COLORADO COMMERCIAL BLDRS. | B= | C | 11/15/2005 | | CURTIS | CURTIS | | B= | C | 2663196 |
COLORADO COMMERCIAL BLDRS. | B= | P | 02/23/2005 | SHELL AND COMMON SPACE ( CHANGED TO PARTIAL ELEVATOR ISSUES NOT CORRECTED DVAEL) | CHRISM | CHRISM | | B= | P | 2663189 |
COLORADO COMMERCIAL BLDRS. | BSP | P | 12/28/2004 | ABOVE GRID CEILING OK IN HALLS AND STAIR WELLS AND BATHROOMS | CHRISM | CHRISM | | BSP | P | 2663180 |
COLORADO COMMERCIAL BLDRS. | BSP | P | 12/22/2004 | FIRECHAULKING ABOVE GRID LINE, OK TO START CEILING, MISSED SOME AREAS, PROTECT STRUCT COLUMNS ABOVE CEILING AT EAST STAIRS | CHRISM | CHRISM | | BSP | P | 2663173 |
COLORADO COMMERCIAL BLDRS. | BSP | R | 12/21/2004 | FIREWALL INSPECTION, NO SUPER AROUND, NO ACCESS TO PLANS IN TRAILER | CHRISM | CHRISM | | BSP | R | 2663165 |
COLORADO COMMERCIAL BLDRS. | BFR | P | 10/27/2004 | COMMON AREA WALLS OK | CHRISM | CHRISM | | BFR | P | 2663157 |
COLORADO COMMERCIAL BLDRS. | BIN | C | 10/27/2004 | | CHRISM | CHRISM | | BIN | C | 2663149 |
COLORADO COMMERCIAL BLDRS. | BIN | P | 09/29/2004 | NEED DOCUMENTATION O WINDOW U-VALUES. | TIMS | TIMS | | BIN | P | 2663141 |
COLORADO COMMERCIAL BLDRS. | BIN | P | 09/27/2004 | SECOND FLOOR WALLS OK TO COVER | CHRISM | CHRISM | | BIN | P | 2663135 |
COLORADO COMMERCIAL BLDRS. | BSP | P | 09/22/2004 | FIRESTOP IN CURTAIN WALLS OK | CHRISM | CHRISM | | BSP | P | 2663127 |
COLORADO COMMERCIAL BLDRS. | BFR | P | 09/17/2004 | PICKED UP HILTI DETAIL FOR FIRESTOP AT FLOOR LINE DETAIL ON FILE | CHRISM | CHRISM | | BFR | P | 2663119 |
COLORADO COMMERCIAL BLDRS. | BFR | P | 09/13/2004 | NEED DETAIL FOR FIRESTOP AT FLOOR LINE, MISSED ROCK WOOL IN DBL STUDS AND ONE BAY WEST WALL | CHRISM | CHRISM | | BFR | P | 2663111 |
COLORADO COMMERCIAL BLDRS. | BFR | P | 09/07/2004 | OK HAT CHANNEL ON FIRST LEVEL | BLAINE | BLAINE | | BFR | P | 2663092 |
COLORADO COMMERCIAL BLDRS. | BLA | C | 09/07/2004 | | BLAINE | BLAINE | | BLA | C | 2663100 |
COLORADO COMMERCIAL BLDRS. | BSP | T | 09/02/2004 | PAID (REC#592575)ADDITIONAL PLAN REVIEW TIME: $50.000 From: RUSSELL Reised gas | RUSSELL | RUSSELL | | BSP | T | 2663083 |
COLORADO COMMERCIAL BLDRS. | BFR | P | 08/31/2004 | ROOF TRUSSES OK | CHRISM | CHRISM | | BFR | P | 2663076 |
COLORADO COMMERCIAL BLDRS. | BFR | P | 08/30/2004 | DRAFTSTOP IN TRUSSES OK, TRUSS REPAIRS OK-ENG ON FILE, MISSED LATERALS ON A-3 TRUSSES, HAT CHANNEL FIRST FLOOR EAST SIDE OF BUILDING OK | CHRISM | CHRISM | | BFR | P | 2663061 |
