GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 04/24/2008 | | CHRISM | CHRISM | | B= | C | 3358880 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | C | 03/18/2008 | KUMAR AND ASSOC ENG COMPLIANCE AND WELD REPORT ON FILE | CHRISM | CHRISM | | BFR | C | 3359498 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFN | C | 03/18/2008 | KUMAR AND ASSOC ENG COMPLIANCE REPORTS ON FILE | CHRISM | CHRISM | | BFN | C | 3359490 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFT | C | 03/18/2008 | KUMAR AND ASSOC. ENG REPORT ON FILE | CHRISM | CHRISM | | BFT | C | 3359482 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 03/06/2008 | NEED FIRE FINAL, NEED ENG INSPECTION REPORTS TO SIGN OFF BFT,BFN,BFR | CHRISM | CHRISM | | B= | P | 3359473 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | BSP | T | 11/19/2007 | PAID (REC#795897)ADDITIONAL PLAN REVIEW TIME: $50.000 From: SHELBY | SHELBY | SHELBY | | BSP | T | 3360560 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 09/10/2007 | EMERGENCY ROOM AREA WALL FRAMING AND VAPOR BARRIER | CHRISM | CHRISM | | BFR | P | 3359463 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 08/22/2007 | GARDEN LEVEL, KITCHEN EXTERIOR WALL VAPOR BARRIER | CHRISM | CHRISM | | BIN | P | 3359455 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 08/07/2007 | FIRESAFE AT SLAB EDGE SOUTHWEST WINDOW WALL ALL FLOORS, CORE BOARD AT FUTURE ELEVATOR SHAFT SECOND AND THIRD FLOORS, ATRIUM SOFFIT FRAMING | CHRISM | CHRISM | | BSP | P | 3359446 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 07/20/2007 | THIRD FLOOR EAST QUARDANT VAPOR BARRIER | CHRISM | CHRISM | | BIN | P | 3359438 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 07/18/2007 | VAPOR BARRIER- THIRD FLOOR "F" WING NORTH EXTERIOR WALL,ELEVATOR LOBBY WINDOW WALL, SECOND FLOOR "B" WING | CHRISM | CHRISM | | BIN | P | 3359431 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 07/12/2007 | VAPOR BARRIER OK AT DIETITIONS OFFICE AREA GARDEN LEVEL | CHRISM | CHRISM | | BIN | P | 3359423 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 07/11/2007 | AREA OF THIRD FLOOR AO PAGE T0G3, VAPOR BARRIER OK AT ELEVATOR SHAFT TEN NOT USED AT THIS TIME | CHRISM | CHRISM | | BIN | P | 3359414 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 07/09/2007 | VAPOR BARRIER SECOND FLOOR "A" WING , THIRD FLOOR ELEVATOR FRONT WALL ELEVATORS 8 & 9. THIRD FLOOR VAPOR BARRIER SEE PAGE TG103 | CHRISM | CHRISM | | BIN | P | 3359407 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 07/02/2007 | VAPOR BARRIER SEE PAGE TG100 | CHRISM | CHRISM | | BSP | P | 3359400 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 06/28/2007 | THIRD FLOOR "E" WING EXTERIOR AND SNOW PIT INSULATION AND VAPOR BARRIER | CHRISM | CHRISM | | BSP | P | 3359392 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 06/25/2007 | SHAFT LINER WEST ELEVATOR ALL FLOORS - OK / VAPOR BARRIER WEST EXTERIOR WALL WATER ROOM OK | MICHAELA | MICHAELA | | BFR | P | 3358896 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 06/21/2007 | SEE SHEET A102 FOR SLAB EDGES AND POPOUTS AND FIRESPRAY | FRANK | FRANK | | BSP | P | 3359385 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 06/11/2007 | VAPOR BARRIER THIRD FLOOR "B" WING, SOFFIT FRAMING AT CHAPEL ROOF | CHRISM | CHRISM | | BSP | P | 3359377 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 06/11/2007 | SHAFTS #3 AND #4 CORE BOARD AT FIRST FLOOR, 6TH FLOOR ELEVATOR SHAFT WALLS CORE BOARD | CHRISM | CHRISM | | BSP | P | 3359369 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 06/06/2007 | UPPER VAPOR BARRIER C-D-E-F WINGS SECOND FLOOR | CHRISM | CHRISM | | BSP | P | 3359362 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 06/06/2007 | SLAB EDGE AT B-D-E-F WINGS SECOND FLOOR OK, SEE RBD PLAN TOG102 | CHRISM | CHRISM | | BSP | P | 3359354 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 06/01/2007 | SECOND FLOOR VAPPOR BARRIER AND FIRESAFE AT SLAB EDGE OK ALL BUT AT WINDOW WALLS WILL REQ NEW E.J. | CHRISM | CHRISM | | BSP | P | 3359345 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 05/25/2007 | CENTER CORE ELEVATOR SHAFTS FRONT WALL CORE BOARD OK 1ST 2ND 3RD FLOOR | CHRISM | CHRISM | | BFR | P | 3359338 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 05/25/2007 | VAPOR BARRIER THIRD FLOOR A WING | CHRISM | CHRISM | | BIN | P | 3359329 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 05/23/2007 | CORE BOARD AT ELEVATOR SHAFT WALLS GARDEN LEVEL | CHRISM | CHRISM | | BSP | P | 3359322 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 05/17/2007 | CEILING FRAMING AND INSULATION AT AMBULANCE BAY | CHRISM | CHRISM | | BFR | P | 3359313 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 05/11/2007 | VAPOR BARRIER D WING, FIRESAFE AT SLAB EDGE CHAPLE AND VESTIBULE ROOFS | CHRISM | CHRISM | | BIN | P | 3359306 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | R | 05/09/2007 | NOT READY | CHRISM | CHRISM | | BIN | R | 3359298 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 05/09/2007 | SECOND FLOOR SHAFTS 5-6-7-8, FIRST FLOOR HARDLID FRAMING AT AMBULANCE BAY | CHRISM | CHRISM | | BFR | P | 3359289 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 05/07/2007 | VAPOR BARRIER AND INSULATION COMPLETE FIFTH FLOOR, ELEVATOR CORE BOARD SHAFTS 1-2-3-4 FOURTH AND FIFTH FLOORS | CHRISM | CHRISM | | BIN | P | 3359278 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | R | 05/03/2007 | NOT READY | CHRISM | CHRISM | | BIN | R | 3359271 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 05/02/2007 | THIRD FLOOR C WING INSULATION AND VAPOR BARRIER, SIXTH FLOOR SLAB EDGE OK ALL BUT IN TEMP STORAGE ROOMS, FOURTH FLOOR PRESSURIZATION ROOMS FRAMING OK TO COVER | CHRISM | CHRISM | | BIN | P | 3359263 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BLA | C | 04/30/2007 | FRONT ENTRY WING WALLS COMPLETE LATH | CHRISM | CHRISM | | BLA | C | 3359255 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 04/30/2007 | INSULATION AND VAPOR BARRIER OK FIFTH FLOOR 45 WALLS, THIRD FLOOR EXTERIOR WALLS OK C WING NEED TO REINSPECT INTERIOR WALLS C WING LOTS OF FLOOR PENETRATIONS OK TO ONE SIDE WALLS | CHRISM | CHRISM | | BIN | P | 3359247 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 04/26/2007 | 45 WALL FIFTH FLOOR OK INSULATION AND VAPOR BARRIER | CHRISM | CHRISM | | BIN | P | 3359239 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 04/26/2007 | FIRESAFE AT SLAB EDGE A-B-C-D WINGS OK, NEED TO KEEP EYE ON SHOWER DRAIN FIRESTOPPING FIFTH FLOOR | CHRISM | CHRISM | | BSP | P | 3359231 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 04/20/2007 | SHAFT #8 THIRD FLOOR | CHRISM | CHRISM | | BSP | P | 3359223 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 04/19/2007 | VAPOR BARRIER AND INSULATION OK "A" WING | CHRISM | CHRISM | | BIN | P | 3359215 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 04/19/2007 | SHAFTS 3 & 4 ON SECOND FLOOR, ELEVATOR SHAFT WALL CORE BOARD FIFTH FLOOR #5-6-7. | CHRISM | CHRISM | | BFR | P | 3359207 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BLA | P | 04/17/2007 | OK AT EAST WALL OF CHAPEL | CHRISM | CHRISM | | BLA | P | 3359199 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 04/16/2007 | FIRESAFE COMPLETE AT FLOOR EDGE FIFTH FLOOR INCLUDING CURTAIN WALLS | CHRISM | CHRISM | | BSP | P | 3359190 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 04/05/2007 | SHAFTS 5-6-7 ON THIRD FLOOR OK CORE BOARD | CHRISM | CHRISM | | BSP | P | 3359183 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 03/30/2007 | VAPOR BARRIER 5D - OK TO COVER | MICHAELA | MICHAELA | | BIN | P | 3359175 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 03/23/2007 | FIRESAFE AT FLOOR EDGE FIFTH FLOOR "A" WING | CHRISM | CHRISM | | BSP | P | 3359167 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 03/21/2007 | INSULATION AND VAPOR BARRIER AT FOURTH FLOOR COMPLETE, SHAFT #8 FOURTH FLOOR COMPLETE | CHRISM | CHRISM | | BIN | P | 3359159 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 03/20/2007 | | GARY | GARY | | BFR | P | 3359151 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 03/19/2007 | SHAFTS 1 AND 2 THIRD FLOOR, SHAFTS 5-7-8 FOURTH FLOOR | CHRISM | CHRISM | | BSP | P | 3359143 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 03/19/2007 | INSULATION AND VAPOR BARRIER AT ATTRIUM SOFFIT AND FOURTH FLOOR "B"-"C"-"D" WINGS | CHRISM | CHRISM | | BIN | P | 3359135 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BLA | P | 03/16/2007 | WEST SIDE FIN WALLS THIRD FLOOR TO ROOF | CHRISM | CHRISM | | BLA | P | 3359127 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 03/15/2007 | SHAFT #8 SIXTH FLOOR , LATH AT NORTH WEST SIDE FIN WALLS | CHRISM | CHRISM | | BSP | P | 3359119 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BLA | P | 03/13/2007 | OK AT SNOW PIT #2 THIRD FLOOR | CHRISM | CHRISM | | BLA | P | 3359111 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 03/13/2007 | SHAFTS 1-2-6 FOURTH FLOOR , ABOVE CEILING SHAFT 8 FIFTH FLOOR, FIRESAFE AT ROOF LINES COMPLETE E AND F WINGS | CHRISM | CHRISM | | BSP | P | 3359103 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 03/12/2007 | FOURTH FLOOR "D" WING INSULATION AND VAPOR BARRIER | CHRISM | CHRISM | | BSP | P | 3359095 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BLA | P | 03/08/2007 | WALL OF WEST SNOW PIT THIRD FLOOR SEE PAGE A103 | CHRISM | CHRISM | | BLA | P | 3359087 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 03/08/2007 | FIRESAFE AT SLAB EDGES FOURTH FLOOR AND ROOF ABOVE THIRD FLOOR AND EMERGENCY ENTRANCE ROOF SEE PAGE A104 CORE AND SHELL SET | CHRISM | CHRISM | | BSP | P | 3359079 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BIN | P | 03/06/2007 | EXTERIOR WALL AT ELECTRIC ROOM FOURTH FLOOR OK | CHRISM | CHRISM | | BIN | P | 3359070 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 03/06/2007 | FIRESAFE AT TOP ROOF LINE COMPLETE, SHAFTS AT FIFTH AND SIXTH FLOORS COMPLETE ALL BUT SHAFTS #8 BOTH FLOORS, | CHRISM | CHRISM | | BSP | P | 3359060 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 02/28/2007 | FIRESAFE AT SLAB EDGE FIFTH FLOOR AREAS C & D OK, FOURTH FLOOR AT ELECTRICAL ROOM OK | CHRISM | CHRISM | | BSP | P | 3359052 |
