COLARELLI CONSTRUCTION, INC. | B= | C | 11/03/2004 | | TERRYB | TERRYB | | B= | C | 2810608 | COLARELLI CONSTRUCTION, INC. | B= | P | 11/02/2004 | OK PENDING ELECTRIC FINAL | TERRYB | TERRYB | | B= | P | 2810638 | COLARELLI CONSTRUCTION, INC. | B= | R | 11/01/2004 | E= REQUIRED, FRONT DOORS AT RECEPTION / EXIT SIGN, POST .DOORS REMAIN OPEN SIGN, 1 HOUR LID REQUIRED AT ROOM #118, STORAGE, PROVIDE PROTECTION AT 2*4 LIGHT FIXTURES , AT 1 HOUR LID, DOOR SEALS AT REAR EXIT DOOR | RICH | RICH | | B= | R | 2810630 | COLARELLI CONSTRUCTION, INC. | BFR | C | 09/23/2004 | | TERRYB | TERRYB | | BFR | C | 2810624 | COLARELLI CONSTRUCTION, INC. | BFR | T | 09/14/2004 | PAID (REC#596046)NO APPROVED PLANS NO ELECTRIC PERMIT NO ELECTRIC INSPECTIONS | TERRYB | TERRYB | | BFR | T | 2810616 | RYBA ELECTRIC, INC. | E= | C | 11/02/2004 | CORRECTIONS MADE, THIS INSPECTION WAS PERFORMED ON 11/02. PERMIT AND PANEL SCHEDULES WERE BROUGHT DOWN TO RBD BY EC'S FOREMAN, NATE | GARYL | GARYL | | E= | C | 2810599 | RYBA ELECTRIC, INC. | E= | R | 11/01/2004 | 1) FLOOR BOXES NOT FINISHED, 2) MARK PANEL CIRCUITS, 3) MOVE FURNITURE WHERE NECESSARY 4) COMPUTOR RECEPT'S TO RE CHECK | GARYL | GARYL | | E= | R | 2810591 | RYBA ELECTRIC, INC. | ER | P | 10/29/2004 | ONLY 1 SECTION OF CEILING LEFT FOR INSPECTION, ALL THE REST OK TO COVER | GARYL | GARYL | | ER | P | 2810584 | RYBA ELECTRIC, INC. | ER | P | 10/28/2004 | CONTACT IS NATE AT 243-1446, ALL CEILINGS OK TO COVER EXCEPT RECEPTION AND BOARD RM AREAS | GARYL | GARYL | | ER | P | 2810575 | RYBA ELECTRIC, INC. | ER | P | 10/27/2004 | CEILINGS WENT OVER WITH EC'S FOREMAN-NATE OK TO COVER SEVERAL AREAS NOT READY CANNOT COVER | GARYL | GARYL | | ER | P | 2810567 | RYBA ELECTRIC, INC. | ER | P | 10/14/2004 | REST OF SOFFITTS OK TO CLOSE | GARYL | GARYL | | ER | P | 2810559 | RYBA ELECTRIC, INC. | ER | P | 10/08/2004 | WALLS OK TO COVER | GARYL | GARYL | | ER | P | 2810551 | RYBA ELECTRIC, INC. | ER | P | 10/06/2004 | SOFFITTS IN BOARD RM AND RECEPTION AREA OK TO COVER | GARYL | GARYL | | ER | P | 2810544 | RYBA ELECTRIC, INC. | ER | P | 09/30/2004 | SOFFITTS OK TO COVER IN P.M. | GARYL | GARYL | | ER | P | 2810535 | RYBA ELECTRIC, INC. | ER | P | 09/29/2004 | OK TO COVER FLOOR BOXES, ONE AREA ONLY | GARYL | GARYL | | ER | P | 2810528 | RYBA ELECTRIC, INC. | ER | P | 09/22/2004 | REST OF WALLS OK TO COVER | GARYL | GARYL | | ER | P | 2810520 | RYBA ELECTRIC, INC. | ER | P | 09/21/2004 | NORTH WALLS AND STORAGE WALLS ONLY | GARYL | GARYL | | ER | P | 2810513 | HVAC SOLUTIONS, INC. | H= | C | 10/28/2004 | | JACK | JACK | | H= | C | 2810678 | HVAC SOLUTIONS, INC. | H= | P | 10/27/2004 | NEED CORNERS WIRED ON RADIATION DAMPERS THROUGH OUT JOB. MISSING A HEAT RUN AND NEED TRANSFER AIR COMPLETED | JACK | JACK | | H= | P | 2810670 | HVAC SOLUTIONS, INC. | HD | C | 10/05/2004 | | JACK | JACK | | HD | C | 2810663 | HVAC SOLUTIONS, INC. | HD | P | 09/28/2004 | TRANFER FANS AND DUCT INSTALLED | JACK | JACK | | HD | P | 2810654 | HVAC SOLUTIONS, INC. | HD | P | 09/15/2004 | NEED TO SEE TRANSFER FANS WHEN INSTALLED, READY FOR INSULATION AND GRID | JACK | JACK | | HD | P | 2810646 | LANDMARK PLUMBING AND HEATING, INC. | P= | C | 11/01/2004 | | JACK | JACK | | P= | C | 2810506 | LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 09/28/2004 | | JACK | JACK | | PTO | C | 2810499 |
|
|