MEMORIAL HOSPITAL | HE16 | C | 05/13/2024 | WITNESSED TRACTION SAFETY TEST W/ROBERT AND TKE. | MATTM | MATTM | | HE16 | C | 8085642 |
MEMORIAL HOSPITAL | H06 | C | 05/13/2024 | WITNESSED TRACTION ELEVATOR SAFETY TESTING W/ TKE - MISSING FASCIA DOOR RESTRICTION COMPONENTS BETWEEN FLOORS 1 AND 2. NEED GOVERNOR ROPE DATA TAG INSTALLED. MH FACILITIES NEEDS TO DETERMINE IF ELEVATOR IS CONNECTED TO BUILDING GENERATOR POWER, IF SO, THE ELEVATOR OPERATION ON GENERATOR POWER NEEDS TO BE WITNESSED BY INSPECTOR W/ ELEVATOR MECHANIC PRESENT. PLEASE COORDINATE DATE AND TIME WITHIN 60 DAYS TO AVOID ELEVATOR RED TAG SHUTDOWN. (Receipt #2067303) | ROBERTV | ROBERTV | | H06 | C | 8093300 |
MEMORIAL HOSPITAL | H02 | C | 04/25/2024 | NO VISIT MADE DUE TO H06 SCHEDULED IN MAY (Receipt #2057222) | ROBERTV | ROBERTV | | H02 | C | 8064485 |
MEMORIAL HOSPITAL | H01 | C | 10/26/2023 | ANNUAL 6/23 -- OTIS W/ TKE SERVICE -- EMERGENCY LIGHT IS NONFUNCTIONAL -- STINGER ON BOTTOM OF COUNTERWEIGHT APPEARS TO BE COMPRESSING OIL/ SPRING RETURN BUFFER MORE THAN 25% (Receipt #2002394) | BENH | BENH | | H01 | C | 7900665 |
MEMORIAL HOSPITAL | HE16 | C | 06/01/2023 | ELEVATOR RECEIVED A RED TAG NOTIFICATION DUE TO THE CATEGORY 1 TESTING BEING OVER 60 DAYS PAST DUE. ELEVATORS SCHEDULED TO BE REMOVED FROM SERVICE ON 6/16/23. (cat 1 -- 6/23, emergency phone line dead and emergency light inoperable per report, red tag removed, DS) | DUSTINS | DUSTINS | | HE16 | C | 7760043 |
MEMORIAL HOSPITAL | H02 | C | 04/28/2023 | H02 -- 5 YEAR 4/19 -- ANNUAL 3/22 -- OTIS W/ TKE SERVICE -- / PPRBD RECORDS INDICATE ANNUAL TRACTION SAFETY TESTING IS PAST DUE, 30 DAYS PROVIDED FOR ANNUAL SAFETY TESTING TO BE COMPLETED TO AVOID RED TAG AND POSSIBLE SERVICE INTERRUPTION | DUSTINS | DUSTINS | | H02 | C | 7729967 |
MEMORIAL HOSPITAL | H01 | C | 10/31/2022 | ANNUAL 3/22 -- OTIS W/ TKE SERVICE -- CAB VANE NOT ENGAGING 2ND FLOOR HOISTWAY DOOR UPPER FLAG -- NEED TO ADD FLAGS ON FASCIA BETWEEN 1ST & 2ND FLOOR -- NEED TO CLEAN PITS -- NEED TO NUMBER HOISTWAY DOORS (Receipt #1910851) | BENH | BENH | | H01 | C | 7566992 |
MEMORIAL HOSPITAL | H02 | C | 04/25/2022 | HO2--5YR 04/2019-- ANNUAL 03/2022-- OTIS WITH TKE SERVICE AND LOCKBOX--/ ALARM BELL AND EMERGENCY LIGHTS WORKING PER MECHANICS REPORT | MIKEM | MIKEM | | H02 | C | 7350790 |
MEMORIAL HOSPITAL | H01 | C | 10/18/2021 | 5YR 04/2019-- ANNUAL 03/2021-- OTIS WITH TKE SERVICE AND LOCKBOX--/ MISSING PHASE 1 FIRE EMERGENCY OPERATOR INSTRUCTIONS AT MAIN LEVEL--/ MISSING IN CASE OF FIRE SIGNS AT MAIN LEVEL--/ EMERGENCY LIGHT AND BELL NON FUNCTIONAL WITHOUT 110 CAB CIRCUIT (Receipt #1815633) (cat 1 -- 3/2022) | MIKEM | MIKEM | | H01 | C | 7145342 |