OLSON PLUMBING & HEATING COMPANY | BSP | T | 02/28/2007 | PAID (REC#739246)ADDITIONAL PLAN REVIEW TIME: $50.000 From: DARYL Reconfigure plumbing base | DARYL | DARYL | | BSP | T | 3359740 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 02/22/2007 | FIRESAFE AT ROOF FRONT WING WALL, AND WORK AREA "D", INSULATION AND VAPOR BARRIER AT FOURTH FLOOR AREA "C" | CHRISM | CHRISM | | BSP | P | 3359043 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 02/16/2007 | COREBOARD AND FRAMING INTERIOR SHAFTS #1 AND #2 FIFTH FLOOR, SEE PAGE A105 RBD SET | CHRISM | CHRISM | | BSP | P | 3359035 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 02/08/2007 | FIRESAFE AT" B" ROOF AND PART OF" A" ROOF | CHRISM | CHRISM | | BSP | P | 3359028 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 02/07/2007 | CORE BOARD INSPECTION ON THE 4TH FLOOR SHAFT AROUND THE LOUVER OK,--- FIRE SAFING AND HILTI FIREPROOF SPRAY ALONG THE ROOF PARAPET OK. ( SEE AREA LIGHLIGHTED IN YELLOW ) | ED | ED | | BSP | P | 3359019 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 02/06/2007 | FIRESAFE SPRAY OK AT FOURTH FLOOR "C " WING SEE RBD PLANS | CHRISM | CHRISM | | BSP | P | 3359010 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 01/30/2007 | PRESSURIZATION ROOMS ARES C AND D FOURTH FLOOR, FRAMING AT FOURTH FLOOR ELECTRICAL AND TELECOM ROOMS | CHRISM | CHRISM | | BFR | P | 3359002 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 01/30/2007 | FIRESAFE OK AT FLOOR LINE IN MOCKUP ROOM FIFTH FLOOR, SHAFT THREE FOURTH FLOOR OK | CHRISM | CHRISM | | BSP | P | 3358994 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BLA | P | 01/29/2007 | WALL OVER KITCHEN ROOF OK, SEE PAGE A205 | CHRISM | CHRISM | | BLA | P | 3358986 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 01/26/2007 | FIRECHAULK AT SHAFTS 3 AND 4 SIXTH FLOOR SEE RBD SET | CHRISM | CHRISM | | BSP | P | 3358978 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 01/26/2007 | FIRESAFE AT ROOF EDGE SOUTH WALL AREA "A", ROOF EDGE AT FIRST FLOOR KITCHEN ROOF SEE RBD SET | CHRISM | CHRISM | | BSP | P | 3358970 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 01/24/2007 | FIRESAFE AT ROOF DECK AREA "C" OK, INTERIOR LARGE SHAFT AREA "C" /PAGE A105 RBD SET | CHRISM | CHRISM | | BSP | P | 3358962 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 01/23/2007 | "C" SIDE OF CENTERAL AIR SHAFT OK TO ROCK, RECIEVED ENGINEER JUDGEMENT FIRESTOP DETAIL FOR FLOOR EDGE AT CURTAIL WALL CONNECTIONS | CHRISM | CHRISM | | BSP | P | 3358954 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BLA | P | 01/18/2007 | OK EAST WALL ABOVE FRONT ENTRY SECOND FLOOR TO ROOF | CHRISM | CHRISM | | BLA | P | 3358946 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BLA | P | 01/10/2007 | SEE ELEVATION PAGE | CHRISM | CHRISM | | BLA | P | 3358939 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 01/09/2007 | FIRESAFE AT FLOOR #4 AREA C EAST AND WEST CURTAIN WALLS OK TO SPRAY, SHAFT #4 AREA C FLOORS 1 THRU 5 OK | CHRISM | CHRISM | | BSP | P | 3358933 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 01/05/2007 | SEE PLAN PAGE 107 FOR FIRESAFE OK | CHRISM | CHRISM | | BSP | P | 3358926 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 12/28/2006 | FIRESTOP AT ROOF LINE SOUTH WING | CHRISM | CHRISM | | BSP | P | 3358919 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | R | 12/12/2006 | JOB BOSS CALLED INSPECTION FORCONFUSION OF WHETHER TO CALL INSPECTION FOR EXTERIOR VANEER FRAMING BEFORE LATH IN SPECTION. WILL CONSULT WITH JIM PEPPER FOR ANSWER. | TIMS | TIMS | | BFR | R | 3358912 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFT | P | 07/19/2006 | OK FOR KUMAR AND ASSOCIATES TO PERFORM BFT AND BFN. SEE IMAGES FOR LETTER. | CURTIS | CURTIS | | BFT | P | 3358904 |
MORTON ELECTRIC INC | E= | C | 04/09/2008 | CONTROLL WIRING FOR DEISEL TANKS | SHELBY | SHELBY | | E= | C | 3360834 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 04/03/2008 | | SHELBY | SHELBY | | E= | C | 3360811 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 03/11/2008 | cielings 301 | THOMAS | THOMAS | | ER | P | 3360804 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 01/08/2008 | PANEL UPS4LDP AND UPS BATTERY BOX | SHELBY | SHELBY | | ER | P | 3360796 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 11/20/2007 | PANELS EL1B AND EL1A | SHELBY | SHELBY | | EP | P | 3360788 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EUG | P | 10/25/2007 | CONDUIT FOR LIGHTS IN HEALING GARDEN OK | SHELBY | SHELBY | | EUG | P | 3360779 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 10/18/2007 | FOR 10/17 AND 10/18 THE FOLLOWING GEAR ON 4TH FLOOR HWCP 1,2,3,4,5,6---SPF 1,2,3,4,5---AHU'S2,4,5,6 A AND B---RF1,2,3,4,5 A AND B---P-1 AND P-1-2 (SPF 1,2,3,4,5 ARE NOT ASSIGNED TO THE CORRECT PANEL ON THE APPROVED PLAN THEREFORE THEY ARE NOT MARKED BUT HAVE BEEN INSPECTED) | SHELBY | SHELBY | | ER | P | 3360770 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 10/16/2007 | VFD,S FOR AHU,S 1,2,3,4 A AND B | SHELBY | SHELBY | | ER | P | 3360759 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 10/11/2007 | THE FOLLOWING PANELS OK NL1 A,B,C,D---NH1 A,A1---CL1 A,B,D,E,F---CH1 A,B---UPSGL---EH1A,EL1D,EL1E---LH1A---LL1 A,B,D,E | SHELBY | SHELBY | | EP | P | 3360751 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 09/28/2007 | THE FOLLOWING GEAR OK AS MARKED ON TE 300,301,302,303---NL2B,NL2C,NL2D,NL2E,NL2F,NLGB,NLGA,NHGA,NHGA1,NHGA,NLGKA,NLGKB,ELGB,ELGC,ELGA,EHGA,CL2B,D,E,F,G,CL2OR1,2,3,4EL2B,D,ECLGA,B,C,GHGA,UPS3L,UPS2L,UPSGL | SHELBY | SHELBY | | EP | P | 3360742 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 09/26/2007 | PACKING OK | SHELBY | SHELBY | | ER | P | 3360736 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | R | 09/25/2007 | NEED PACKING INSPECTION FOR SEAL OFFS BEHIND NATIRAL GAS METERS---ALL THIS EQUIPMENT APPEARS TO BE IN USE AT THIS TIME.ELECTRICAL CONTRACTOR HAS BEEN ALERTED TO THE PROBLEM AND WILL SCHEDULE AN INSPECTION ON 9/26/7 | SHELBY | SHELBY | | EP | R | 3360728 |
