EMERALD C.M., INC. | B= | C | 11/04/2005 | | CHRISM | CHRISM | | B= | C | 3054636 |
EMERALD C.M., INC. | B= | P | 11/03/2005 | ABOVE CEILING IN TOILET ROOM HOLE IN ONE HOUR WALL NEAR TOP PLATE / PLUMBING DRAIN NOT CONNECTED TO VENT THRU ROOF. ACCESS TO THIS INSPECTION IS THRU TOILET ROOM CEILING ABOVE LAVATORY. | LEEG | LEEG | | B= | P | 3054628 |
EMERALD C.M., INC. | BFR | C | 10/19/2005 | | CHRISM | CHRISM | | BFR | C | 3054620 |
EMERALD C.M., INC. | BFR | P | 10/04/2005 | OK 3' EXTENSION FOR X-RAY ROOM . OK LEADROCK ONE SIDE. | BOBB | BOBB | | BFR | P | 3054611 |
EMERALD C.M., INC. | B= | P | 09/09/2005 | FIRE FINAL PARTIALED OK FOR TCO, NEED TEST ON FIREALARM, NEED TO SEAL PENETRATIONS IN CORRIDOR WALL NOT MADE FOR THIS UNIT | CHRISM | CHRISM | | B= | P | 3054604 |
EMERALD C.M., INC. | B= | P | 09/09/2005 | FIREFINAL PARTIALED OK FOR TCO, NEED FIRE ALARM TEST, CONTRACTOR TO SEAL PENETRATIONS IN CORRIDOR WALL NORTH SIDE OF UNIT NOT MADE FOR THIS UNIT | CHRISM | CHRISM | | B= | P | 3054595 |
EMERALD C.M., INC. | BSP | P | 09/01/2005 | ABOVE GRID OK WITH THE EXCEPTION OF COLD AIR RETURN ABOVE THE RECEPTION OFFICE, NO SMOKE DAMPER INSTALLED ON TENANT FINISH SIDE | CHRISM | CHRISM | | BSP | P | 3054588 |
EMERALD C.M., INC. | BFR | P | 07/18/2005 | WALL FRAMING IN MRI ROOM | CHRISM | CHRISM | | BFR | P | 3054582 |
EMERALD C.M., INC. | BFR | P | 06/29/2005 | OK TO ROCK WALLS AFTER MECH ROUGHS, RETURN AIR THRU CORRIDOR WALL MUST BE ADDRESSED | CHRISM | CHRISM | | BFR | P | 3054575 |
WESTCO ELECTRIC, INC. | E= | C | 11/04/2005 | COMPLETED 11-3-05 | MATTHEW | MATTHEW | | E= | C | 3054513 |
Q-5 INC. | E= | C | 11/03/2005 | X-RAY EQUIP DISCONNECT AND J-BOX OK; EQUIP HOOK UP BY QUALIFIED TECH | MATTHEW | MATTHEW | | E= | C | 3054430 |
WESTCO ELECTRIC, INC. | E= | C | 11/03/2005 | TO COMPLETE WESTCO'S PERMIT | MATTHEW | MATTHEW | | E= | C | 3054505 |
Q-5 INC. | ER | C | 10/19/2005 | | MATTHEW | MATTHEW | | ER | C | 3054422 |
WESTCO ELECTRIC, INC. | EE | C | 09/21/2005 | ReOpened by MINDY | MINDY | MINDY | | EE | C | 3054499 |
WESTCO ELECTRIC, INC. | E= | P | 09/02/2005 | | MATTHEW | MATTHEW | | E= | P | 3054491 |
WESTCO ELECTRIC, INC. | E= | R | 09/01/2005 | INSTALL CORRECT BRKR AND INSTALL RIGHT SIDE UP AT PANEL LC-1, PANEL SCHEDULES, NEED DUAL LEVEL SWITCHING, #2 GEC TO XFMR, GRN BUSHINGS AT 480 V EQUIP | MATTHEW | MATTHEW | | E= | R | 3054482 |
WESTCO ELECTRIC, INC. | ER | P | 08/31/2005 | | MATTHEW | MATTHEW | | ER | P | 3054473 |
WESTCO ELECTRIC, INC. | ER | P | 08/19/2005 | CEILING IN MRI AND CAT SCAN ROOM OK TO COVER | MATTHEW | MATTHEW | | ER | P | 3054466 |
WESTCO ELECTRIC, INC. | ES | R | 07/18/2005 | | RED | RED | | ES | R | 3054457 |
WESTCO ELECTRIC, INC. | ER | P | 07/18/2005 | WALLS MRI RM | RED | RED | | ER | P | 3054455 |
WESTCO ELECTRIC, INC. | ER | P | 06/30/2005 | ALL WALLS EXCEPT MRI INNER SHELL WALL | MATTHEW | MATTHEW | | ER | P | 3054447 |
WESTCO ELECTRIC, INC. | ER | R | 06/29/2005 | NEED REDUNDANT GRN IN PATIENT CARE AREAS, SOME AREAS NOT FRAMED, STRAP MC 1 1/4'' BACK FROM FACE OF STUD | MATTHEW | MATTHEW | | ER | R | 3054440 |
ARMSTRONG HTG. & AIR COND. | H= | P | 10/13/2005 | Temp CO: NEED VENTS ON CONDENSATE DRAINS | ROLF | ROLF | | H= | P | 3054523 |
ARMSTRONG HTG. & AIR COND. | H= | C | 09/20/2005 | | JACK | JACK | | H= | C | 3054568 |
ARMSTRONG HTG. & AIR COND. | H= | L | 09/16/2005 | LOCKED AT 12:06 PM | JACK | JACK | | H= | L | 3054560 |
ARMSTRONG HTG. & AIR COND. | H= | P | 09/02/2005 | NEED SEPARATE OVERFLOW DRAINS FROM UNITS BACK TO FLOOR SINKS | JACK | JACK | | H= | P | 3054553 |
ARMSTRONG HTG. & AIR COND. | H= | P | 08/31/2005 | NEED VENTS ON CONDENSATE DRAINS | JACK | JACK | | H= | P | 3054547 |
ARMSTRONG HTG. & AIR COND. | HD | P | 08/12/2005 | READY TO INSULATE | JACK | JACK | | HD | P | 3054539 |
ARMSTRONG HTG. & AIR COND. | HV | P | 08/12/2005 | LACKING DROPS TO RESTROOMS | JACK | JACK | | HV | P | 3054530 |
KILPATRICK PLMBG & HTG | P= | C | 10/18/2005 | | JACK | JACK | | P= | C | 3054416 |
KILPATRICK PLMBG & HTG | PTO | C | 09/21/2005 | | JACK | JACK | | PTO | C | 3054409 |
KILPATRICK PLMBG & HTG | P= | P | 08/31/2005 | CHANGED TO PARTIAL TO ALLOW ADDITIONAL ATTACHMENT AND INSPECTION, KYE | JACK | JACK | | P= | P | 3054400 |
KILPATRICK PLMBG & HTG | PTO | C | 06/30/2005 | | JACK | JACK | | PTO | C | 3054392 |
KILPATRICK PLMBG & HTG | PB | C | 06/23/2005 | | JEFF | JEFF | | PB | C | 3054384 |
KILPATRICK PLMBG & HTG | PB | P | 06/22/2005 | NEED PROPER TRANSITION COUPLINGS AT ALL WASTE BRANCH CONNECTIONS, REST OK, FUTURE BATH ROUGH AND RISERS X 4 ADDED TO SCOPE OF WORK OK | JEFF | JEFF | | PB | P | 3054376 |