COLORADO COMMERCIAL BLDRS. | BLA | P | 08/30/2004 | NORTH HALF OK | CHRISM | CHRISM | | BLA | P | 2663068 |
COLORADO COMMERCIAL BLDRS. | BFR | R | 08/25/2004 | SEE NOTE ON CARD, MISSED SOME LATERALS, DBL H2.5 CLIPS REQUIURED ALL OVERHANGING TRUSSES, ENG REQ FOR TRUSS REPAIRS "A" AND "A4" S | CHRISM | CHRISM | | BFR | R | 2663051 |
COLORADO COMMERCIAL BLDRS. | BFR | R | 08/24/2004 | NEED COMPLETE TRUSS DETAILS AND ENG FOR TRUSS REPAIRS, DO NOT HANG ANY ROCK UPSTAIRS | CHRISM | CHRISM | | BFR | R | 2663043 |
COLORADO COMMERCIAL BLDRS. | BFR | R | 08/23/2004 | NO INSPECTION DONE ON TRUSSES, ENG REQUIRED FOR WEBS BROKEN-WEST SIDE JUST NORTH OF STAIR WELL, NEED WELDING CERTIFICATIONS FOR ALL WELDERS, | CHRISM | CHRISM | | BFR | R | 2663036 |
COLORADO COMMERCIAL BLDRS. | BFR | P | 08/09/2004 | PARTIAL FRAME FOR ROOF OVERHANG SOFFITS- NEED DRAFTSTOPS INSTALLED | BLAKE | BLAKE | | BFR | P | 2663026 |
COLORADO COMMERCIAL BLDRS. | BFR | P | 06/14/2004 | SECOND FLOR DECK OK TO POUR WELD CERT REQUIRED | CHRISM | CHRISM | | BFR | P | 2663018 |
COLORADO COMMERCIAL BLDRS. | BFD | C | 04/06/2004 | OK FOUNDATION WATERPROOFING. | BOBB | BOBB | | BFD | C | 2663005 |
COLORADO COMMERCIAL BLDRS. | BFI | C | 04/06/2004 | OK FOUNDATION INSULATION. | BOBB | BOBB | | BFI | C | 2663013 |
COLORADO COMMERCIAL BLDRS. | BSP | P | 04/01/2004 | SIX INTERIOR PADS AND ELEVATOR WALL OK, SEE PAGE S-1 APPROVED PLANS | CHRISM | CHRISM | | BSP | P | 2662997 |
COLORADO COMMERCIAL BLDRS. | BFT | P | 03/29/2004 | OK PADS FOR ELEVATOR SHAFT. | BOBB | BOBB | | BFT | P | 2662989 |
COLORADO COMMERCIAL BLDRS. | BFN | P | 03/29/2004 | OK FOUNDATION WALLS; 1 TO 14 ON C LINE & C TO G ON 1 LINE . SEE APPROVED PLANS. | BOBB | BOBB | | BFN | P | 2662982 |
COLORADO COMMERCIAL BLDRS. | BFT | P | 03/23/2004 | WEST WALL PADS, SEE SHEET S1, STAMPED PLANS | RICH | RICH | | BFT | P | 2662974 |
COLORADO COMMERCIAL BLDRS. | BFN | P | 03/18/2004 | NORTH AND EAST WALLS OK | CHRISM | CHRISM | | BFN | P | 2662966 |
COLORADO COMMERCIAL BLDRS. | BFN | R | 03/17/2004 | VERTS AT PILASTERS SHORT | CHRISM | CHRISM | | BFN | R | 2662949 |
COLORADO COMMERCIAL BLDRS. | BFT | P | 03/17/2004 | SOUTH WALL LINE PADS | CHRISM | CHRISM | | BFT | P | 2662957 |