MORTON ELECTRIC INC | ER | C | 09/21/2007 | MONITORING CONDUIT BETWEEN DEISEL TANKS AND BUILDING | SHELBY | SHELBY | | ER | C | 3360826 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 09/17/2007 | THE FOLLOWING PANELS AND THE TRANSFORMERS THAT ENERGIZE THEM ARE OK; NL3 A,B,D,E,NH3A,NH3A1,CL30R1,CL30R2,CL3A,B,C,D,E,F,G,EL3 A,B,D,E,EH3A AS MARKED ON TE 301,302,303 | SHELBY | SHELBY | | ER | P | 3360720 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/29/2007 | UPS4LDP OK | SHELBY | SHELBY | | ER | P | 3360712 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/23/2007 | EQUIPMENT AS MARKED ON TE 300,301 | SHELBY | SHELBY | | ER | P | 3360703 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 08/21/2007 | THE FOLLOWING ITEMS AS MARKED ON TE 300 AND TE301 CPNHG2,CPNLG2,NHSDBH1,ATS DZT,CPEH,CPELG1,MPB,UPSCLP,CPNHG2,TCPHHL2,CPNLG2,NHSDBH1 | SHELBY | SHELBY | | ER | P | 3360695 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 08/16/2007 | THE FOLLOWING GEAR AS MARKED ON TE 301-304---ATS-H1C,CHSDB-H1,ATS-H1C,CHSBD-H1,EDBH,EDP,EMDC-1,GENERATOR 1,GENERATOR 2 | SHELBY | SHELBY | | EP | P | 3360687 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EUG | P | 07/30/2007 | UNG BETWEEN BUILDING AT SOUTH SIDE OF LOADING DOCK TO STUB UP AT END OF DRIVEWAY JUST OVER CURB ON SOUTH SIDE | SHELBY | SHELBY | | EUG | P | 3360679 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 07/30/2007 | GEAR AS MARKED ON TE 503 | SHELBY | SHELBY | | EP | P | 3360656 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EUG | P | 07/26/2007 | NEED TO VERIFY DEPTH OF TRENCH | SHELBY | SHELBY | | EUG | P | 3360649 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 07/26/2007 | ON SHEET TE 300 B1CP,B2CP OK---GEAR MARKED IN ORANGE ON SHEETS TE 301,302,303,304 OK THIS DATE(SLE 7/26/7 IS S726) | SHELBY | SHELBY | | EP | P | 3360641 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 07/25/2007 | THE FOLLOWING GEAR OK---OVERCURRENT PROTECTION AND TERMINATIONS AS MARKED ON TE 300 CH1CP,CH2CP,CP1CP,CP2CP,CT1CP,CT2CP,CWP1CP,CWP2CP,HWP1CP,HWP2CP,DA1CP,DA2CP | SHELBY | SHELBY | | EP | P | 3360633 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EUG | P | 07/24/2007 | EUG FOR LANDSCAPE LIGHTING AND IRRIGATION ON SOUTHEAST SIDE OF LOADING DOCK AREA OK FROM BUILDING TO END OF PERPENDICULAR PORTION OF DRIVEWAY | SHELBY | SHELBY | | EUG | P | 3360625 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 07/24/2007 | ELECTRICAL GEAR HIGHLIGHTED IN ORANGE SHEETS TE 301,302,303,304 OK THIS DATE | SHELBY | SHELBY | | EP | P | 3360617 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 07/23/2007 | GEAR MARKED ON TE 300 AND TE301 IN ORANGE OK THIS DATE | SHELBY | SHELBY | | EP | P | 3360610 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | P | 07/20/2007 | ELECTRICAL GEAR AND PANELS AS MARKED IN ORANGE ON SHEET TE 300---ITEMS HIGHLIGHTED IN ORANGE ARE COMPLETE AND MAY HAVE ALL COVERS INSTALLED | SHELBY | SHELBY | | EP | P | 3360602 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ES | P | 07/19/2007 | COMMERCIAL SERVICE: TWO 277/480 4000 AMP 4 WIRE SERVICES BY BERWICK ELECTRIC---NEED TRANSFORMERS 1 AND 3 ENERGIZED AND METERS INSTALLED FOR TRANSFORMERS 1 AND3 | SHELBY | SHELBY | | ES | P | 3360593 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ES | P | 06/01/2007 | COMMERCIAL SERVICE: 277/480 4000 AMP 4 WIRE SERVICE BY BERWICK ELECTRIC | THOMAS | THOMAS | | ES | P | 3360585 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 05/09/2007 | RECESSED CANS (CANOPY LIGHTING) OVER DRIVE UP AREA OK | SHELBY | SHELBY | | ER | P | 3360576 |
MORTON ELECTRIC INC | EUG | P | 01/29/2007 | EUG IN GRC FOR LOW VOLT MONITORING OF DIESEL TANKS---MORTON ELECTRIC | THOMAS | THOMAS | | EUG | P | 3360818 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EUG | P | 01/24/2007 | CONSULTATION | THOMAS | THOMAS | | EUG | P | 3360569 |
US ENGINEERING COMPANY | H= | C | 04/08/2008 | PARTIAL HVAC AND HWP FINALS FOR SHEETS M400, M401, M402, M404, M405, M406, M700.1, M700.2, M700.3 AND M700.4. FINALS PENDING BALANCE REPORT. | LYNNS | LYNNS | | H= | C | 3359732 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 02/25/2008 | GAS FINAL. | LYNNS | LYNNS | | H= | C | 3359789 |
US ENGINEERING COMPANY | HC | C | 10/31/2007 | RELEASE AND LOCK METER FOR KITCHEN. | LYNNS | LYNNS | | HC | C | 3359725 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 07/25/2007 | 200# TEST ON HIGH PRESSURE STEAM LINE OK, 100# TEST ON CONDENSATE SUPPLY AND RETURN, 100# TEST ON CHILL WATER RETURN OK. | LYNNS | LYNNS | | HWP | P | 3359780 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 07/19/2007 | SNOW MELT SYSTEM ON APPROCH RAMP TO FRONT DOOR. | LYNNS | LYNNS | | HWP | P | 3359773 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 07/18/2007 | NEED TO CHECK SHUT OFFS BEFORE UNIONS. | LYNNS | LYNNS | | H= | P | 3359765 |
OLSON PLUMBING & HEATING COMPANY | HC | C | 07/18/2007 | OK FOR METER. 10# ELEVATED PRESSURE SYSTEM. | LYNNS | LYNNS | | HC | C | 3359757 |
OLSON PLUMBING & HEATING COMPANY | HI | C | 07/18/2007 | 60# TEST AND DESIGN OK. NEED TO ADD A SHUT OFF BEFORE THE UNION ON THE MANIFOLDS, WILL CHECK AT FINAL. | LYNNS | LYNNS | | HI | C | 3359748 |
