KEY CONSTRUCTION, INC. | B= | C | 07/17/2007 | | MICHAELA | MICHAELA | | B= | C | 3397412 |
KEY CONSTRUCTION, INC. | B= | P | 07/16/2007 | FINAL COMPLETE PENDING ALL REQUIRED FINAL INSPECTIONS | MICHAELA | MICHAELA | | B= | P | 3397403 |
KEY CONSTRUCTION, INC. | B= | P | 07/12/2007 | MISSING 4 EXIT SIGNS - 5 EXIT SIGNS ARE INCORRECT FOR DIRECTION - FRONT BATHROOMS OK - HIGH PILE STORAGE SIGNS IN PLACE / NORTH EMERGENCY EXIT REQUIRE 44" LANDING IN DIRECTION OF TRAVEL - RE-QUIRES RESTRIPE AT PHARMACY DRIVE-THROUGH | MICHAELA | MICHAELA | | B= | P | 3397395 |
KEY CONSTRUCTION, INC. | B= | P | 07/08/2007 | Temp CO: STILL NEED FINAL APPROVALS, ALL DEPARTMENTS | SHELLEY | SHELLEY | | B= | P | 3397179 |
KEY CONSTRUCTION, INC. | B= | P | 06/06/2007 | COMPLETE FRONT BATHROOMS / COMPLETE EXIT SIGNAGE / INSTALL SIGNAGE FOR HIGH-PILE STORAGE / NEED ALL REQUIRED FINAL INSPECTIONS / NEED FIRE DEPARTMENT CLARIFICATION FOR CURRENT FIRE APPROVAL STATUS / EXTERIOR NOT INSPECTED | MICHAELA | MICHAELA | | B= | P | 3397388 |
KEY CONSTRUCTION, INC. | BFR | C | 04/30/2007 | ALL COLD ROLL FRAMING COMPLETE | MICHAELA | MICHAELA | | BFR | C | 3397379 |
KEY CONSTRUCTION, INC. | BFR | P | 04/18/2007 | SEE PLAN DATED 3/26/07 FOR APPROVALS | MICHAELA | MICHAELA | | BFR | P | 3397371 |
KEY CONSTRUCTION, INC. | BSP | T | 03/29/2007 | PAID (REC#744451)ADDITIONAL PLAN REVIEW TIME: $50.000 FROM: JERRY SPLICES 6 AND 7 | JERRY | JERRY | | BSP | T | 3397363 |
KEY CONSTRUCTION, INC. | BFR | P | 03/28/2007 | INTERIOR WALL FRAMING NOTED ON RBD SET PAGE A1 / UL#465 IS FIRESTOP ASSEMBLY BEING USED AT ALL GYPBOARD FIRE WALLS | MICHAELA | MICHAELA | | BFR | P | 3397355 |
KEY CONSTRUCTION, INC. | BFR | P | 03/08/2007 | SEE APPROVED PLAN FOR SPECIFICS | MICHAELA | MICHAELA | | BFR | P | 3397347 |
KEY CONSTRUCTION, INC. | BFR | P | 02/23/2007 | LITE GAUGE FRAMING BOTH SIDE FRONT ENTRY - OK TO COVER | MICHAELA | MICHAELA | | BFR | P | 3397341 |
KEY CONSTRUCTION, INC. | BFR | P | 02/12/2007 | ADD COLD ROLL BRIDGING TO THE BOTTOM SIDE OF THE UPPER PORTION OF CEILING FRAMING AT BOTH MAIN ENTRANCES.WALL FRAMING OF THE SOUTHEAST ENTRANCE IS OK. --- THIS INSPECTION DID NOT INCLUDE STEEL TRUSSES---OK TO COVER WALL FRAMING | ED | ED | | BFR | P | 3397333 |
KEY CONSTRUCTION, INC. | BFR | P | 02/08/2007 | FRAME OK AT THE NORTH END DRIVE THREW . FRMING CLIPS FROM TRUSSES TO WOOD BEAM OK @ THE NORTHEAST END STOREFRONT. | ED | ED | | BFR | P | 3397325 |
KEY CONSTRUCTION, INC. | BFR | P | 02/05/2007 | ( MISSING)--- DETAIL (3) ON S67.1 SHOWS 3X3 ANGLE CLIPS CONNECTED FROM TRUSS TO WOOD BEAM, THESE CLIPS ARE NOT INSTALLED AND CAN BEEN SEEN FROM THE UNDERSIDE.LATERAL BRACING ON THE VERTICAL BRACE OK.-- OK TO COVER UP THE ROOF DECK--- ON THE DRIVE THRU FRAMING, MISSING SCREW AND WELDED CONNECTIONS,----PLEASE COMPLETE WORK AND CALL FOR REINSPECTION | ED | ED | | BFR | P | 3397315 |
