. | H= | P | 06/06/2002 | Gas final only, complete. OK to release meter. | LYNNS | LYNNS | | H= | P | 2227398 |
COBB MECHANICAL CONTRACTORS, INC. | HV | C | 06/06/2002 | Bath exhaust system and 2- water heater vents complete. | LYNNS | LYNNS | | HV | C | 2227410 |
COBB MECHANICAL CONTRACTORS, INC. | HI | C | 06/04/2002 | Correction made to raising gas line on roof and added a flange above ceiling on gas lint to Ansel. | LYNNS | LYNNS | | HI | C | 2227392 |
COBB MECHANICAL CONTRACTORS, INC. | HD | P | 06/04/2002 | Clearance to combustable corrected on grease duct. OK to fire wrap duct. | LYNNS | LYNNS | | HD | P | 2227386 |
COBB MECHANICAL CONTRACTORS, INC. | HI | P | 05/30/2002 | 60# test and design per approved plans, need to change union above ceiling at Ansel, need to raise gas line on roof to 6" off roof. | LYNNS | LYNNS | | HI | P | 2227382 |
COBB MECHANICAL CONTRACTORS, INC. | HD | P | 05/30/2002 | Need 3" clearance to combustables on grease duct through roof area. Need to see before wrap. | LYNNS | LYNNS | | HD | P | 2227375 |
COBB MECHANICAL CONTRACTORS, INC. | P= | C | 06/11/2002 | | JACK | JACK | | P= | C | 2227429 |
COBB MECHANICAL CONTRACTORS, INC. | P= | P | 06/10/2002 | 3 compartment has to be direct tie in, dishwasher has to have air gap, back flow on carbonator | JACK | JACK | | P= | P | 2227418 |
COBB MECHANICAL CONTRACTORS, INC. | PTO | C | 05/01/2002 | | JACK | JACK | | PTO | C | 2227370 |
COBB MECHANICAL CONTRACTORS, INC. | PB | C | 04/12/2002 | | JACK | JACK | | PB | C | 2227365 |
COBB MECHANICAL CONTRACTORS, INC. | PB | P | 04/02/2002 | restrooms and kitchen to grease trap complete | JACK | JACK | | PB | P | 2227359 |