US ENGINEERING COMPANY | HD | P | 07/11/2007 | STAIR PRESSURAZATION DUCT IN STAIRWELLS 1 THROUGH 6 COMPLETE. | LYNNS | LYNNS | | HD | P | 3359717 |
US ENGINEERING COMPANY | HD | P | 07/06/2007 | C.U.P. BUILDING, ROUGH DUCT, RELIEF UNITS, MUA, EXHAUST AND BOILER VENTS OK. | LYNNS | LYNNS | | HD | P | 3359709 |
US ENGINEERING COMPANY | HWP | P | 04/11/2007 | 2- 100# TESTS ON HWP LINES FOR SHELL SPACE HEATERS OK. | LYNNS | LYNNS | | HWP | P | 3359701 |
US ENGINEERING COMPANY | HWP | P | 03/30/2007 | 100# TEST ON HEATING WATER, AREA C, 3RD FLOOR. | LYNNS | LYNNS | | HWP | P | 3359693 |
US ENGINEERING COMPANY | HWP | P | 03/30/2007 | 100# TEST ON HEATING WATER, AREA C, 3RD FLOOR. | LYNNS | LYNNS | | HWP | P | 3359685 |
US ENGINEERING COMPANY | HD | P | 03/29/2007 | 4TH FLOOR: AREA A, ROUGH DUCT OK TO INSULATE, TIE-INS ON 2- SUPPLY LINES AND 1- RETURN. 3RD FLOOR: AREA C, ROUGH DUCT OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3359677 |
US ENGINEERING COMPANY | HWP | P | 03/23/2007 | 100# TEST ON HEATING WATER FOR 5TH FLOOR AREA B. | LYNNS | LYNNS | | HWP | P | 3359668 |
US ENGINEERING COMPANY | HD | P | 03/20/2007 | FIFTH FLOOR AREA B: ROUGH DUCT OK TO INSULATE. FIRE DAMPER FRAMING ON FIFTH AND FOURTH FLOORS. SEE TENNANT FINISH SHEETS FOR DAMPERS AND DATES. | LYNNS | LYNNS | | HD | P | 3359661 |
US ENGINEERING COMPANY | HWP | P | 03/15/2007 | 2ND FLOOR, RADIANT HEATING LINES FOR SOFFIT: 100# TEST, 5TH FLOOR "A" WING, 100# TEST ON HEATING WATER LOOP OK. | LYNNS | LYNNS | | HWP | P | 3359653 |
US ENGINEERING COMPANY | HD | P | 03/12/2007 | 5TH FLOOR AREA A AND 1/2 OF B, OK TO INSULATE. 4TH FLOOR: SEE SHEET TM404 FOR DATE AND ROUGH DUCT, OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3359647 |
US ENGINEERING COMPANY | HWP | P | 02/28/2007 | 5TH FLOOR AREA D, 100# TEST ON HEATING SUPPLY AND RETURN LINES OK. | LYNNS | LYNNS | | HWP | P | 3359639 |
US ENGINEERING COMPANY | HD | P | 02/22/2007 | 5TH FLOOR, AREA "D" ROUGH DUCT, SHAFT 8, 1ST FLOOR THROUGH 6TH, 4TH FLOOR AREA "C" OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3359631 |
US ENGINEERING COMPANY | HWP | P | 02/14/2007 | 5TH FLOOR HEATING WATER TEST ON C WING, 100#. 1ST FLOOR, 5- 100# TESTS IN HEATING AND CHILL WATER HORIZONTAL LINES. | LYNNS | LYNNS | | HWP | P | 3359623 |
US ENGINEERING COMPANY | HD | P | 02/14/2007 | RISER SHAFTS 6 AND 7 FROM 1ST THROUIGH 6TH FLOORS OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3359614 |
US ENGINEERING COMPANY | HD | P | 02/02/2007 | RISER SHAFT DUCT ON SHAFT 1, 2ND THROUGH 6TH FLOORS AND SHAFT 5, 1ST THROUGH 6TH FLOORS OK TO INSULATE. 5TH FLOOR ROUGH DUCT IN AREA C OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3359606 |
US ENGINEERING COMPANY | HWP | P | 01/18/2007 | SHAFT 6 AREA A HWP FROM 1ST THRU 6TH FLOOR O.K, CWP 1ST THRU 4TH FLOOR O.K | JOEL | JOEL | | HWP | P | 3359598 |
US ENGINEERING COMPANY | HD | P | 01/08/2007 | SHAFT 2, 2ND THROUGH 6TH FLOORS. OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3359590 |
US ENGINEERING COMPANY | HD | P | 12/19/2006 | SHAFTS 3 AND 4 ON 5TH AND 6TH FLOORS. OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3359582 |
US ENGINEERING COMPANY | HD | P | 12/08/2006 | RISER DUCTS IN SHAFTS 3 AND 4, GARDEN LEVEL THROUGH 4TH FLOOR, OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3359574 |
US ENGINEERING COMPANY | HWP | P | 12/08/2006 | 8- 100# TESTS ON RISERS IN SHAFT 3 OK TO INSULATE. | LYNNS | LYNNS | | HWP | P | 3359566 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 04/08/2008 | SEE SCAN FOR PROOF OF POTABLE WATER | JEFF | JEFF | | P= | C | 3360544 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 10/10/2007 | CORE AND SHELL ONLY | JEFF | JEFF | | P= | C | 3360537 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 10/10/2007 | | JEFF | JEFF | | PTO | C | 3360529 |
OLSON PLUMBING & HEATING COMPANY | PRD | C | 06/08/2007 | STORM AND OVERFLOW DRAINS COMPLETE | JEFF | JEFF | | PRD | C | 3360521 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 06/07/2007 | DWV CUP COMPLETE | JEFF | JEFF | | PTO | P | 3360513 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 06/07/2007 | O/D AT CUP OK | JEFF | JEFF | | PRD | P | 3360505 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 06/06/2007 | LEVEL 1 STORM AND O/D COMPLETE | JEFF | JEFF | | PRD | P | 3360497 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 06/05/2007 | LEVEL 1 AREA E AND F COLUMN B TO K, LINE 1 THROUGH 20 STORM DRAIN AND O/D OK | JEFF | JEFF | | PRD | P | 3360489 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 06/04/2007 | LEVEL 2 STORM AND OVERFLOW COMPLETE | JEFF | JEFF | | PRD | P | 3360481 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 05/21/2007 | GARDEN LEVEL 6" STORM SHAFT 4 TO POINT OF CONNECTION OK | JEFF | JEFF | | PRD | P | 3360473 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 05/21/2007 | GARDEN LEVEL 6" WASTE SHAFT 3 TO POINT OF CONNECTION OK | JEFF | JEFF | | PTO | P | 3360465 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 05/17/2007 | GARDEN LEVEL KITCHEN ROOF STORM AND OD OK | JEFF | JEFF | | PRD | P | 3360458 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 05/16/2007 | NOTHING READY FOR INSPECTION | JEFF | JEFF | | PRD | P | 3360450 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 