MEMORIAL HOSPITAL | H02 | C | 04/25/2024 | NO VISIT MADE DUE TO H06 SCHEDULED IN MAY (Receipt #2057223) | ROBERTV | ROBERTV | | H02 | C | 8064486 |
MEMORIAL HOSPITAL | H01 | C | 10/26/2023 | ANNUAL 6/23 -- OTIS W/ TKE SERVICE -- COULD NOT ESTABLISH TWO WAY COMMUNICATION -- NOTE: MONITOR ROUGED COUNTERWEIGHT ROPES BETWEEN 4TH & 5TH FLOOR FOR DIAMETERS (Receipt #2002390) | BENH | BENH | | H01 | C | 7900633 |
MEMORIAL HOSPITAL | HE16 | C | 06/01/2023 | ELEVATOR RECEIVED A RED TAG NOTIFICATION DUE TO THE CATEGORY 1 TESTING BEING OVER 60 DAYS PAST DUE. ELEVATORS SCHEDULED TO BE REMOVED FROM SERVICE ON 6/16/23. (cat 1 -- 6/23, red tag removed, DS) | DUSTINS | DUSTINS | | HE16 | C | 7760040 |
MEMORIAL HOSPITAL | H02 | C | 04/28/2023 | H02 -- 5 YEAR 4/19 -- ANNUAL 3/22 -- OTIS W/ TKE SERVICE -- / PPRBD RECORDS INDICATE ANNUAL TRACTION SAFETY TESTING IS PAST DUE, 30 DAYS PROVIDED FOR ANNUAL SAFETY TESTING TO BE COMPLETED TO AVOID RED TAG AND POSSIBLE SERVICE INTERRUPTION | DUSTINS | DUSTINS | | H02 | C | 7729979 |
MEMORIAL HOSPITAL | H01 | C | 10/31/2022 | ANNUAL 3/22 -- OTIS W/ TKE & LOCKBOX -- NEED TO CLEAN PITS -- NEED TO ADD FLAGS TO FASCIA BETWEEN 1ST & 2ND FLOOR -- 3RD FLOOR HOISTWAY DOOR GIBBS ARE WORN -- NEED TO CHECK DOOR OPERATOR CHAIN (Receipt #1910855) | BENH | BENH | | H01 | C | 7567013 |
MEMORIAL HOSPITAL | H02 | C | 04/25/2022 | HO2-- 5YR 04/2019-- ANNUAL 03/2022-- OTIS WITH TKE SERVICE AND LOCKBOX | MIKEM | MIKEM | | H02 | C | 7350779 |
MEMORIAL HOSPITAL | H01 | C | 10/18/2021 | 5YR 04/2019-- ANNUAL 03/2021-- OTIS WITH TKE SERVICE AND LOCKBOX--/ MISSING PHASE 1 FIRE EMERGENCY OPERATOR INSTRUCTIONS AT MAIN LEVEL--/ MISSING IN CASE OF FIRE SIGNS AT MAIN LEVEL (Receipt #1815635) (cat 1 -- 3/2022) | MIKEM | MIKEM | | H01 | C | 7145355 |
MEMORIAL HOSPITAL | HE16 | C | 08/16/2021 | PERFORMED FOLLOW-UP INSPECTIONS: TRAVELING CABLES HAVE BEEN REPLACED. (NOTE: ELEVATOR TWO-WAY COMMUNICATION OPERATION TO BE CLOSELY MONITORED DUE TO INTERMITTENT PROBLEM WITH OPERATOR NOT CAPABLE OF HEARING PASSENGER, ELEVATOR SUBJECT TO BEING REMOVED FROM SERVICE ANY TIME TWO-WAY COMMUNICATION CANNOT BE ESTABLISHED) | ROBERTV | ROBERTV | | HE16 | C | 7073362 |
MEMORIAL HOSPITAL | H02 | C | 04/26/2021 | 5YR -- 4/19 -- CAT1 -- 3/21 -- OTIS W/ TKE SERVICE. TRAVELING CABLE SHEATHING CONDITIONS AND REPAIRS CONTINUE TO WORSEN. TRAVELING CABLES NEED REPLACED. ELEVATOR EMERGENCY PHONE IS NOT WORKING NOW. | ROBERTV | ROBERTV | | H02 | C | 6947688 |
MEMORIAL HOSPITAL | H01 | C | 10/22/2020 | 5YR -- 4/19 -- CAT1 --1/20 -- OTIS W/ TKE LOCKBOX AT TOP OF STAIRS. EMERGENCY LIGHT AND ALARM BELL NOT WORKING. CAB MOUNTED DIRECTIONAL INDICATOR IS NOT SOUNDING WHEN CAR ARRIVES AT FLOOR. TRAVELING CABLE CONDITION HAS BECOME VERY POOR IN AREAS WHERE REPAIRS HAVE BEEN ALREADY MADE. NEED QUARTERLY EMERGENCY PHONE AND FIRE SERVICE TESTING LOGS ONSITE. (Receipt #1723928) cat1 3/21 | ROBERTV | ROBERTV | | H01 | C | 6751874 |
