CRADDOCK DEVELOPMENT COMPANY, INC. | B= | C | 12/05/2005 | | CLOVIS | CLOVIS | | B= | C | 3064289 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFR | C | 12/05/2005 | FIRE CAULKING ABOVE CORRIDOR LID OK | CLOVIS | CLOVIS | | BFR | C | 3064282 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFN | C | 12/05/2005 | | CLOVIS | CLOVIS | | BFN | C | 3064274 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFT | C | 12/05/2005 | | CLOVIS | CLOVIS | | BFT | C | 3064265 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BSP | R | 11/22/2005 | 1 HR CORRIDOR ABOVE GRID: FIRE CAULK ALL WIRE PENETRATIONS AND AROUND EDGES OF SHEETROCK OVERLAY PATCHES | CLOVIS | CLOVIS | | BSP | R | 3064257 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFR | P | 11/22/2005 | CANOPY OVER HANG OK | CLOVIS | CLOVIS | | BFR | P | 3064249 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFR | P | 10/24/2005 | CENTER CORRIDOR FRAMING OK | CLOVIS | CLOVIS | | BFR | P | 3064242 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BSP | P | 10/24/2005 | FOUNTAIN FIRE DEPARTMENT HAS OK'D FOR TENENT FINISH | CLOVIS | CLOVIS | | BSP | P | 3064234 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BSP | P | 10/05/2005 | OK TO ALLOW TENANT FINISH OK ONLY AFTER FOUNTAIN FIRE DEPARTMENT APPROVAL | CLOVIS | CLOVIS | | BSP | P | 3064226 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFD | C | 10/05/2005 | STAMPED ENGINEERING LETTERS ON FILE | CLOVIS | CLOVIS | | BFD | C | 3064218 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFD | P | 08/24/2005 | LETTER CONTENT OK, HOWEVER IT NEEDS TO HAVE ENGINEER'S STAMP | CLOVIS | CLOVIS | | BFD | P | 3064209 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BSP | T | 06/24/2005 | PAID (REC#648512)ADDITIONAL PLAN REVIEW TIME: $50.000 From: RONW Michael made plan changes = okay | RONW | RONW | | BSP | T | 3064201 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFT | P | 06/21/2005 | (11) PIER CAPS OK, PIER CAPS COMPLETE | CLOVIS | CLOVIS | | BFT | P | 3064193 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFT | P | 06/06/2005 | CAISSONS: PENDING ENGINEER'S CAISSON LOG. REPRESENTITIVE FROM COLORADO ENGINEERING ON SITE | CLOVIS | CLOVIS | | BFT | P | 3064185 |
D & J QUALITY ELECTRIC INC | E= | C | 12/01/2005 | | TIMA | TIMA | | E= | C | 3064400 |
D & J QUALITY ELECTRIC INC | E= | R | 11/30/2005 | BOND POLE LIGHTS TO BRANCH CIRCUT GROUND,NEED ACCESS TO ROOF TO CHECK RTU,INSTALL LIGHTS FOR ENTRY SIGN | TIMA | TIMA | | E= | R | 3064393 |
D & J QUALITY ELECTRIC INC | ER | P | 11/21/2005 | CAN OPY-HALL CEILING | RED | RED | | ER | P | 3064385 |
D & J QUALITY ELECTRIC INC | E= | P | 11/21/2005 | A,LL BUT CANOPY-OUTSIDE LIGHTS-ROOF TOP UNIT | RED | RED | | E= | P | 3064377 |
D & J QUALITY ELECTRIC INC | ES | C | 10/31/2005 | COMMERCIAL SERVICE: 100 AMP 4/W HOUSE PANEL SERVICE NEEDS METER SET D & J QUALITY ELECTRIC | TIMA | TIMA | | ES | C | 3064361 |
D & J QUALITY ELECTRIC INC | ER | R | 10/31/2005 | NOT READY | TIMA | TIMA | | ER | R | 3064353 |
D & J QUALITY ELECTRIC INC | ER | P | 10/24/2005 | WALLS OK | TIMA | TIMA | | ER | P | 3064344 |
D & J QUALITY ELECTRIC INC | ES | P | 10/12/2005 | COMMERCIAL SERVICE: 800 AMP 4/W GUTTER NEED METER SET FOR 400 AMP 4/W D & J QUALITY ELECTRIC | TIMA | TIMA | | ES | P | 3064336 |
D & J QUALITY ELECTRIC INC | ES | R | 10/11/2005 | BOND WIRES NOT CORRECT SIZES,BOND NEUTRAL IN GUTTER,INSTALL BOND SCREW 400 AMP DISCONNECT,BOND CT CAN,OVER 6" IN FRONT OF EQUIPMENT ON GUTTER,BOND METER,NEED EQUIPMENT GROUND IN 2ND PARRALLEL RUN TO 400 AMP PANEL | TIMA | TIMA | | ES | R | 3064327 |
D & J QUALITY ELECTRIC INC | EUG | C | 09/21/2005 | NORTH SIDE SITE LIGHTING OK | TIMA | TIMA | | EUG | C | 3064319 |
D & J QUALITY ELECTRIC INC | EUG | R | 09/16/2005 | SOUTH SIDE SITE LIGHTING OK NORTH SIDE NOT DEEP ENOUGH NO PERMIT CARD | TIMA | TIMA | | EUG | R | 3064311 |
D & J QUALITY ELECTRIC INC | EUG | P | 08/17/2005 | SERVICE LATERAL OK SLAB OK | TIMA | TIMA | | EUG | P | 3064303 |
BUSCH MANNS MECHANICAL, LLC | H= | C | 11/01/2005 | | JIMV | JIMV | | H= | C | 3064417 |
CHUCK STEINHAUSER | H= | C | 11/01/2005 | | JIMV | JIMV | | H= | C | 3064473 |
CHUCK STEINHAUSER | HC | C | 11/01/2005 | | JIMV | JIMV | | HC | C | 3064465 |
CHUCK STEINHAUSER | HI | C | 11/01/2005 | | JIMV | JIMV | | HI | C | 3064457 |
BUSCH MANNS MECHANICAL, LLC | HD | C | 09/30/2005 | NEED APPROVED PLANS | JIMV | JIMV | | HD | C | 3064408 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 11/22/2005 | | JOEL | JOEL | | P= | C | 3064448 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 11/03/2005 | | JACK | JACK | | PTO | C | 3064441 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 09/13/2005 | | JIMV | JIMV | | PB | C | 3064432 |
LANDMARK PLUMBING AND HEATING, INC. | PB | P | 09/12/2005 | NEED 3" RISER AT END OF LINE FOR CLEANOUT TO SERVICE 4" TRUNK. | JIMV | JIMV | | PB | P | 3064424 |