GERALD H PHIPPS INC | B= | C | 02/13/2003 | | DANF | DANF | | B= | C | 2411997 |
GERALD H PHIPPS INC | B= | T | 02/12/2003 | PAID (REC#498639)TEMPERED SIDELITES OK; WIRE TRAYS NOT AS PER UL DETAIL FOR 1HR WALL | DANF | DANF | | B= | T | 2411993 |
GERALD H PHIPPS INC | B= | R | 02/10/2003 | CORRIDOR OK; TOP OF WALL OK; NEED UL DETAIL FOR CABLE TRAY; COMPLETE SIDELITE GLASS | DANF | DANF | | B= | R | 2411989 |
GERALD H PHIPPS INC | B= | R | 02/07/2003 | 1) MISSING TEMPERED GLASS AT SIDE LIGHTS 2) CORRIDOR ENCLOSURE NOT COMPLETE AT EAST DOOR 3) SPRAY TO OF RATED WALL ELECRTIC ROOM 4) COMPLETE FIRECAULKING | DANF | DANF | | B= | R | 2411986 |
GERALD H PHIPPS INC | B= | P | 02/05/2003 | EXIT PATH FROM 2ND FLOOR AREA 10 REINSTALLED | DANF | DANF | | B= | P | 2411982 |
GERALD H PHIPPS INC | BSP | T | 02/04/2003 | PAID (REC#497469)FIRE CAULKING AND TRAY PILLOWS NOT COMPLETED; ABOVE GRID AREA 10 OK | DANF | DANF | | BSP | T | 2411978 |
GERALD H PHIPPS INC | B= | P | 01/31/2003 | EGRESS PATH FROM 2ND FLOOR AREA 10 OK PER MEETING WITH ARTCHITECT AND BLAKE | DANF | DANF | | B= | P | 2411974 |
GERALD H PHIPPS INC | B= | R | 01/30/2003 | RECALL FRIDAY | DANF | DANF | | B= | R | 2411966 |
GERALD H PHIPPS INC | BSP | P | 01/30/2003 | WENT OVER TEMP EGRESS NEEDS FOR AREA 9; CONTRACTOR TO RECALL FRIDAY | DANF | DANF | | BSP | P | 2411969 |
GERALD H PHIPPS INC | BSP | T | 01/29/2003 | PAID (REC#496653)PAYMENT FOR SPECIAL PARTIAL BUILDING FINAL | JAN | JAN | | BSP | T | 2411958 |
GERALD H PHIPPS INC | BSP | R | 01/29/2003 | FIRECAULKING MISSING PILLOWS FOR TRAYS | DANF | DANF | | BSP | R | 2411961 |
GERALD H PHIPPS INC | BFR | C | 01/28/2003 | | DANF | DANF | | BFR | C | 2411953 |
GERALD H PHIPPS INC | BFR | P | 01/24/2003 | AREA 10 OK EXCEPT WEST COLUMNS WRAP | DANF | DANF | | BFR | P | 2411950 |
GERALD H PHIPPS INC | BSP | P | 01/22/2003 | ABOVE GRID FIRECAULK OK NORTH AND EAST WALL OK OUTSIDE OK; NEED INSIDE OF ELECTRICAL COMPLETED AND SOUTH AND WEST OUTSIDE WALLS | DANF | DANF | | BSP | P | 2411945 |
GERALD H PHIPPS INC | BFR | P | 01/21/2003 | FRAMING 1ST FLOOR WEST OF 2HR WALL OK; SEE SHEET A2.1 APPROVED PLANS | DANF | DANF | | BFR | P | 2411938 |
GERALD H PHIPPS INC | BFR | R | 01/17/2003 | RBD CANCEL | RICH | RICH | | BFR | R | 2411933 |
GERALD H PHIPPS INC | BFR | P | 01/16/2003 | NON RATED WALLS AREA 9, SEE APPROVED PLANS FOR MARKE AREA, 1ST AND 2ND FLOORS, CALLED JOHN AT 499-9334 , ACCESS THRU DOOR #13 LOADING DOCK | RICH | RICH | | BFR | P | 2411931 |
GERALD H PHIPPS INC | BFR | P | 01/15/2003 | 2ND FLOOR IS OK | DANF | DANF | | BFR | P | 2411926 |