COLORADO COMMERCIAL BLDRS. | BFT | P | 03/12/2004 | FOOTER PADS EAST WALL LINE OK | CHRISM | CHRISM | | BFT | P | 2662942 |
COLORADO COMMERCIAL BLDRS. | BFT | P | 03/11/2004 | FOOTER PADS NORTH WALL LINE OK | CHRISM | CHRISM | | BFT | P | 2662935 |
COLORADO COMMERCIAL BLDRS. | BFT | P | 03/08/2004 | ALL INTERIOR PADS OK | CHRISM | CHRISM | | BFT | P | 2662928 |
COLORADO COMMERCIAL BLDRS. | BFT | P | 03/04/2004 | PADS AT LINE 12 AND 13 OK | CHRISM | CHRISM | | BFT | P | 2662921 |
MEYER ELECTRIC | E= | C | 02/08/2005 | | BRET | BRET | | E= | C | 2662914 |
MEYER ELECTRIC | E= | P | 02/07/2005 | BATHROOM LIGHTS AND RECEPTALES, NEED COVER ON HAND HOLE FOR POLE, ROOFTOP GFCI NOT WORKING PROPERLY | BRET | BRET | | E= | P | 2662906 |
MEYER ELECTRIC | E= | R | 02/04/2005 | LABEL PANELS, NO POWER TO RECEPTACLES IN CORRIDOR, NO LIGHT IN STAIRWELL WEST, NO POWER TO ROOFTOP RECEPTACLE,SIGN AT STREET NOT INSTALLED, LIGHT FIXTURE AT EXTERIOR DOOR NOT INSTALLED , HAVE EXTERIOR LIGHTS ON FOR INSPECTION, WIRE WATER AS PER NEC 250.119, NEED TO HAVE ELECTRICAN PRESENT FOR NEXT INSPECTION | BRET | BRET | | E= | R | 2662898 |
MEYER ELECTRIC | ER | P | 01/24/2005 | CEILINGS OK THROUGH CORRIDOR 1ST AND 2ND FLOOR | BRET | BRET | | ER | P | 2662888 |
MEYER ELECTRIC | ER | P | 10/25/2004 | FIRST FLOOR LOBBY AND BATHROOMS, HARDLID IN BATHROOMS,PHONEROOM AND ELEVATOR ROOM, STAIRWELLS OK | BRET | BRET | | ER | P | 2662881 |
MEYER ELECTRIC | ER | P | 10/20/2004 | WEST STAIRWELL,2ND FLOOR HALL AND WEST BATHROOM | BRET | BRET | | ER | P | 2662874 |
MEYER ELECTRIC | ES | C | 10/11/2004 | COMMERCIAL SERVICE: 800 AMP 4/WIRE UG NEED TRANSFORMER OPEN FOR TERMINATIONS | BRET | BRET | | ES | C | 2662865 |
MEYER ELECTRIC | EUG | P | 09/09/2004 | PARKING LOT LIGHTS. | RON | RON | | EUG | P | 2662857 |
MEYER ELECTRIC | EUG | P | 04/30/2004 | UG IN BUILDING OK | BRET | BRET | | EUG | P | 2662849 |
HVAC SOLUTIONS, INC. | H= | C | 01/18/2005 | CORRECTIONS MADE. | LYNNS | LYNNS | | H= | C | 2663291 |
HVAC SOLUTIONS, INC. | H= | P | 01/13/2005 | NEED TO REMOVE BOLTS AS DISCUSSED WITH CONTRACTOR, NEED TO COMPLETE RETAINING ANGLES ON 4- F/S DAMPERS AND REMOVE FIRE CAULKING. | LYNNS | LYNNS | | H= | P | 2663283 |
HVAC SOLUTIONS, INC. | HD | P | 11/12/2004 | SHEET ROCK TOO TIGHT AROUND F/S DAMPER AT VAV-101, STILL NEED TO CORRECT BOLTS AND HANGERS FROM LAST INSPECTION. DO NOT CLOSE SHAFT UNTIL CONFIRMED BOLTS REMOVED. | LYNNS | LYNNS | | HD | P | 2663275 |
