MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | B= | C | 12/14/2006 | ALL FINALS COMPLETE
| MIKE | MIKE | | B= | C | 3350383 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | C | 12/14/2006 | NATHAN COMPLETED OUTSTANDING FRAMING ITEMS ON 08-25-06
| MIKE | MIKE | | BFR | C | 3350378 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | B= | P | 09/24/2006 | Temp CO: FOR MCDONALDS ONLY | DAVEL | DAVEL | | B= | P | 3350337 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | B= | P | 08/25/2006 | MC DONALDS ONLY OK. FRAMING AT SOFFIT OVE MILK COOLERS CORRECTED. | NATHAN | NATHAN | | B= | P | 3350375 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | B= | R | 08/24/2006 | NEED TO CLEAR FRAMING INSPECTIONS NEED ALL OTHER FINALS | TERRYB | TERRYB | | B= | R | 3350370 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | R | 08/03/2006 | DELI SOFFIT FRAMING - COMPLETE SOFFIT FRAMING AS SPECIFIED ON SHEET GA5
| MIKE | MIKE | | BFR | R | 3350363 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | T | 08/02/2006 | PAID (REC#709253)DELI - NEED APPROVED PLANS | MIKE | MIKE | | BFR | T | 3350360 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | P | 07/03/2006 | VISION CENTER FRAMING OK | DANF | DANF | | BFR | P | 3350355 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | P | 06/30/2006 | VISION CENTER - NEED ELECTRIC/PLUMBING/HEAT INSPECTIONS,NEED DOUBLE TRIMMERS @ ALL DOOR HEADERS PER SECTION 3/VC1,SECURE TRIMMERS TO KING STUDS
| MIKE | MIKE | | BFR | P | 3350350 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | P | 06/27/2006 | MCDONALD'S FRAMING OK PENDING ENGINEERING FOR ATTACHMNENT OF 16' SOFFET TO ROOF DECK; CURRENTLY HAVE ONE SCREW EVERY 16"OC | DANF | DANF | | BFR | P | 3350346 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | R | 06/26/2006 | MISSING PLANS FOR MCDONALDS RESTURANT; ALSO NEED DETAIL FORM ARCHITECT FOR ATTACHMENT OF 16' SHEETROCK SOFFET TO ROOF DECK | DANF | DANF | | BFR | R | 3350342 |
WADDELL ELECTRIC | E= | C | 09/19/2006 | | BRET | BRET | | E= | C | 3350603 |
WADDELL ELECTRIC | E= | P | 09/18/2006 | BATHROOMS AND VISION CENTER OK, LABEL PANELS AND PANEL SCHEDULES, 2 AND 3 WIRES UNDER SAME SCREW IN TRANSFORMERS, INSTALL PLASTIC BUSHING IN SWITCHGEAR, INSTALL REQUIRED STRAPS AND SUPPORT ON CONDUIT FEEDING TRANSFORMER, INSTALL CORRECT SIZE EQUIPTMENT BONDING JUMPER IN TRANSFORMERS. | BRET | BRET | | E= | P | 3350601 |
WADDELL ELECTRIC | E= | P | 08/23/2006 | MCDONALDS OK | BRET | BRET | | E= | P | 3350594 |
WADDELL ELECTRIC | E= | R | 08/16/2006 | GFCI PROTECT OUTLETS THAT SERVE FOOD PREP AREAS, OPEN J-BOXES IN CEILING, 4 CLIPS OR 2 SCREWS IN ALL FIXTURES, MISSING 6 FIXTURES AND 1 SIGN, REMOVE RECEPTACLE FROM ABOVE CEILING, INSTALL BUSHINGS IN ALL TRANSFORMERS AND 0N REQUIRED SIZE CONDUITS, INSTALL BREAKER OR FILLERS ON ALL UN-USED OPENINGS | BRET | BRET | | E= | R | 3350592 |
WADDELL ELECTRIC | ER | P | 07/20/2006 | FRONT RESTROOMS ROUGH OK, VISION CENTER FINAL REJECTED INSTALL SUPPORT WIRES ON ALL FIXTURES, PANEL SCHEDULES, AND GFCI PROTECT PLUG MOLD IN LAB, NEED INSPECTION ON PHOTO LAB TRANSFORMER AND DISCONNECT, INDENTIFY NEUTRAL AND GROUNDS IN LAB PANEL | BRET | BRET | | ER | P | 3350584 |