GERALD H PHIPPS INC | BFR | P | 01/13/2003 | SEE APPROVED PLANS SHEET A2.1 AND A2.2 | DANF | DANF | | BFR | P | 2411923 |
GERALD H PHIPPS INC | BFR | P | 01/07/2003 | BATHROOMS OK; NEED HARDCEILINGS INSPECTION | DANF | DANF | | BFR | P | 2411918 |
GERALD H PHIPPS INC | BFR | P | 12/30/2002 | INFORMATION MANAGEMENT ROOMS AND ELECTRICAL ROOMS 1ST AND 2ND FLOOR; COLUMNS AND CHASESOK; OPENINGS BETWEEN FLOOR FRAMING OK; STILL NEED TO INSPECT BATHROOM AREAS AND CONFERENCE ROOMS; 2HR ROLLER DOOR | DANF | DANF | | BFR | P | 2411915 |
GREEN ELECTRIC INC | E= | C | 02/07/2003 | | MIKEC | MIKEC | | E= | C | 2412160 |
GREEN ELECTRIC INC | ER | P | 02/06/2003 | CONF. ROOMS CEILING AREA 10 | MIKEC | MIKEC | | ER | P | 2412154 |
GREEN ELECTRIC INC | E= | P | 02/05/2003 | FINAL AREA # 9, ER CEILINGS AREA # 10 | MIKEC | MIKEC | | E= | P | 2412150 |
GREEN ELECTRIC INC | ER | P | 02/04/2003 | FIRST FLOOR AERA # 9 POWER POLES | GARY | GARY | | ER | P | 2412146 |
GREEN ELECTRIC INC | ES | R | 02/03/2003 | NOT NEEDED | MIKEC | MIKEC | | ES | R | 2412142 |
GREEN ELECTRIC INC | E= | P | 02/03/2003 | LOWER LEVEL CEILING | MIKEC | MIKEC | | E= | P | 2412138 |
GREEN ELECTRIC INC | E= | P | 01/31/2003 | CALLED IN BY ACCIDENT | MIKEC | MIKEC | | E= | P | 2412129 |
GREEN ELECTRIC INC | ER | R | 01/31/2003 | CALLED IN BY ACCIDENT | MIKEC | MIKEC | | ER | R | 2412134 |
GREEN ELECTRIC INC | ER | P | 01/30/2003 | CEILING CLOUDS MAIN LEVEL | MIKEC | MIKEC | | ER | P | 2412126 |
GREEN ELECTRIC INC | E= | P | 01/30/2003 | FINAL 2ND FLOOR | MIKEC | MIKEC | | E= | P | 2412121 |
GREEN ELECTRIC INC | E= | P | 01/29/2003 | 2ND FLOOR | MIKEC | MIKEC | | E= | P | 2412116 |
GREEN ELECTRIC INC | E= | P | 01/28/2003 | 2ND FLOOR EXCEPT N.W. QUAD | MIKEC | MIKEC | | E= | P | 2412112 |
GREEN ELECTRIC INC | ER | P | 01/27/2003 | ROUGH AREA SEE PRINTS, FINAL ON ROOFTOP UNITS 2,3,5,6. PARTIAL FINAL ON 2ND FLOOR EAST HALF | MIKEC | MIKEC | | ER | P | 2412107 |
GREEN ELECTRIC INC | ER | P | 01/24/2003 | EAST END ALL BUT REC. IN POLES AND ROOF | RED | RED | | ER | P | 2412099 |
GREEN ELECTRIC INC | ER | P | 01/24/2003 | WALL AREA 10 | RED | RED | | ER | P | 2412104 |
GREEN ELECTRIC INC | ER | P | 01/23/2003 | CEILINGS SEE PRINTS | MIKEC | MIKEC | | ER | P | 2412091 |
GREEN ELECTRIC INC | ERS | P | 01/23/2003 | TEST | MIKEC | MIKEC | | ERS | P | 2412096 |
GREEN ELECTRIC INC | ER | P | 01/21/2003 | walls and ceilings see prints | MIKEC | MIKEC | | ER | P | 2412087 |
GREEN ELECTRIC INC | ER | P | 01/16/2003 | walls and ceilings see prints | MIKEC | MIKEC | | ER | P | 2412083 |