KEY CONSTRUCTION, INC. | BSP | T | 02/02/2007 | PAID (REC#735154)ADDITIONAL PLAN REVIEW TIME: $100.000 From: TIMC | TIMC | TIMC | | BSP | T | 3397298 |
KEY CONSTRUCTION, INC. | BSP | T | 02/02/2007 | PAID (REC#735155)ADDITIONAL PLAN REVIEW TIME:FIVE HUNDRED DOLLARS $500.00 COMPLETE CHECK OF FIELD SET (APPROVED SHEETS MISSING) FROM: JERRY | JERRY | JERRY | | BSP | T | 3397307 |
KEY CONSTRUCTION, INC. | BFR | P | 01/26/2007 | NORTH EAST STORE FRONT WALL FRAMING OK, FRAMING OF WALLS ABOVE THE ROOF OK, NEED TO INSTALL ACCESS DOOR FRAMING. ---- LEAVE CEILING FRAMING OPEN FOR ELECTRICAL INSPECTION | ED | ED | | BFR | P | 3397293 |
KEY CONSTRUCTION, INC. | BSP | T | 01/25/2007 | PAID (REC#735157)ADDITIONAL PLAN REVIEW TIME: $50.000 From: RUSSELL Revised mechanical for rtu-13 | RUSSELL | RUSSELL | | BSP | T | 3397286 |
INTERSTATE MECHANICAL, INC. | BSP | T | 01/25/2007 | PAID (REC#735156)ADDITIONAL PLAN REVIEW TIME: $100.000 From: DARYL Had to dig and get approved P1 page to approve new P1 and also P2 | DARYL | DARYL | | BSP | T | 3396639 |
KEY CONSTRUCTION, INC. | BSP | P | 01/17/2007 | EXTERIOR HIGH WALL BUMP OUT FRAMING OK, PARAPET WALL FIRE STOPPING INSTALLED BETWEEN METAL DECK ,CMU WALL AND IN CAVITY OF PARAPET FRAMING,--OK TO COVER UP THESE TWO AREAS | ED | ED | | BSP | P | 3397277 |
KEY CONSTRUCTION, INC. | BFR | P | 01/04/2007 | EXTERIOR TOP WALL BUMP OUT FRAMING, AND HIGN WALL PARAPET FRAMING OK. NEED TO INSTALL FIRESAFING BETWEEN DECK WEBING & CMU WALL AT THE HIGH PARAPET WALL | ED | ED | | BFR | P | 3397270 |
KEY CONSTRUCTION, INC. | BSP | T | 12/18/2006 | PAID (REC#731099)ADDITIONAL PLAN REVIEW TIME: $200.000 From: RUSSELL Revised mechanical | RUSSELL | RUSSELL | | BSP | T | 3397261 |
KEY CONSTRUCTION, INC. | BSP | T | 12/13/2006 | PAID (REC#731099)ADDITIONAL PLAN REVIEW TIME: $100.000 From: TIMC Plans revisions; Subway, Pharmacy and Tire Center | TIMC | TIMC | | BSP | T | 3397254 |
KEY CONSTRUCTION, INC. | BSP | T | 11/07/2006 | PAID (REC#724914)ADDITIONAL PLAN REVIEW TIME: $300.000 FROM: SHELBY---THE ORIGINAL PLAN SHEETS WERE CHANGED AFTER THEY WERE APPROVED. WHEN THE JOB WAS PERMITEDTHE PLAN SCANNED BY RBD HAD ALL BUT THREE OF THE UNAPPROVED SPLICE SHEETS . WE DID A COMPLETE PLAN REVIEW ON THE ORIGINAL AND THEN THE REVIEW FOR THE SPLICE.---THIS FEE DOES NOT INCLUDE PREVIOUS TRIP FEE---TOTAL FEE $350--- | SHELBY | SHELBY | | BSP | T | 3397246 |
KEY CONSTRUCTION, INC. | BFT | P | 10/19/2006 | ENGINEER ON SITE AND WILL COMPLETE FOUNDATION , STRUCTURAL STEEL AND STRUCTURAL MASONRY INSPECTIONS | MICHAELA | MICHAELA | | BFT | P | 3397237 |
KEY CONSTRUCTION, INC. | BFT | P | 10/17/2006 | AREA HIGHLIGHTED IN YELLOW ON APPROVED DRAWINGS, COMMENTS ON INSPECTION LOG | ED | ED | | BFT | P | 3397230 |