WADDELL ELECTRIC | ER | R | 07/19/2006 | FREE CONDUCTORS LEAVING J-BOX IN BATHROOM GREEN BOARD ALREADY INSTALLED, CEILING NOT OPEN IN VISION CENTER . IF THERE IS A PROBLEM HAVING SOMEONE ON SITE SCHEDULE AN AFTER HOUR INSPECTION | BRET | BRET | | ER | R | 3350579 |
WADDELL ELECTRIC | E= | R | 07/17/2006 | INSTALL 2 BOLTS IN RECEPTACLES USED WITH INDUSTRAL COVERS , J-BOX OPEN IN CEILING, NEED PANEL LOCATION | BRET | BRET | | E= | R | 3350575 |
WADDELL ELECTRIC | E= | R | 07/12/2006 | VISION CENTER OK EXCEPT FOR POWER POLES PANEL SCHEDULES, GFCI PLUG MOLD AND HAVE CEILING OPEN , NEED CEILING ROUGH INSPECTION | BRET | BRET | | E= | R | 3350570 |
WADDELL ELECTRIC | E= | R | 07/11/2006 | ACCESS PANEL NOT INSTALLED MENS ROOM LEFT OF SINK CALL AHEAD # NOT IN SERVICE 3:30 PM | BRET | BRET | | E= | R | 3350566 |
WADDELL ELECTRIC | ER | P | 06/30/2006 | VISION CENTER WALLS ONLY | BRET | BRET | | ER | P | 3350560 |
WADDELL ELECTRIC | ER | R | 06/29/2006 | GROUNDS MUST BE MADE AND PIGTAILED WHERE MC IS BEING USED. | BRET | BRET | | ER | R | 3350556 |
WADDELL ELECTRIC | ER | P | 06/27/2006 | WALLS ONLY IN MACDONALDS AREA. | DAVID | DAVID | | ER | P | 3350551 |
WADDELL ELECTRIC | ER | P | 06/23/2006 | BATHROOMS WALLS AND CEILINGS OK NEED CEILING ACCEESS IN EAST BATHROOM LEFT SIDE OF SINK | BRET | BRET | | ER | P | 3350550 |
WADDELL ELECTRIC | ER | R | 06/22/2006 | CALLED NO ANSWER, NO ONE ON SITE 4:30 PM | BRET | BRET | | ER | R | 3350543 |
HORIZON SHEET METAL | H= | C | 12/11/2006 | RECIEVED BALANCE REPORT. | JON | JON | | H= | C | 3350474 |
HORIZON SHEET METAL | H= | P | 12/08/2006 | MET WITH KYLER AND HE WILL FAX BALANCE REPORT ON MONDAY. | JON | JON | | H= | P | 3350470 |
HORIZON SHEET METAL | H= | P | 08/24/2006 | PENDING BALANCE REPORTS ON ALL. REST OK | JON | JON | | H= | P | 3350466 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 08/23/2006 | REFRIGERATION ONLY | JON | JON | | H= | C | 3350417 |
HORIZON SHEET METAL | H= | P | 08/21/2006 | MCDONALDS, NEED BALANCE REPORT AND HOOD EXHAUST TO INTERLOCK WITH BOTH RTU'S PER NOTE #9 ON APPROVED PLANS. REST OK | JON | JON | | H= | P | 3350462 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 08/15/2006 | GAS FINAL ONLY | JON | JON | | H= | C | 3350394 |
HORIZON SHEET METAL | HD | P | 08/10/2006 | NEED TO REPAIR GREASE DUCT WRAP AS DISCUSSED, NEED BALANCE REPORTS ON STORE AND MCDONALD'S, NEED TO SEE MUA UNIT WORK ON ROOF, EF-4, 5 AND 6 DUCT AND GRILLES COMPLETE, TRANSFERS (6) WITH GRILLES COMPLETE, REGISTERS AND GRILLES OVER WALK-IN COOLERS COMPLETE. | LYNNS | LYNNS | | HD | P | 3350456 |
HORIZON SHEET METAL | HV | R | 08/02/2006 | NO FUEL BURNING VENTS SEEN AT THIS TIME. | JON | JON | | HV | R | 3350451 |
HORIZON SHEET METAL | HD | P | 08/02/2006 | OK FOR WRAP AT GREASE DUCT TRANSITION FITTING TO HOOD CONNECTION AND ROUGH DUCT OK FOR WRAP AT 2 RTU SYSTEMS ALL FOR MCDONALDS. | JON | JON | | HD | P | 3350448 |
OLSON PLUMBING & HEATING COMPANY | HI | P | 08/01/2006 | MEDIUM PRESSURE SIDE OF SYSTEM FOR MCDONALDS, 2- 1'' STUBS AND 1- 1 1/4'' STUB ON ROOF TO PENETRATIONS DOWN, OK | JON | JON | | HI | P | 3350391 |
RIAL HEATING AND AIR CONDITIONING, INC. | HRP | P | 07/28/2006 | UNDER FLOOR PIPING THROUGH CHASE OK, NEAR NEW WALK IN COOLER EXPANSION. | JON | JON | | HRP | P | 3350412 |
HORIZON SHEET METAL | H= | P | 07/21/2006 | DELI AREA FINAL IS COMPLETE BALANCE REPORT TO SCANNING. | JON | JON | | H= | P | 3350443 |