GREEN ELECTRIC INC | ER | P | 01/15/2003 | walls and ceilings, see highlighted areas | MIKEC | MIKEC | | ER | P | 2412078 |
GREEN ELECTRIC INC | ER | P | 01/14/2003 | walls and ceilings in highlighted areas. conduit sp2 to dp23. panels rp 23 d [ 1'2'3'4 ] rp2323e [ 1'2'3'4 ] | MIKEC | MIKEC | | ER | P | 2412075 |
GREEN ELECTRIC INC | ER | P | 01/13/2003 | | MIKEC | MIKEC | | ER | P | 2412070 |
GREEN ELECTRIC INC | ER | P | 01/10/2003 | walls and bathroom hard ceilings, see highlighted areas on prints | MIKEC | MIKEC | | ER | P | 2412067 |
GREEN ELECTRIC INC | ER | P | 01/07/2003 | see highlighted areas on prints | MIKEC | MIKEC | | ER | P | 2412062 |
GREEN ELECTRIC INC | ER | P | 12/30/2002 | walls [ see highlighted areas on prints ] | MIKEC | MIKEC | | ER | P | 2412059 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 02/03/2003 | | JOHNW | JOHNW | | H= | C | 2412041 |
HEATING & PLUMBING ENGINEERS, INC | HD | C | 02/03/2003 | | JOHNW | JOHNW | | HD | C | 2412046 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 01/30/2003 | 1ST FLOOR AREA 9 COMPLETE | JOHNW | JOHNW | | H= | P | 2412037 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 01/21/2003 | 2nd floor | JOHNW | JOHNW | | H= | P | 2412029 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 01/21/2003 | 2nd floor complete | JOHNW | JOHNW | | HD | P | 2412033 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 01/13/2003 | 2nd floor south end complete , the rest of 2nd floor above ceiling duct complete / 1st floor above ceiling rough ok | JOHNW | JOHNW | | HD | P | 2412025 |
HEATING & PLUMBING ENGINEERS, INC | HWP | C | 12/30/2002 | 1st floor piping complete | JOHNW | JOHNW | | HWP | C | 2412017 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 12/23/2002 | 1st floor med pressure duct ok / 2nd floor office area duct and low and med pressure duct rough in | JOHNW | JOHNW | | HD | P | 2412009 |
HEATING & PLUMBING ENGINEERS, INC | HWP | P | 12/20/2002 | 2nd floor piping inc. condensate | JOHNW | JOHNW | | HWP | P | 2412005 |
HEATING & PLUMBING ENGINEERS, INC | P= | C | 02/03/2003 | | LEE | LEE | | P= | C | 2412054 |
HEATING & PLUMBING ENGINEERS, INC | P= | P | 01/24/2003 | UPPER RESTROOMS MISSING PARTITIONS, STILL NEED LOWER RESTROOMS | LEE | LEE | | P= | P | 2412050 |
HEATING & PLUMBING ENGINEERS, INC | PTO | C | 12/31/2002 | | LEE | LEE | | PTO | C | 2412021 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 12/30/2002 | DWV ok except lower carrier nipples leaking, need all H20 | LEE | LEE | | PTO | P | 2412013 |
HEATING & PLUMBING ENGINEERS, INC | PB | C | 12/18/2002 | | LEE | LEE | | PB | C | 2412001 |