KEY CONSTRUCTION, INC. | BFT | P | 10/17/2006 | OK ENGINEER TO DO FOOTINGS | JIMP | JIMP | | BFT | P | 3397222 |
KEY CONSTRUCTION, INC. | BFN | P | 10/17/2006 | OK ENGINEER TO DO FOUNDATIONS | JIMP | JIMP | | BFN | P | 3397214 |
KEY CONSTRUCTION, INC. | BFT | P | 10/16/2006 | SLAB ON GRADE, PIT STEEL OK,(NOT WALLS) | ED | ED | | BFT | P | 3397205 |
KEY CONSTRUCTION, INC. | BFT | P | 10/13/2006 | SECTION HIGNLIGHTED IN YELLOW, ON S1 SHEET OF APPROVED DRAWINGS. UFER WAS COMPLETED BY ELECT. | ED | ED | | BFT | P | 3397197 |
KEY CONSTRUCTION, INC. | BFT | P | 10/11/2006 | HIGHLIGHTED IN YELLOW ON SHEET (S-8), NO UFER NEEDED IN THIS AREA, | ED | ED | | BFT | P | 3397187 |
T F S ELECTRIC, LLC | E= | C | 07/16/2007 | | DAVID | DAVID | | E= | C | 3397493 |
BIBLE ELECTRIC, INC. | E= | C | 07/13/2007 | STORE COMPLETE!! | DAVID | DAVID | | E= | C | 3397171 |
BIBLE ELECTRIC, INC. | E= | P | 07/11/2007 | ALL AREAS COMPLETE EXCEPT FOR ONE AREA IN GARDEN CENTER, THEY NEED TO MOVE A RACK AWAY FROM DISCONNECT SWITCH FOR FAN. | DAVID | DAVID | | E= | P | 3397163 |
BIBLE ELECTRIC, INC. | E= | P | 07/11/2007 | PANELS EDC-2, EDC-3, SUBWAY SHOP AND THE GARDEN CENTER COMPLETE. INSPECTION DONE BY GARY H, INPUT BY DAVID J. | DAVID | DAVID | | E= | P | 3397156 |
BIBLE ELECTRIC, INC. | EP | P | 07/10/2007 | PANELS NEEDS TO BE CLEANED | GARY | GARY | | EP | P | 3397148 |
BIBLE ELECTRIC, INC. | ER | P | 07/10/2007 | CEILINGS, DISCONNECTS AND PANEL | GARY | GARY | | ER | P | 3397140 |
BIBLE ELECTRIC, INC. | E= | P | 07/09/2007 | PARKING LOT COMPLETE | DAVID | DAVID | | E= | P | 3397132 |
BIBLE ELECTRIC, INC. | ER | R | 07/09/2007 | GARDEN CENTER NOT READY. | DAVID | DAVID | | ER | R | 3397124 |
BIBLE ELECTRIC, INC. | E= | P | 07/06/2007 | SALES FLOOR COMPLETE! | DAVID | DAVID | | E= | P | 3397116 |
BIBLE ELECTRIC, INC. | E= | P | 07/05/2007 | CASH WRAPS ON EAST END COMPLETE, HAIR SALOON COMPLETE, SALES FLOOR PARTIAL ONLY (NEEDS ALOT OF STRAPPING OF CONDUITS). | DAVID | DAVID | | E= | P | 3397105 |
BIBLE ELECTRIC, INC. | EP | P | 07/03/2007 | FOLLOWING PANEL ARE OK EXCEPT FOR 480 VOLT PANELS I STILL NEED FALUT CURRENT INFORMATION; 277/480 VOLT PANELS H4B1; H2A; H3B; H4B3; H2B; H1P1 H1P2 ((H1A & H1B HAVE FACTORY WIRED FEEDERS) H4B3 H4B2 120 /208 PANELS L1D1-1 L1D1-2 L1U AND PANEL L1D2 BRANCH CIRCUITS OK FEEDERS FACTORY WIRED; THESE PANELS STILL NEED PROPER LABELING | JOSEPH | JOSEPH | | EP | P | 3397098 |
BIBLE ELECTRIC, INC. | EP | P | 07/02/2007 | PANELS - LRX, LVC, LHC, L2U, LFS, H4B2, H4B3 ALL THESE PANELS ARE COMPLETE. PANELS L4D1-1, L4D1-2, L4D2-1, L4D2-2, TFS, T4D, LFS, H4C, H4B1 BRANCH CIRCUITS ONLY - THESE PANELS CAME ON A FACTORY WIRED SKID. | DAVID | DAVID | | EP | P | 3397090 |
BIBLE ELECTRIC, INC. | E= | P | 06/15/2007 | BAKERY DEPARTMENT/ PRODUCE PREP/ SEAFOOD/ MEAT DEPARTMENT/ DAIRY (BASICALLY THIS INSPECTION WAS A FINAL FOR THE WHOLE NORTH END OF BUILDING). | DAVID | DAVID | | E= | P | 3397081 |