MEMORIAL HOSPITAL | HE16 | C | 08/16/2021 | PERFORMED FOLLOW-UP INSPECTIONS: TRAVELING CABLES HAVE BEEN REPLACED. (NOTE: ELEVATOR TWO-WAY COMMUNICATION OPERATION TO BE CLOSELY MONITORED DUE TO INTERMITTENT PROBLEM WITH OPERATOR NOT CAPABLE OF HEARING PASSENGER, ELEVATOR SUBJECT TO BEING REMOVED FROM SERVICE ANY TIME TWO-WAY COMMUNICATION CANNOT BE ESTABLISHED) | ROBERTV | ROBERTV | | HE16 | C | 7073430 |
MEMORIAL HOSPITAL | H02 | C | 04/26/2021 | 5YR -- 4/19 -- CAT1 -- 3/21 -- OTIS W/ TKE SERVICE. TRAVELING CABLE SHEATHING CONDITIONS AND REPAIRS CONTINUE TO WORSEN. TRAVELING CABLES NEED REPLACED | ROBERTV | ROBERTV | | H02 | C | 6947686 |
MEMORIAL HOSPITAL | H01 | C | 10/22/2020 | 5YR -- 4/19 -- CAT1 --1/20 -- OTIS W/ TKE LOCKBOX AT TOP OF STAIRS. COULD NOT ESTABLISH TWO-WAY COMMUNICATION ON ELEVATOR PHONE EVEN AFTER MULTIPLE ATTEMPTS. THIS ISSUE HAS BEEN A PROBLEM IN THIS ELEVATOR FOR QUITE SOME TIME.....30 DAYS TO ADDRESS PROBLEM WITH ELEVATOR PHONE COMMUNICATION OR PPRBD WILL HAVE NO OTHER OPTION BUT TO PLACE ELEVATOR OUT OF SERVICE PENDING PERMANENT REPAIRS. ALSO, CAB MOUNTED DIRECTIONAL INDICATOR IS NOT SOUNDING WHEN CAR ARRIVES AT FLOOR. TRAVELING CABLE CONDITION HAS BECOME VERY POOR IN AREAS WHERE REPAIRS HAVE BEEN ALREADY MADE. NEED QUARTERLY EMERGENCY PHONE AND FIRE SERVICE TESTING LOGS ONSITE. (Receipt #1723927) (Update: Elevator phones have been ordered, traveling cables replacements are still questionable 1/22/2021 RV) cat 1 3/21 | ROBERTV | ROBERTV | | H01 | C | 6751862 |
MEMORIAL HOSPITAL | H02 | C | 04/02/2020 | 5 YEAR 4/19, CAT 1 1/20, OTIS, TKE LOCKBOX, HO2 | ERIC | ERIC | | H02 | C | 6530177 |
MEMORIAL HOSPITAL | H01 | C | 10/22/2019 | 5YR 4/19--OTIS W/ TKE SERVICE & LOCKBOX--EMERGENCY PHONE NOT WORKING CORRECTLY (OPERATOR ANSWERS BUT CANNOT HEAR PASSENGER)--TRAVELING CABLE SHEATHING CRACKING (Receipt #1639104) (Cat. 1 Performed 01/2020 - Emergency phone still not operable) | CALE | CALE | | H01 | C | 6375911 |
MEMORIAL HOSPITAL | H02 | C | 04/11/2019 | WITNESSED 5YR TRACTION SAFETY TEST W/ TKE 04/10/19 | CALE | CALE | | H02 | C | 6162270 |
MEMORIAL HOSPITAL | H06 | C | 04/11/2019 | WITNESSED 5YR TRACTION SAFETY TEST W/ TKE 04/10/19--OTIS W/ TKE LOCKBOX--EMERGENCY PHONE ANSWERS BUT OPERATOR CANNOT HEAR PASSENGER--TRAVELING CABLE SHEATHING IS CRACKING--1ST LEVEL HOISTWAY DOOR GIBB NEEDS REPLACING (Receipt #1589377) | CALE | CALE | | H06 | C | 6162264 |