RIAL HEATING AND AIR CONDITIONING, INC. | HRP | P | 07/20/2006 | ALL NEW CIRCUITS NOW TESTED. JUST NEED TO SEE FINAL CONNECTIONS AND CONDENSATE. | JON | JON | | HRP | P | 3350409 |
HORIZON SHEET METAL | H= | P | 07/18/2006 | TYPE I HOOD IN DELI AREA FINAL. BALANCE REPORT BEING FAXED TO OFFICE. | LYNNS | LYNNS | | H= | P | 3350440 |
HORIZON SHEET METAL | HD | P | 07/14/2006 | SEE ORANGE CARD ATTATCHED TO PERMIT CARD FOR INSPECTION NOTES. (ALWAYS HAVE ON SITE) FOR VISION, MCDONALDS AND DELI. | JON | JON | | HD | P | 3350435 |
HORIZON SHEET METAL | HD | P | 07/13/2006 | CALL AHEAD TO CONTRACTOR IN FUTURE. VISION CENTER NOT READY NEEDS TILES REMOVED FOR INSPECTIONS. OK TO WRAP GREASE DUCT AT DELI. | JON | JON | | HD | P | 3350432 |
HORIZON SHEET METAL | HV | R | 07/13/2006 | NO VENTS READY | JON | JON | | HV | R | 3350425 |
RIAL HEATING AND AIR CONDITIONING, INC. | HRP | P | 07/12/2006 | NEED TO REVIEW APPROVED PLANS, OFFICE LOCKED UP..TEST OK ON 3 CIRCUITS... SHOULD HAVE NO NEW EQUIPMENT,,, USING EXISTING RACK SYSTEMS, ENLARGING COMPRESSORS. VERIFY WHEN PLANS AVAILIBLE... RBD NOTE: DOUBLE CHECK PLANS FOR ENTIRE SCOPE, TYPE ONE HOODS ETC. | JON | JON | | HRP | P | 3350402 |
RIAL HEATING AND AIR CONDITIONING, INC. | HRP | R | 07/11/2006 | NO CONTACT PERSON, NEED CALL AHEAD TO SOMEONE WHO CAN PROVIDE ACCESS TO PLANS AND BUILDING FOR INSPECTIONS. DID NOT FIND ANYONE. | JON | JON | | HRP | R | 3350399 |
VOGEL PLUMBING, INC. | P= | C | 11/06/2006 | FINAL ON DAIRY CASE. | MARTY | MARTY | | P= | C | 3350542 |
VOGEL PLUMBING, INC. | P= | P | 08/25/2006 | MCDONALDS | MARTY | MARTY | | P= | P | 3350536 |
VOGEL PLUMBING, INC. | P= | R | 08/24/2006 | PERSON I USUALLY MEET NOT THERE,DON'T KNOW WHAT SECTION TO LOOK AT. | MARTY | MARTY | | P= | R | 3350531 |
VOGEL PLUMBING, INC. | P= | P | 08/07/2006 | FRONT BATHROOMS,VTR AND BACKFLOW PREVENTER FOR PHOTO LAB,VTR FOR DAIRY CASE. | MARTY | MARTY | | P= | P | 3350527 |
VOGEL PLUMBING, INC. | PB+ | C | 07/27/2006 | ISLAND COOLER. | MARTY | MARTY | | PB+ | C | 3350522 |
VOGEL PLUMBING, INC. | P= | P | 07/13/2006 | FINAL ON VISION LAB. | MARTY | MARTY | | P= | P | 3350517 |
VOGEL PLUMBING, INC. | PTO+ | C | 07/13/2006 | ON PHOTO LAB,SEE 3" VTR ON FINAL. | MARTY | MARTY | | PTO+ | C | 3350514 |
VOGEL PLUMBING, INC. | PB | C | 07/06/2006 | | MARTY | MARTY | | PB | C | 3350509 |
VOGEL PLUMBING, INC. | PTO | C | 06/30/2006 | | MARTY | MARTY | | PTO | C | 3350506 |
VOGEL PLUMBING, INC. | PTO | P | 06/29/2006 | MCDONALDS. | MARTY | MARTY | | PTO | P | 3350501 |
VOGEL PLUMBING, INC. | PB | P | 06/28/2006 | NEED WRAPS. | MARTY | MARTY | | PB | P | 3350497 |
VOGEL PLUMBING, INC. | PTO | P | 06/28/2006 | NO TEST NEED WRAPS ON STACKS, NO PLASTIC IN RATED CEILING,STRAP VENTS,LOWER BACKFLOW TO EYE LEVEL. | MARTY | MARTY | | PTO | P | 3350493 |
VOGEL PLUMBING, INC. | PB | P | 06/23/2006 | GREASE LINE FOR MCDONALDS,PARTIAL PTO FOR REAR RESTROOMS REPLACING FIXTURES. | MARTY | MARTY | | PB | P | 3350489 |
VOGEL PLUMBING, INC. | PTO | R | 06/22/2006 | CALLED NUMBER DON'T KNOW WHAT THEY WANT. | MARTY | MARTY | | PTO | R | 3350485 |
VOGEL PLUMBING, INC. | PTO | T | 06/21/2006 | PAID (REC#703019)NO PLANS,NOT READY,TRIED TO CALL NUMBER DID NOT WORK,DON'T CALL TILL READY. | MARTY | MARTY | | PTO | T | 3350479 |