BIBLE ELECTRIC, INC. | E= | P | 06/13/2007 | ROOF TOP COMPLETE, EXCEPT FOR THE GARDEN CENTER. ALSO AUTOMOTIVE COMPLETE INCLUDING PIT. | DAVID | DAVID | | E= | P | 3397073 |
BIBLE ELECTRIC, INC. | E= | P | 06/11/2007 | REAR RESTROOMS, CUSTOMER SERVICE, TRAINING ROOM, INVOICING ROOM, AUTOMOTIVE (EXCLUDING PIT), STOCK ROOM (BY AUTOMOTIVE), BREAK ROOM, MANAGERS OFFICE, AND RECEIVING AREA | DAVID | DAVID | | E= | P | 3397065 |
BIBLE ELECTRIC, INC. | E= | P | 06/08/2007 | COURTSEY DESK, VISION, FRONT BATHROOMS, GM VESTUIBLE, LP OFFICE, SPRINKLER PUMP ROOM, PHARMACY AND SALES FLOOR. DID NOT LOOK AT RTU'S. | DAVID | DAVID | | E= | P | 3397058 |
T F S ELECTRIC, LLC | E= | P | 06/04/2007 | 1. TIGHTEN SEALTIGHT CONNECTIONS ON ROOF. 2. NEED POWER TO RECEPTACLES. 3. PHASE TAPE CONDUCTORS. | DAVID | DAVID | | E= | P | 3397485 |
BIBLE ELECTRIC, INC. | ER | P | 05/29/2007 | CEILINGS ON EAST SIDE OF BUILDING | GARY | GARY | | ER | P | 3397051 |
BIBLE ELECTRIC, INC. | EUG | P | 05/24/2007 | 1" TO MONUEMENT SIGN ON NORTHEAST CORNER OF LOT, BEING FEED FROM LAST LIGHT POLE. | DAVID | DAVID | | EUG | P | 3397044 |
BIBLE ELECTRIC, INC. | ER | P | 05/11/2007 | CEILINGS TLE VESTUIBLE, TLE BATHROOM, GM VESTUIBLE, BREAKROOM, SMOKERS ROOM, CUSTOMER SERVICE,TRAINING ROOM AND MANAGERS OFFICE. ALL MARKED ON SHEET E1 | DAVID | DAVID | | ER | P | 3397037 |
BIBLE ELECTRIC, INC. | ER | P | 05/02/2007 | AUTOMOTIVE WALLS OK! AS MARKED ON SHEET E-2. | DAVID | DAVID | | ER | P | 3397029 |
BIBLE ELECTRIC, INC. | EUG | P | 05/02/2007 | 3/4" PVC TO TLC KIOSK OK TO BACKFILL. | DAVID | DAVID | | EUG | P | 3397024 |
BIBLE ELECTRIC, INC. | ER | P | 05/01/2007 | NORTHEAST VESTUIBLE WALLS ONLY AS MARRKED ON SHEET E-2. FIREALARM ALSO OK. | DAVID | DAVID | | ER | P | 3397017 |
BIBLE ELECTRIC, INC. | ER | P | 04/25/2007 | 1. WALLS AS MARKED ON SHEET E-2. 2. SUBWAY WALLS AS MARKED ON SHEET E-2. 3. GARDEN CENTER VESTUBLE WALLS AND CEILING AS MARKED ON SHEET E-2. | DAVID | DAVID | | ER | P | 3397011 |
BIBLE ELECTRIC, INC. | ER | R | 04/18/2007 | NEED APROVED SET OF PLANS SET OUT AT TIME OF INSPECTION TO ALLOW US TO MARK DOWN WHAT WE HAVE LOOKED AT. | DAVID | DAVID | | ER | R | 3397003 |
BIBLE ELECTRIC, INC. | ER | P | 04/10/2007 | WALLS ONLY IN GM VESTUBILE, MECH ROOM BY GM VESTUBILE, LP OFFICE. | DAVID | DAVID | | ER | P | 3396998 |
BIBLE ELECTRIC, INC. | ER | P | 04/05/2007 | WALLS PHARMACY, BATHROOMS, EYE CARE | GARY | GARY | | ER | P | 3396991 |
BIBLE ELECTRIC, INC. | ER | P | 04/02/2007 | WALLS AND SOFFITS, SEE PRINTS THIS DATE | GARY | GARY | | ER | P | 3396980 |
BIBLE ELECTRIC, INC. | ER | P | 03/19/2007 | WALLS ONLY ROOMS 179.152,151,166,165,162,171,168,163 AND 167. | DAVID | DAVID | | ER | P | 3396971 |