MEMORIAL HOSPITAL | H01 | C | 10/03/2018 | 5YR -- 2/14 -- ANNUAL 10/17 -- OTIS W/ TKE LOCKBOX. TRAVELING CABLE SHEATHING IS CRACKING (Receipt #1543758) | ROBERTV | ROBERTV | | H01 | C | 5983884 |
MEMORIAL HOSPITAL | H02 | C | 04/17/2018 | 5YR 2/14- OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 5819027 |
MEMORIAL HOSPITAL | H01 | C | 10/09/2017 | 5YR -- 2/14 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING HAS YET TO BE PERFORMED AND MUST BE COMPLETED BY 10/31/2017. THE EMERGENCY PHONE HAS HAD INTERMITTENT PROBLEMS WHERE THE OPERATOR CANNOT HEAR THE PASSENGER FOR QUITE SOME TIME THAT HAS YET TO BE ADDRESSED AS WELL. ALSO, MISSING HOISTWAY DOOR RESTRICTOR FLAGS ON 2ND FLOOR. (Receipt #1457982 from 10/09/2017) | ROBERTV | ROBERTV | | H01 | C | 5648860 |
MEMORIAL HOSPITAL | H02 | C | 04/10/2017 | 5 YEAR 2/14 OTIS. TKE SERVICE, CAR DOOR GIBS NEED TO BE ADJUSTED OR REPLACED, NEED ANNUAL INSPECTION TEST TAGS AND INSPECTION FORMS | ERIC | ERIC | | H02 | C | 5470254 |
MEMORIAL HOSPITAL | H01 | C | 10/21/2016 | 5 YEAR 2/14 OTIS, TKE SERVICE AND LOCKBOX. NEED ANNUAL TEST TAG AND FORM (Receipt #1374426) | ERIC | ERIC | | H01 | C | 5324389 |
MEMORIAL HOSPITAL | H02 | C | 04/26/2016 | H02 | ROBERTV | ROBERTV | | H02 | C | 5184443 |
MEMORIAL HOSPITAL | H01 | C | 10/30/2015 | 5YR -- 2/14 -- OTIS W/ TKE LOCKBOX. EMERGENCY PHONE ANSWERS BUT OPERATOR CANNOT HEAR PASSENGER, RUN/STOP SWITCH USES UNKNOWN KEY, MISSING CATEGORY 1 TEST FORM AND TAG FOR 2/2015 (Receipt #1296485) | ROBERTV | ROBERTV | | H01 | C | 5069235 |
MEMORIAL HOSPITAL | H02 | C | 04/30/2015 | 5 YEAR 2/14 OTIS TKE SERVICE. SUSPENSION ROPES AND TRAVELING CABLE REPLACED. HO2 | ERIC | ERIC | | H02 | C | 4946954 |
MEMORIAL HOSPITAL | HE16 | C | 02/03/2015 | INSPECTION OF ROPES INDICATE WEAR AND BREAKAGE BEYOND NORMAL CONDITIONS PER ASME A17.6-2010 - ITEM 1.10.12 (c). ROPES NEED REPLACED AS SOON AS POSSIBLE AND ALSO FREQUENT MONITORING OF ROPES REQUIRED UNTIL REPLACEMENT PERFORMED | ROBERTV | ROBERTV | | HE16 | C | 4895717 |
MEMORIAL HOSPITAL | H01 | C | 10/21/2014 | 5YR 2-14 OTIS (Receipt #1227717) | TOM | TOM | | H01 | C | 4839369 |
MEMORIAL HOSPITAL | H02 | C | 04/14/2014 | WITNESSED 2/14 | ERIC | ERIC | | H02 | C | 4720015 |
MEMORIAL HOSPITAL | H06 | C | 02/06/2014 | WITNESSED 5 YEAR SAFETY INSPECTION. TRAVELING CABLE DAMAGED AND MUST BE REPAIRED/REPLACED, NEED CALL STATION FIRE SIGNS AT ALL LANDINGS (Receipt #1178426) | ERIC | ERIC | | H06 | C | 4684369 |