05/03/2007 | LEVEL 3 AREA D AND E STORM DRAINS COMPLETE | JEFF | JEFF | | PRD | P | 3360442 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 05/01/2007 | LEVEL 3 AREA F 6" STORM DRAINS X 2 AND OVERFLOW DRAUNS X 2 OK, SD/OD AREA F COMPLETE | JEFF | JEFF | | PRD | P | 3360435 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 04/30/2007 | LEVEL 3 4" SD X 4 WEST AND NORTH SIDE TO ROOF OK | JEFF | JEFF | | PRD | P | 3360429 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 04/26/2007 | LEVEL 2 AREA E AND F ALL STORM AND OD DRAINS LESS 8" OD AND 2 X 4" SD WEST SIDE TO INCLUDE "SNOW" CATCH AREAS | JEFF | JEFF | | PRD | P | 3360420 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 04/25/2007 | LEVEL 2 AREA C OUT OF SHAFT 4 TO ROOF DRAINS AT BB -DD/33-35 | JEFF | JEFF | | PRD | P | 3360412 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 04/13/2007 | 6" STORM AT COLUMN L/ LINE 27 REROUTED | JEFF | JEFF | | PRD | P | 3360404 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 04/12/2007 | LEVEL 1 COLUMN AA TO PP/ LINE 9 TO 11 STORM DRAIN AND OVERFLOW OK TO LEVEL 2 | JEFF | JEFF | | PRD | P | 3360396 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 04/10/2007 | VESTIBULE 1001 OK | JEFF | JEFF | | PRD | P | 3360389 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 04/09/2007 | VESTIBULE 1001 ROOF LEADERS, CRACKED FITTING | JEFF | JEFF | | PRD | P | 3360382 |
OLSON PLUMBING & HEATING COMPANY | PB | C | 04/05/2007 | ALL UNDER GROUND COMPLETE LESS KITCHEN, SEE G18425 FOR KITCHEN | JEFF | JEFF | | PB | C | 3360375 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 04/03/2007 | LEVEL 4 AREA A WATER PIPE COMPLETE | JEFF | JEFF | | PTO | P | 3360368 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 04/02/2007 | ADDED 2" IRRIGATION STUB OUT LEVEL 1 | JEFF | JEFF | | PB | P | 3360361 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 03/30/2007 | LEVEL 4 AREA A WATER PIPE TRUNK LINES OK | JEFF | JEFF | | PTO | P | 3360352 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 03/30/2007 | LEVEL 1 COLUMN J - W/ LINES 1 THROUGH 5 LAB WASTE OK | JEFF | JEFF | | PB | P | 3360344 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 03/21/2007 | LEVEL 1 COLUMN G - M/LINES 1 - 5 OK | JEFF | JEFF | | PB | P | 3360336 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 03/20/2007 | ROOM 1341 SINK DRAIN OK | JEFF | JEFF | | PB | P | 3360323 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 03/16/2007 | COLUMN LINES 5 - 8/J TO T SANITARY WASTE OK | JEFF | JEFF | | PB | P | 3360316 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 03/15/2007 | LEVEL 1 SHAFT 6 10" TO POINT OF CONNECTION | JEFF | JEFF | | PRD | P | 3360309 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 03/15/2007 | LEVEL 1 COLUMN 7 - AA WASTE OK | JEFF | JEFF | | PB | P | 3360303 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 03/14/2007 | LEVEL 1 LINE B - M, 5 THROUGH 16 LESS MRI ROOM OK | JEFF | JEFF | | PB | P | 3360296 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 03/14/2007 | LEVEL 1 SHAFT 5 AND 8 TO POINT OF CONNECTION OK | JEFF | JEFF | | PRD | P | 3360288 |
OLSON PLUMBING & HEATING COMPANY | PRD | R | 03/13/2007 | NOT READY | JEFF | JEFF | | PRD | R | 3360280 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | PRD | P | 03/12/2007 | GARDEN LEVEL 10" STORM AT LINE 17 AND MM OK | JEFF | JEFF | | PRD | P | 3359544 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 03/12/2007 | MATCH LINE W THROUGH LINE PP COMPLETE | JEFF | JEFF | | PB | P | 3360272 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 03/09/2007 | LEVEL 1 GG - LL/ 9 THROUGH 14 | JEFF | JEFF | | PB | P | 3360265 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 03/09/2007 | LEVEL 4 AA - MM/ 2 THROUGH 12 DWV OK | JEFF | JEFF | | PTO | P | 3360258 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 03/08/2007 | P401F.A LINE HH TO GRID 9 AND 12 | LYNNIE | LYNNIE | | PB | P | 3360251 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 03/08/2007 | 5TH FLOOR AREA "A"---DWV--TF405.3--GRID X TO FF---LINE 9 TO 19 | LYNNIE | LYNNIE | | PTO | P | 3360243 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 03/07/2007 | 6''--6TH FLOOR--AREA B--- SHAFT 7-8 AND OUT TO DRAINS----P406.A | LYNNIE | LYNNIE | | PRD | P | 3360235 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | PB | P | 03/06/2007 | 2" SINK DRAIN LINE 7.5/PP LEVEL 1 OK | JEFF | JEFF | | PB | P | 3359536 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | PRD | P | 03/06/2007 | 8" UNDER GROUND STORM MOVED TO COLUMN HH - 14 OK | JEFF | JEFF | | PRD | P | 3359529 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 03/06/2007 | LEVEL 4 SHAFT 5 TO LEVEL 5 DWV OK, SHAFT 8 RETEST VENT ONLY LEVEL 2 TO LEVEL 4 OK | JEFF | JEFF | | PTO | P | 3360227 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 03/05/2007 | LEVEL 4 LINES MM - TT/ 11 THROUGH 15 DWV OK, SHAFT 8 RETEST ON VENT STACK ONLY(NOT WASTE) | JEFF | JEFF | | PTO | P | 3360221 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 02/28/2007 | LEVEL 6 STORM SHAFT 6 AND 7 TO ROOF COMPLETE | JEFF | JEFF | | PRD | P | 3360212 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/28/2007 | LEVEL 4 LINE NN TO TT, 15 THROUGH 19 DWV OK | JEFF | JEFF | | PTO | P | 3360204 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/27/2007 | LEVEL 4 LINE