BIBLE ELECTRIC, INC. | EUG | P | 02/12/2007 | 1-2" AND 1-2 1/2" FROM TIRE AND LUBE CENTER (TLE) TO GARDEN CENTER. | DAVID | DAVID | | EUG | P | 3396963 |
BIBLE ELECTRIC, INC. | EUG | P | 02/08/2007 | SITE LIGHTING ON SOUTH END COMPLETE. | DAVID | DAVID | | EUG | P | 3396956 |
BIBLE ELECTRIC, INC. | ES | C | 01/29/2007 | COMMERCIAL SERVICE: 3600 A 3 PHASE 4 WIRE 277/480 VOLT SERVICE NEED POWER ENERGIZED | DAVID | DAVID | | ES | C | 3396946 |
BIBLE ELECTRIC, INC. | EUG | P | 01/24/2007 | 4-3" PVC'S, 2-2 1/2" PVC'S AND 1-1" FROM MAIN ELECTRIC ROOM TO EDC-4 ON NORTH EAST END OF BUILDING COMPLETE. | DAVID | DAVID | | EUG | P | 3396939 |
BIBLE ELECTRIC, INC. | EUG | R | 01/12/2007 | CUSTOMER CANCELLED. | DAVID | DAVID | | EUG | R | 3396931 |
BIBLE ELECTRIC, INC. | EUG | P | 01/03/2007 | 4-3" PVC'S, 2-2 1/2" PVC'S, 1-1" PVC'S FROM COLUMN LINE 9E TO COLUMN LINE 3D OK TO BACKFILL. | DAVID | DAVID | | EUG | P | 3396925 |
BIBLE ELECTRIC, INC. | EUG | P | 12/18/2006 | 2 -3" PVC TO PANEL H2B COMPLETE, 2 -2 1/2" TO PANEL H2A COMPLETE, 2 - 2 1/2 " TO PANEL H3B COMPLETE, ---- 4-3" PVC'S, 2-2 1/2" PVC'S AND 1-1" PVC FROM MDP TO COLUMN LINE 9E COMPLETE----- | DAVID | DAVID | | EUG | P | 3396917 |
BIBLE ELECTRIC, INC. | EUG | P | 12/13/2006 | SITE LIGHTING AS MARKED ON SHEET E1.2 OF APPROVED PLANS. | DAVID | DAVID | | EUG | P | 3396910 |
BIBLE ELECTRIC, INC. | EUG | P | 11/21/2006 | TWO 3" PVC'S. TWO 3 1/2" PVC'S, TWO 1 1/4" PVC'S ON EAST SIDE OF BUILDING IN ELECTRIC ROOM. THEY EXTEND 30' TO THE EAST! | DAVID | DAVID | | EUG | P | 3396902 |
BIBLE ELECTRIC, INC. | ER | T | 11/01/2006 | PAID (REC#724915)SOME OF THE PLAN SHEETS THAT WERE PERMITED ARE NOT THE APPROVED SHEETS,NO INSPECTIONS UNTIL THE PLANS ARE CORRECTED | JERRY | JERRY | | ER | T | 3396895 |
BIBLE ELECTRIC, INC. | EUG | P | 10/23/2006 | (10) 4" PVC TRANSFORMER TO MDP OK, (6) 3" AND (6) 2.5" FEEDERS FROM MDP STUBBED UNDER PAD OK.======RESUBMIT SERVICE ENTRANCE CONDUCTORS CHANGE TO RBD FOR APPROVAL.======== | ROBERT | ROBERT | | EUG | P | 3396888 |
BIBLE ELECTRIC, INC. | EUG | P | 10/12/2006 | 3/0 EUFER OK. | DAVID | DAVID | | EUG | P | 3396881 |
PUEBLO SHEET METAL WORKS INC | H= | C | 07/13/2007 | MECHANICAL CONTRACTOR. SEE SCANNED ENGINEERS LETTERS FOR UNIT HEATER VENTING AND DELETION OF MOTORIZED DAMPERS AT FIRE PUMP ROOM. | ERIC | ERIC | | H= | C | 3396632 |
INTERSTATE MECHANICAL, INC. | H= | C | 07/13/2007 | GAS CONTRACTOR | ERIC | ERIC | | H= | C | 3396685 |
PUEBLO SHEET METAL WORKS INC | H= | P | 07/12/2007 | PROPERLY INSULATE UNIT HEATER VENTS THRU UNCONDITIONED SPACES AND NEED ENGINEERING LETTERS ON UNIT HEATER VENTS AND FIREROOM DAMPERS. ALSO NEED TEST AND BALANCE REPORT. | ERIC | ERIC | | H= | P | 3396625 |