HVAC SOLUTIONS, INC. | HD | P | 10/07/2004 | ON 2ND FLOOR: REMOVE BOLTS FROM CORNERS, AT TDC/DUCTMATE, ON ALL F/S DAMPERS, COMPLETE CLIPS ON 102/26 RETURN DUCT, SEAL ALL DUCT ON EF-1, COMPLETE SEALING UPSTREAM AND DOWNSTREAM DUCT ON FAN POWER BOXES, NEED ADDITIONAL INTERMEDIATE SUPPORTR ON 102/26 ELBOWS. SEAL ALL DUCT FOR MEDIUM PRESSURE. | LYNNS | LYNNS | | HD | P | 2663268 |
HVAC SOLUTIONS, INC. | HD | P | 09/23/2004 | RISER DUCTS OK. NEED TO SEE FRAMING FOR FIRE/SMOKE DAMPERS IN SHAFT. | LYNNS | LYNNS | | HD | P | 2663260 |
DAVIS GAS SHOP INC | H= | C | 09/08/2004 | GAS FINAL. PLANS REVISED. | LYNNS | LYNNS | | H= | C | 2662841 |
DAVIS GAS SHOP INC | HC | C | 08/31/2004 | OK TO SET METER. | LYNNS | LYNNS | | HC | C | 2662825 |
DAVIS GAS SHOP INC | HI | C | 08/31/2004 | 60# TEST ON ELEVATED PRESSURE GAS AND SIZING OK. REVISE PLANS TO SHOW NEW METER LOCATION AND GAS PIPE ROUTE BEFORE FINAL. | LYNNS | LYNNS | | HI | C | 2662833 |
HOGAN MECHANICAL, INC. | P= | C | 02/03/2005 | | JACK | JACK | | P= | C | 2663353 |
HOGAN MECHANICAL, INC. | PTO | C | 10/26/2004 | SHELL ONLY | JEFF | JEFF | | PTO | C | 2663345 |
HOGAN MECHANICAL, INC. | PTO | P | 08/26/2004 | FUTURE DRAINS AND VENT STACKS X 4 OK | JEFF | JEFF | | PTO | P | 2663338 |
HOGAN MECHANICAL, INC. | PRD | C | 08/18/2004 | | LEE | LEE | | PRD | C | 2663329 |
HOGAN MECHANICAL, INC. | PTO | P | 08/12/2004 | DWV THROUGH FLOORS OK, CONTRACTOR TO RETEST, BUILDING DEPARTMENT TO DETERMINE FIRE ASSEMBLIES | JEFF | JEFF | | PTO | P | 2663321 |
HOGAN MECHANICAL, INC. | PRD | P | 08/12/2004 | TEST ON PRIMARY DRAINS AND DESIGN OK, NEED TO TEST OVERFLOW DRAINS | JEFF | JEFF | | PRD | P | 2663314 |
HOGAN MECHANICAL, INC. | PB | C | 04/21/2004 | | JEFF | JEFF | | PB | C | 2663299 |
HOGAN MECHANICAL, INC. | PRD | P | 04/21/2004 | UNDER SLAB OK | JEFF | JEFF | | PRD | P | 2663306 |
COLORADO COMMERCIAL BLDRS. | V= | C | 11/14/2005 | FINAL 0K --- ALL ITEMS CORRECTED | LES | LES | | V= | C | 2663244 |
COLORADO COMMERCIAL BLDRS. | V= | P | 02/25/2005 | NOT READY | LES | LES | | V= | P | 2663236 |
COLORADO COMMERCIAL BLDRS. | V= | P | 02/15/2005 | CALK AROUND HALLWAY DOOR 1ST FLOOR --- FIRE SEAL HOISTWAY DOORS BOTH FLOORS --- NEED SMOKE TEST --- REMOVE ACCESS PANEL FROM CEILING IN MACHINE ROOM | LES | LES | | V= | P | 2663229 |