HH-NN, 15 THROUGH 19 DWV OK | JEFF | JEFF | | PTO | P | 3360197 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 02/27/2007 | LEVEL 6 LINE D TO SHAFT 2, LINE 20 THROUGH 29 STORM OK | JEFF | JEFF | | PRD | P | 3360190 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 02/26/2007 | LEVEL 4 SHAFT 6 TO SHAFT 7 8" STORM OK | JEFF | JEFF | | PRD | P | 3360181 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/23/2007 | SHAFT 7 AND 8 LEVEL 2 THROUGH 4 SANITARY WASTE OK | JEFF | JEFF | | PTO | P | 3360173 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 02/23/2007 | SHAFT 8 LEVEL 4 15' OUT THROUGH LEVEL 5 8" STORM OK | JEFF | JEFF | | PRD | P | 3360166 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 02/22/2007 | SHAFT 8 LEVEL 4 STORM DRAIN OK | JEFF | JEFF | | PRD | P | 3360159 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/22/2007 | LEVEL 4 ROOMS 404/405/406 TO LEVEL 5 WASTE AND VENT OK | JEFF | JEFF | | PTO | P | 3360152 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/21/2007 | SHAFT 7 4" WASTE LEVEL 4/5/6, SHAFT 8 4" WASTE LEVEL 4/5/6 | JEFF | JEFF | | PTO | P | 3360146 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 02/21/2007 | SHAFT 7 LEVEL 5 AND 6, SHAFT 8 LEVEL 6 | JEFF | JEFF | | PRD | P | 3360141 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/20/2007 | LEVEL 4, 4" WASTE STACK AT LINE X.3 X 17 TO 4" WASTE STACK AT LINE Q X 22, LEVEL 4 D WING COMPLETE | JEFF | JEFF | | PTO | P | 3360136 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 02/16/2007 | LEVEL 4/5/6 SHAFT 5 AND 6 STORM DRAIN OK | JEFF | JEFF | | PRD | P | 3360130 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/16/2007 | LEVEL 4/5/6 SHAFT 5 AND 6 DWV OK | JEFF | JEFF | | PTO | P | 3360127 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 02/15/2007 | SHAFT 5 LEVEL 2 AND 3 TO 4, SHAFT 6 LEVEL 4 AND 5 TO SIX, LEVEL 4 SHAFT 3 TO 2 OK | JEFF | JEFF | | PRD | P | 3360121 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/15/2007 | SHAFT 5 LEVEL 2 AND 3 TO 4 WASTE, SHAFT 6 LEVEL 4 AND 5 TO SIX WASTE | JEFF | JEFF | | PTO | P | 3360114 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/13/2007 | LEVEL 2 AND 3 TO 4TH FLOOR SHAFT 6 STORM AND SANITARY WASTE AND VENT OK | JEFF | JEFF | | PTO | P | 3360106 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/09/2007 | LEVEL 2 THROUGH 6 SHAFT 6 DOMESTIC WATER PIPE OK | JEFF | JEFF | | PTO | P | 3360098 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/08/2007 | LEVEL 4 LINE 20 - 25, A THROUGH L WASTE AND VENT TO LEVEL 5 OK | JEFF | JEFF | | PTO | P | 3360091 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/07/2007 | LEVEL 4 LINE 24 TO 29, A THROUGH L WASTE AND VENT OK | JEFF | JEFF | | PTO | P | 3360083 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/06/2007 | DWV---SHAFT 2---4'' RISERS ON FLOORS 3 & 4 P 403B AND P 404B | LYNNIE | LYNNIE | | PTO | P | 3360076 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 02/05/2007 | SHAFT 1 LEVEL 3 WASTE STACK, SHAFT 2 LEVEL 5 AND 6 WASTE AND VENT STACKS OK | JEFF | JEFF | | PTO | P | 3360069 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 01/29/2007 | LEVEL 4 TO 5140/5124ST DWV OK | JEFF | JEFF | | PTO | P | 3360061 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 01/26/2007 | NOT READY | JEFF | JEFF | | PTO | P | 3360052 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 01/25/2007 | LEVEL 4 LINE 29 THROUGH 36, LINE N TO Z DWV OK | JEFF | JEFF | | PTO | P | 3360045 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 01/24/2007 | SW WASTE AND VENT STACKS AREA C OK | JEFF | JEFF | | PTO | P | 3360037 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 01/23/2007 | LEVEL 4 THROUGH TO 5, LINE 35 TO 36/ U TO Y DWV OK | JEFF | JEFF | | PTO | P | 3360028 |
OLSON PLUMBING & HEATING COMPANY | PTO | R | 01/16/2007 | CANCELLED PER CONTRACTOR | JEFF | JEFF | | PTO | R | 3360020 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 01/09/2007 | CUP AREA 1/2 BATH WALLS ONLY OK | JEFF | JEFF | | PTO | P | 3360013 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | PTO | P | 01/04/2007 | VENT STACKS AT SHAFT 3 AND 4 THROUGH ROOF OK | JEFF | JEFF | | PTO | P | 3359522 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 01/04/2007 | STORM DRAINS GARDEN LEVEL THROUGH ROOF AT SHAFT 3 AND 4 COMPLETE | JEFF | JEFF | | PRD | P | 3360004 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 12/12/2006 | LEVEL 4 - 6 SHAFTS 3 AND 4 OK | JEFF | JEFF | | PRD | P | 3359996 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 12/12/2006 | LEVEL 4 - 6 SHAFTS 3 AND 4 OK | JEFF | JEFF | | PTO | P | 3359988 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 12/11/2006 | DOMESTIC WATER RISERS IN SHAFT #3-----CLOUDED AREAS ON PLANS--BACK IN OLSONS TRIALER NOW | LYNNIE | LYNNIE | | PTO | P | 3359980 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 12/04/2006 | LEVEL 1-2-3 RISERS AT SHAFTS 3-4 OK | JEFF | JEFF | | PRD | P | 3359974 |