PUEBLO SHEET METAL WORKS INC | HD | P | 06/19/2007 | REMOVE SHEET ROCK FROM FIRE DAMPER FRAMING AT PUMP ROOM. NEED A MINIMUM OF 1/4'' SPACE AROUND BOTH DAMPERS. WATER HEATER VENT OK TO ROOF. NEED TO CHECK VENT ABOVE WHILE INSPECTING REST OF ROOF. FAR NORTH/WEST UNIT HEATER IN GARAGE NEEDS TO BE BRACED TO WALL, SEAL NEW ELBOW ON UNIT HEATER THAT WAS BROKEN. | LYNNS | LYNNS | | HD | P | 3396617 |
INTERSTATE MECHANICAL, INC. | H16 | P | 06/12/2007 | HI--NOTES FOR FINAL. NEED ALL MEDIUM PRESSURE PIPING PROPERLY LABELED, CHECK ALL REGS INSIDE FOR VENTS TO EXTERIOR, GAS COCKS AHEAD OF REGS, UNIONS AFTER REGS, NOTICED UNIT HEATERS IN AUTO CENTER ARE UNREGULATED, CHECK ALL THE REST, CHECK GAS FLEX SIZING ON WATER HEATER,CHECK SIZING OF GAS LINE TO WATER HEATER, CHECK FOR 4 CAPPED FUTURE STUBS, CK SUPPORT ON ALL GAS DROPS TO EQUIPMENT. REVISED PLANS FOR METER LOCATION. WALK THE REST | ERIC | ERIC | | H16 | P | 3396677 |
PUEBLO SHEET METAL WORKS INC | H16 | P | 06/12/2007 | HV--NOTES FOR FINAL. SEAL JOINT ON UNIT HEATER VENT IN AUTO CENTER, CHECK VENTING SUPPORTS ON ALL UNIT HEATERS, CHECK WATER HEATER VENT, ALL ENTRYWAY UNIT HEATER VENTS ARE INSTALLED CONTRARY TO CODE, SINGLEWALL VENT CONCEALED, CONCEALED IN UNCONDITIONED SPACE, LENGTH LIMITS EXCEEDED, NOT PROPERLY SUPPORTED, TOO CLOSE TO COMBUSTIBLES ETC... WILL REQUIRE SITE & MODEL SPECIFIC LETTER FROM MANUFACTURER AND APPROVAL FROM MECHANICAL ENGINEER ON EXACT VENTING CONFIGURATION. WALK ALL | ERIC | ERIC | | H16 | P | 3396610 |
PUEBLO SHEET METAL WORKS INC | H16 | P | 06/12/2007 | HD--NOTES FOR FINAL-NEED WRAP ON TOP OF 2 HOODS, CHECK FRAMING FOR FIRE DAMPERS AND MOTORIZED DAMPERS AT FIRE PUMP ROOM, ALL DUCTS INTO PUMP ROOM TO BE FIRE WRAPPED FROM LID TO ROOF DECK, NEED TO SEE DRYER VENT IN HAIR SALON, REINSPECT ROOF AREA FOR PLUMBING VENT CLEARANCE TO AIR INTAKES RTU'S 11,20 & 30, CHECK CLEARANCES ON ADDED PLUMBING VENTS,CHECK FIRE PUMP EXHAUST CLEARANCE TO AIR INTAKE, CO DETECTORS AT RTU'S 5,16,21,&23. RTU LABELS ETC... | ERIC | ERIC | | H16 | P | 3396603 |
VICTORY AIR | H= | C | 06/11/2007 | REFRIGERATION CONTRACTOR AND WALK THRU FOR OTHER HEAT FINALS | ERIC | ERIC | | H= | C | 3397477 |
VICTORY AIR | H16 | C | 06/11/2007 | TRAINING H= WITH ERIC | TIM | TIM | | H16 | C | 3397469 |
PUEBLO SHEET METAL WORKS INC | H= | P | 06/08/2007 | OK FOR MECHANICAL TCO | ERIC | ERIC | | H= | P | 3396595 |
INTERSTATE MECHANICAL, INC. | H= | P | 06/07/2007 | OK FOR TEMPORARY USE | JIMV | JIMV | | H= | P | 3396669 |
VICTORY AIR | H= | P | 06/07/2007 | OK FOR TEMPORARY USE | JIMV | JIMV | | H= | P | 3397461 |
PUEBLO SHEET METAL WORKS INC | HD | P | 06/06/2007 | AUTO CENTER, GARDEN CENTER AND SOUTH END SPIRAL DUCT TO ENTRY OK. HOODS NEED TOP FIRE WRAP, NEED TO SEE DRYER VENT IN HAIR SALON AREA, FIRE PUMP ROOM PLANS CALL FOR MOTORIZED DAMPERS AND FIREWRAP FROM CEILING TO ROOF DECK, IF NO WRAP AND MANUAL FIRE DAMPERS ARE APPROVED BY MECHANICAL ENGINEER AND PPRBD, I WILL NEED INSTALLATION MANUALS FOR DAMPERS. | ERIC | ERIC | | HD | P | 3396588 |