MEMORIAL HOSPITAL | H02 | C | 04/02/2020 | 5 YEAR 4/19, CAT 1 1/20, OTIS, TKE LOCKBOX, HO2 | ERIC | ERIC | | H02 | C | 6530182 |
MEMORIAL HOSPITAL | H01 | C | 10/22/2019 | 5YR 4/19--OTIS W/ TKE SERVICE & LOCKBOX--RBD NOTE: (MONITOR TRAVELING CABLE SHEATHING FOR CRACKS) (Receipt #1639106) (Cat. 1 Performed 01/2020) | CALE | CALE | | H01 | C | 6375921 |
MEMORIAL HOSPITAL | H02 | C | 04/11/2019 | WITNESSED 5YR TRACTION SAFETY TEST W/ TKE 04/10/19 | CALE | CALE | | H02 | C | 6162277 |
MEMORIAL HOSPITAL | H06 | C | 04/11/2019 | WITNESSED 5YR TRACTION SAFETY TEST W/ TKE 04/10/19--OTIS W/ TKE LOCKBOX--TRAVELING CABLE SHEATHING IS CRACKING (Receipt #1589379) | CALE | CALE | | H06 | C | 6162273 |
MEMORIAL HOSPITAL | H01 | C | 10/03/2018 | 5YR -- 2/14 -- ANNUAL 10/17 -- OTIS W/ TKE LOCKBOX. TRAVELING CABLE SHEATHING IS CRACKING (Receipt #1543757) | ROBERTV | ROBERTV | | H01 | C | 5983882 |
MEMORIAL HOSPITAL | H02 | C | 04/17/2018 | 5YR 2/14- OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 5819030 |
MEMORIAL HOSPITAL | H01 | C | 10/09/2017 | 5YR -- 2/14 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING HAS YET TO BE PERFORMED AND MUST BE COMPLETED BY 10/31/2017........... ALSO, MISSING HOISTWAY DOOR RESTRICTOR FLAGS ON 3RD FLOOR. | ROBERTV | ROBERTV | | H01 | C | 5648866 |
MEMORIAL HOSPITAL | H02 | C | 04/10/2017 | 5 YEAR 2/14 OTIS. TKE SERVICE, CAR DOOR GIBS NEED TO BE ADJUSTED OR REPLACED, NEED ANNUAL INSPECTION TEST TAGS AND INSPECTION FORMS | ERIC | ERIC | | H02 | C | 5470257 |
MEMORIAL HOSPITAL | H01 | C | 10/21/2016 | 5 YEAR 2/14 OTIS, TKE SERVICE AND LOCKBOX. NEED ANNUAL TEST TAG AND FORM (Receipt #1374427) | ERIC | ERIC | | H01 | C | 5324390 |
MEMORIAL HOSPITAL | H02 | C | 04/26/2016 | H02 | ROBERTV | ROBERTV | | H02 | C | 5184445 |
MEMORIAL HOSPITAL | H01 | C | 10/30/2015 | 5YR -- 2/14 -- OTIS W/ TKE LOCKBOX. RUN/STOP SWITCH USES UNKNOWN KEY, MISSING CATEGORY 1 TEST FORM AND TAG FOR 2/2015 (Receipt #1296487) | ROBERTV | ROBERTV | | H01 | C | 5069238 |
MEMORIAL HOSPITAL | H02 | C | 04/30/2015 | 5 YEAR 2/14 OTIS TKE SERVICE. SUSPENSION ROPES AND TRAVELING CABLE REPLACED. HO2 | ERIC | ERIC | | H02 | C | 4946955 |
MEMORIAL HOSPITAL | HE16 | C | 02/03/2015 | INSPECTION OF ROPES INDICATE WEAR AND BREAKAGE BEYOND NORMAL CONDITIONS PER ASME A17.6-2010 - ITEM 1.10.12 (c). ROPES NEED REPLACED AS SOON AS POSSIBLE AND ALSO FREQUENT MONITORING OF ROPES REQUIRED UNTIL REPLACEMENT PERFORMED | ROBERTV | ROBERTV | | HE16 | C | 4895721 |
MEMORIAL HOSPITAL | H01 | C | 10/21/2014 | 5YR 2-14 OTIS--SMALL AMOUNT OF WATER IN PIT-CK NEXT INSP (Receipt #1227718) | TOM | TOM | | H01 | C | 4839370 |