MEMORIAL HOSPITAL | H01 | C | 10/17/2013 | 5YR 11-08-OTIS (Receipt #1163873) | TOM | TOM | | H01 | C | 4633837 |
MEMORIAL HOSPITAL | H02 | C | 04/19/2013 | 5YR 11-08--OTIS | TOM | TOM | | H02 | C | 4515061 |
MEMORIAL HOSPITAL | H01 | C | 10/30/2012 | 5YR 11-08--OTIS (Receipt #1090883) | TOM | TOM | | H01 | C | 4412528 |
MEMORIAL HOSPITAL | H02 | C | 04/18/2012 | 5 YR 11-08--OTIS | TOM | TOM | | H02 | C | 4303457 |
MEMORIAL HOSPITAL | H01 | C | 10/05/2011 | 5 YR 11-08--OTIS--PHONE VOLUME NOW OK (Receipt #1009349) | TOM | TOM | | H01 | C | 4229069 |
MEMORIAL HOSPITAL | H02 | C | 04/08/2011 | 5YR 11-08--OTIS-NEED MORE PHONE VOLUME | TOM | TOM | | H02 | C | 4142485 |
MEMORIAL HOSPITAL | H01 | C | 10/01/2010 | 5YR-11-08--OTIS PHONE VOLUME IS NOT LOUD ENOUGH TO HEAR OPERATOR (Receipt #942667) | TOM | TOM | | H01 | C | 4064431 |
MEMORIAL HOSPITAL | H02 | C | 04/06/2010 | 5 YR 11-08--OTIS | TOM | TOM | | H02 | C | 3968388 |
MEMORIAL HOSPITAL | H01 | C | 10/01/2009 | OTIS AND LOCKBOX 5 YR 11/08 (Receipt #878872) | ERIC | ERIC | | H01 | C | 3892800 |
MEMORIAL HOSPITAL | H02 | C | 04/30/2009 | 5 YR 11-08--OTIS | TOM | TOM | | H02 | C | 3829769 |
MEMORIAL HOSPITAL | HE16 | C | 11/21/2008 | WITNESSED 5 YEAR TRACTION SAFETY TEST | ERIC | ERIC | | HE16 | C | 3794386 |
MEMORIAL HOSPITAL | H01 | C | 10/30/2008 | 5YR EXPIRED--LAST TEST 7-03--OTIS (Receipt #833277) | TOM | TOM | | H01 | C | 3762896 |
MEMORIAL HOSPITAL | H02 | C | 04/04/2008 | 5 YR 7-03 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 2591090 |
MEMORIAL HOSPITAL | H01 | C | 10/05/2007 | 5 YR 7-03 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 2591086 |
MEMORIAL HOSPITAL | H02 | C | 04/13/2007 | 5 YR 7-03 --- OTIS | LES | LES | | H02 | C | 2591084 |
MEMORIAL HOSPITAL | H01 | C | 10/05/2006 | 5 YR 7-03 --- OTIS | LES | LES | | H01 | C | 2591080 |
MEMORIAL HOSPITAL | H02 | C | 04/05/2006 | 5 YR 7-03 --- OTIS | LES | LES | | H02 | C | 2591077 |
MEMORIAL HOSPITAL | H01 | C | 10/28/2005 | 5 YR 7-03 --- OTIS | LES | LES | | H01 | C | 2591074 |
MEMORIAL HOSPITAL | H02 | C | 04/20/2005 | 5 YR 7-03 --- OTIS | LES | LES | | H02 | C | 2591071 |
MEMORIAL HOSPITAL | H01 | C | 10/26/2004 | 5 YR 7-03 --- OTIS | LES | LES | | H01 | C | 2591068 |
MEMORIAL HOSPITAL | H02 | C | 04/28/2004 | 5 YR 7-03 --- OTIS | LES | LES | | H02 | C | 2591064 |
MEMORIAL HOSPITAL | H01 | C | 10/13/2003 | INITIAL INSPECTION--PERMIT ISSUED | TOM | TOM | | H01 | C | 2591062 |