PUEBLO SHEET METAL WORKS INC | HD | P | 05/29/2007 | OK TO WRAP ALL EAST SIDE DUCTS. STILL NEED GREASE DUCTS, GARDEN CENTER, AUTO CENTER, SOUTH END SPIRAL DUCTING, WATER HEATER VENT AND CORRECTIONS FROM PREVIOUS INSPECTION AND PROPER VENTING OF ALL ENTRYWAY UNIT HEATERS. | ERIC | ERIC | | HD | P | 3396580 |
PUEBLO SHEET METAL WORKS INC | HD | P | 05/11/2007 | OK FOR CEILING TILE AT WEST OFFICE AREAS ONLY. FIRE DAMPERS AT RECIEVING AND BREAKROOM- OK. **** ISSUES TO BE RESOLVED BY FINAL-PLUMBING VENTS LESS THAN 10' FROM INTAKES ON RTU'S #11, 20 AND 30. FIREPUMP EXHAUST TERMINATES LESS THAN 10' FROM FRESHAIR INTAKE. | ERIC | ERIC | | HD | P | 3396572 |
VICTORY AIR | HRP | C | 05/11/2007 | BY FINAL NEED REFRIGERANT LABELS AND FLOW LABELS | ERIC | ERIC | | HRP | C | 3397452 |
PUEBLO SHEET METAL WORKS INC | HV | P | 05/11/2007 | UNIT HEATER VENTS IN GARDEN CENTER, RECIEVING AND AUTO CENTER-OK SEAL NEW VENT JOINT IN AUTO CENTER BY FINAL. HAVE QUESTIONS ON SINGLEWALL VENTS IN CONCEALED LOCATIONS AT ALL VESTBIULE UNIT HEATERS. WILL NEED SITE SPECIFIC, MODEL SPECIFIC APPROVAL FROM MANUFACTURER AND MECHANICAL ENGINEER FOR THE ENTIRE VENTING SYSTEM ON UNIT HEATERS, INCLUDING LENGTH, CONCEALED LOCATION, UNCONDITIONED SPACE. IF ALLOWED WILL NEED PROPER SUPPORT ON VENTS. NEED WATER HEATER VENT. | ERIC | ERIC | | HV | P | 3396562 |
PUEBLO SHEET METAL WORKS INC | HD | P | 05/03/2007 | OK TO WRAP ALL DUCT ON WEST SIDE, OK TO WRAP ROUGH DUCT ON EAST AND NORTH SIDES. NO DAMPER FRAMING YET. | ERIC | ERIC | | HD | P | 3396548 |
PUEBLO SHEET METAL WORKS INC | HD | P | 03/20/2007 | OK TO WRAP THE FOLLOWING AREAS OF ROUGH DUCT-RTU-1, RTU-3, RTU-9, RTU-10, RTU-27, RTU-31, RTU-32 AND EF-10. SEE YELLOW HIGHLITES ON APPROVED SET. ALL OTHER AREAS OF DUCTING MISSED SEALING OR HAVEN'T STARTED SEALING, AREAS OF BROKEN DUCTS OR INCOMPLETE DUCTS. COMPLETE SECTIONS AND IDENTIFY AT INSPECTION REQUEST WHICH AREAS ARE READY FOR INSPECTION. | ERIC | ERIC | | HD | P | 3396555 |
INTERSTATE MECHANICAL, INC. | H16 | C | 02/15/2007 | TRAINING WITH ERIC INSIDE GAS | TIM | TIM | | H16 | C | 3396662 |
INTERSTATE MECHANICAL, INC. | HC | C | 02/15/2007 | OK FOR METER. NEED APPROVAL LETTER FOR ELEVATED PRESSURE. | ERIC | ERIC | | HC | C | 3396655 |
INTERSTATE MECHANICAL, INC. | HI | P | 02/15/2007 | 60# TEST. NEED LETTER FROM CSPU FOR ELEVATED PRESSURE, REVISE PLANS TO SHOW CORRECT METER LOCATION, MEDIUM PRESSURE LABELS, GAS DROPS TO INSIDE EQUIPMENT, GAS TIE INS AND PRESSURE REGS AND REG VENTS, PLUG 4 FUTURE STUBS. | ERIC | ERIC | | HI | P | 3396647 |
INTERSTATE MECHANICAL, INC. | P= | C | 07/16/2007 | | TIM | TIM | | P= | C | 3396874 |