MEMORIAL HOSPITAL | H02 | C | 04/14/2014 | WITNESSED 2/14 | ERIC | ERIC | | H02 | C | 4720016 |
MEMORIAL HOSPITAL | H06 | C | 02/06/2014 | WITNESSED 5 YEAR SAFETY TEST. TRAVELING CABLE IS DAMAGED AND MUST BE REPLACED/REPAIRED, NEED CALL STATION FIRE SIGNS AT ALL LANDINGS (Receipt #1178423) | ERIC | ERIC | | H06 | C | 4684362 |
MEMORIAL HOSPITAL | H01 | C | 10/17/2013 | 5YR 4-11-OTIS (Receipt #1163874) | TOM | TOM | | H01 | C | 4633838 |
MEMORIAL HOSPITAL | H02 | C | 04/19/2013 | 5YR 11-08--OTIS | TOM | TOM | | H02 | C | 4515062 |
MEMORIAL HOSPITAL | H01 | C | 10/30/2012 | 5YR 11-08--OTIS (Receipt #1090885) | TOM | TOM | | H01 | C | 4412530 |
MEMORIAL HOSPITAL | H02 | C | 04/18/2012 | 5 YR 11-08--OTIS--PHONE IN CAR NOT WORKING | TOM | TOM | | H02 | C | 4304129 |
MEMORIAL HOSPITAL | H01 | C | 10/05/2011 | 5 YR 11-08--OTIS--PHONE IN CAR NOT WORKING (Receipt #1009350) | TOM | TOM | | H01 | C | 4229071 |
MEMORIAL HOSPITAL | H02 | C | 04/08/2011 | 5YR 11-08--OTIS | TOM | TOM | | H02 | C | 4142488 |
MEMORIAL HOSPITAL | H01 | C | 10/01/2010 | 5YR-11-08--OTIS PHONE INOP (Receipt #942668) | TOM | TOM | | H01 | C | 4064432 |
MEMORIAL HOSPITAL | H02 | C | 04/06/2010 | 5 YR 11-06--OTIS ALARM IN CAR INOP | TOM | TOM | | H02 | C | 3968390 |
MEMORIAL HOSPITAL | H01 | C | 10/01/2009 | OTIS AND LOCKBOX 5 YR 11/08. EMERGENCY PHONE DOES NOT WORK (Receipt #878873) | ERIC | ERIC | | H01 | C | 3892812 |
MEMORIAL HOSPITAL | H02 | C | 04/30/2009 | 5 YR 11-08--OTIS | TOM | TOM | | H02 | C | 3829770 |
MEMORIAL HOSPITAL | HE16 | C | 11/21/2008 | WITNESSED 5 YEAR TRACTION SAFETY TEST | ERIC | ERIC | | HE16 | C | 3794388 |
MEMORIAL HOSPITAL | H01 | C | 10/30/2008 | 5YR EXPIRED--LAST TEST 7-03--OTIS (Receipt #833278) | TOM | TOM | | H01 | C | 3762897 |
MEMORIAL HOSPITAL | H02 | C | 04/04/2008 | 5 YR 7-03 --- OTIS ELEV. AND LOCKBOX --- 1/2" CABLE | LES | LES | | H02 | C | 2591124 |
MEMORIAL HOSPITAL | H01 | C | 10/05/2007 | 5 YR 7-03 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 2591121 |
MEMORIAL HOSPITAL | H02 | C | 04/13/2007 | 5 YR 7-03 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 2591118 |
MEMORIAL HOSPITAL | H01 | C | 10/05/2006 | 5 YR 7-03 --- OTIS | LES | LES | | H01 | C | 2591115 |
MEMORIAL HOSPITAL | H02 | C | 04/05/2006 | 5 YR 7-03 --- OTIS | LES | LES | | H02 | C | 2591112 |
MEMORIAL HOSPITAL | H01 | C | 10/28/2005 | 5 YR 7-03 --- OTIS | LES | LES | | H01 | C | 2591109 |
MEMORIAL HOSPITAL | H02 | C | 04/20/2005 | 5 YR 7-03 --- OTIS --- PHONE INOP. | LES | LES | | H02 | C | 2591104 |
MEMORIAL HOSPITAL | H01 | C | 10/26/2004 | 5 YR 7-03 --- OTIS | LES | LES | | H01 | C | 2591103 |
MEMORIAL HOSPITAL | H02 | C | 04/28/2004 | 5 YR 7-03 | LES | LES | | H02 | C | 2591098 |
MEMORIAL HOSPITAL | H01 | C | 10/13/2003 | INITIAL INSPECTION-PERMIT ISSUED | TOM | TOM | | H01 | C | 2591097 |