OLSON PLUMBING & HEATING COMPANY | PTO | P | 12/04/2006 | LEVEL 1-2-3 RISERS AT SHAFTS 3-4 OK | JEFF | JEFF | | PTO | P | 3359967 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 11/17/2006 | UNDER SLAB COMPLETE | JEFF | JEFF | | PRD | P | 3359959 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 11/17/2006 | SANITARY COMPLETE LESS KITCHEN GREASE WASTE | JEFF | JEFF | | PB | P | 3359952 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 11/13/2006 | LINE 25 LINE CC THROUGH GG STORM DRAIN OK | JEFF | JEFF | | PRD | P | 3359945 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 11/13/2006 | LINE 30 - 33 LINE AA THROUGH CC SANITARY OK | JEFF | JEFF | | PB | P | 3359937 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 11/09/2006 | SD----X3 BY LINE 25.5 | LYNNIE | LYNNIE | | PRD | P | 3359929 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 11/07/2006 | S.S.--DWV--LINE EE OVER TO COLUM 30 | LYNNIE | LYNNIE | | PB | P | 3359923 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 11/02/2006 | SEE JEFFS NOTES ON 02-NOV-06---I VERIFIED WATER TESTS-- | LYNNIE | LYNNIE | | PRD | P | 3359918 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 11/02/2006 | LINE 10 - BRANCH LINES AT K & M STORM DRAINS OK | JEFF | JEFF | | PRD | P | 3359912 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 11/02/2006 | LINE 5 - J THROUGH W SANITARY WASTE OK | JEFF | JEFF | | PB | P | 3359893 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 11/01/2006 | LINE 10 - F THROUGH W OK | JEFF | JEFF | | PB | P | 3359887 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 10/31/2006 | W-PP LINE 2-12 UNDERGROUND STORM DRAIN COMPLETE | JEFF | JEFF | | PRD | P | 3359883 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 10/31/2006 | W-PP LINE 2-12 COMPLETE LESS DECONTAMINATION DRAIN | JEFF | JEFF | | PB | P | 3359878 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 10/24/2006 | LINE 1O CC THROUGH EE | JEFF | JEFF | | PRD | P | 3359874 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 10/24/2006 | LINE 5 LINE ST/ LINE 5 G THROUGH J/ LINE 10 LESS HH THROUGH NN | JEFF | JEFF | | PB | P | 3359869 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 10/20/2006 | C.U.P.===SS UNDER GROUND COMPLETE--ELEVATION 80 AND 84 | LYNNIE | LYNNIE | | PB | P | 3359865 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 10/20/2006 | C.U.P.===UNDER GROUND COMPLETE--ELEVATION 80 AND 84 | LYNNIE | LYNNIE | | PRD | P | 3359859 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 10/19/2006 | LINE 23---FROM 8'' WYE WITH CLEANOUT OUT TO LINE K BY COLUM | LYNNIE | LYNNIE | | PB | P | 3359854 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 10/17/2006 | C U P BUILDNIG---80 ELEVATION--CWV AND SANITY SEWER--CLOUDED AREAS ON APPROVED PLANS | LYNNIE | LYNNIE | | PB | P | 3359846 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 10/16/2006 | CLOUDED AREAS ON APPROVED PLANS----W THRU PP--LINE 5--C.U.P. BUILDING- COMBO WASTE AND VENT CLOUDED ON PLANS | LYNNIE | LYNNIE | | PB | P | 3359839 |
OLSON PLUMBING & HEATING COMPANY | PB | P | 10/11/2006 | CHANGED TO PARTIAL TO ALLOW ADDITIONAL INSPECTIONS, PLANS PARTIALY APPROVED FOR UNDERSLAB, EXCEPT BASEMENT (KYE) .TO COMPLETE PERMIT, CONTRACTOR CONTINUING AT OWN RISK, SANITARY TRUNK LINE LINE 5 W-GG OK, NEED APPROVED PLANS FOR FUTHER INSPECTIONS | JEFF | JEFF | | PB | P | 3359833 |
OLSON PLUMBING & HEATING COMPANY | P16 | C | 10/11/2006 | MET WITH JEFF ON SITE TO GET SCOPE OF WORK-SITE WHEN HE IS OFF | LYNNIE | LYNNIE | | P16 | C | 3359829 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | PRD | P | 10/04/2006 | STORM TRUNK LINE AT LINE 10 FROM W - PP | JEFF | JEFF | | PRD | P | 3359515 |
OLSON PLUMBING & HEATING COMPANY | PB | T | 10/04/2006 | PAID (REC#719550): TRIP FEE, TO COVER ADDITIONAL INSPECTION, CONTRACTOR CONTINUING AT OWN RISK, SANITARY TRUNK LINE AT LINE 10 FROM W - PP TEST OK | JEFF | JEFF | | PB | T | 3359822 |
OLSON PLUMBING & HEATING COMPANY | PB | T | 09/27/2006 | PAID (REC#718499): TRIP FEE, TRIP FEE TO COVER ADDITIONAL INSPECTION, WILL WAIVE TRIP FEE IF PERMIT UPDATED, SANITARY TRUNK LINE AT LINE 5 THROUGH TO W OK | JEFF | JEFF | | PB | T | 3359813 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 09/26/2006 | STORM DRAIN ONLY AREA C LINE 10 THROUGH TO W | JEFF | JEFF | | PRD | P | 3359808 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 09/26/2006 | STORM DRAIN ONLY AREA C LINE 10 THROUGH TO W | JEFF | JEFF | | PRD | P | 3359801 |
OLSON PLUMBING & HEATING COMPANY | PRD | P | 09/14/2006 | STORM DRAIN ONLY LINE 24-26 LINE C THROUGH BB TRUNK LINE OK | JEFF | JEFF | | PRD | P | 3359796 |
OTIS ELEVATOR COMPANY | V= | C | 04/24/2008 | ALL ITEMS COMPLETE | TOM | TOM | | V= | C | 3360552 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | V= | C | 04/21/2008 | OTIS--ALL ITEMS CORRECTED OK TO ISSUE PERMIT | TOM | TOM | | V= | C | 3358889 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | V= | P | 04/03/2008 | SUMP WIRING STILL ON PIT FLOORS / NON GFI'S FOR ALL SUMPS / LIGHTING AT TOP OF H/W INOP CARS 5 & 6 / MOVE ALL SUMP SENSORS ABOVE SILL LEVEL / SEQUENCE NUMBER ALL CARS @ FIRE LEVELS / FIRE FINAL | TOM | TOM | | V= | P | 3359559 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | V= | P | 04/03/2008 | OTIS--GEN II--CAR 1--RAMP SILLS @ LEVEL 6 / MOVE ALL SUMP SENSORS ABOVE SILL LEVEL IN PITS--CAR 2--FIRE SEAL H/W PENE--CAR 3--FIRE SEAL TOP OF H/W PENE / PIT LIGHT INOP--CAR 4--PHONE--CAR 5--PHONE--CAR 6--TOP OF H/W LIGHTING / TOP OF CAR LIGHTING / PIT LIGHT--CAR 7--MOVE SUMP PUMP BELOW GRATE / SUMP WIRING ON FLOOR OF PIT / CLEAN ALL PITS / RENUMBER MAINLINE DISCONNECTS / CAR 8--MOVE SUMP PUMP BELOW GRATE--SIGNS ON M/R / FIRE EXT / NON GFI IN ALL PITS | TOM | TOM | | V= | P | 3359551 |