INTERSTATE MECHANICAL, INC. | P= | P | 07/13/2007 | NEED PROPER EXPANSION TANK AT MAIN WATER HEATERS ALSO NEED TO GO THRU PHOTO LAB REST OK | TIM | TIM | | P= | P | 3396866 |
INTERSTATE MECHANICAL, INC. | PTO | C | 07/12/2007 | | TIM | TIM | | PTO | C | 3396858 |
INTERSTATE MECHANICAL, INC. | P= | P | 07/12/2007 | STILL NEED EXPANSION TANK AT MAIN WATER HEATER, RE-PIPE CHEMICAL STATIONS AT AT MOP SINKS, FINISH PIPE INSULATION, STILL HAS 1 FLOOR DRAIN COVERED, RE-CHECK WATER TEMPS, CAP LINES TO FUTURE ICE MACHINE NEED ACCESS TO PHARMACY | TIM | TIM | | P= | P | 3396851 |
INTERSTATE MECHANICAL, INC. | P= | R | 07/11/2007 | NEED FLOOR DRAINS AT DISPLAYS IN VIEW, CHECK ALL WATER TEMPS SOME TO HOT SOME NOT HOT ENOUGH, FINISH ALL PIPE INSULATION, LEAK ON DRINKING FOUNTAIN IN FRONT, SECURE RP DEVICE IN TLE, ALL RPS ARE LEAKING, BREAK ROOM FAUCET LOOSE, CUT TRAP PRIMER OFF IN SUBWAY AND INSTALL STRAINER, NEED ACCESS TO PHARMACY, ACCESS TO HAMMER ARESTORS | TIM | TIM | | P= | R | 3396845 |
INTERSTATE MECHANICAL, INC. | P= | P | 06/05/2007 | PUBLIC RESTROOMS ONLY | TIM | TIM | | P= | P | 3396837 |
INTERSTATE MECHANICAL, INC. | PTO | P | 05/01/2007 | TLE OK | TIM | TIM | | PTO | P | 3396831 |
INTERSTATE MECHANICAL, INC. | PTO | P | 04/26/2007 | SUBWAY AND 2-2" DRAINS FOR FUTURE TENANT | TIM | TIM | | PTO | P | 3396823 |
INTERSTATE MECHANICAL, INC. | PTO | P | 04/20/2007 | DELI, BAKERY, SEAFOOD, VEGI PREP, FRONT MECHANICAL ROOM | TIM | TIM | | PTO | P | 3396816 |
INTERSTATE MECHANICAL, INC. | PRD | C | 04/06/2007 | ALL ROOF DRAINS COMPLETE | TIM | TIM | | PRD | C | 3396809 |
INTERSTATE MECHANICAL, INC. | PRD | P | 04/05/2007 | NORTH END DRAINS 1,2,3 | TIM | TIM | | PRD | P | 3396802 |
INTERSTATE MECHANICAL, INC. | PTO | P | 04/05/2007 | PHOTO LAB OK | TIM | TIM | | PTO | P | 3396795 |
INTERSTATE MECHANICAL, INC. | PB | C | 04/04/2007 | | TIM | TIM | | PB | C | 3396788 |
INTERSTATE MECHANICAL, INC. | PRD | P | 04/04/2007 | SOUTH END DRAINS 4,5,6 | TIM | TIM | | PRD | P | 3396780 |
INTERSTATE MECHANICAL, INC. | PTO | P | 04/02/2007 | FRONT BATHROOMS PLUS HAIR SALON, PHARMACY, AND VISION | TIM | TIM | | PTO | P | 3396774 |
INTERSTATE MECHANICAL, INC. | PRD | P | 04/02/2007 | SOUTH END DRAINS 1,2, AND 3 | TIM | TIM | | PRD | P | 3396768 |
INTERSTATE MECHANICAL, INC. | PTO | P | 03/19/2007 | REAR PUBLIC AND FAMILY RESTROOMS AND THE JANITORS ROOM | TIM | TIM | | PTO | P | 3396762 |
INTERSTATE MECHANICAL, INC. | PB | P | 02/27/2007 | ALL DWV COMPLETE NEED APPROVED PLAN FOR SUBWAY | TIM | TIM | | PB | P | 3396754 |
INTERSTATE MECHANICAL, INC. | PB | P | 02/21/2007 | BACK REST ROOMS GREASE LINE TO PIT | TIM | TIM | | PB | P | 3396748 |
INTERSTATE MECHANICAL, INC. | PB | P | 02/14/2007 | LOADING DOCK | TIM | TIM | | PB | P | 3396737 |
INTERSTATE MECHANICAL, INC. | PB | P | 01/23/2007 | SUBWAY AREA | TIM | TIM | | PB | P | 3396728 |
INTERSTATE MECHANICAL, INC. | PB | P | 01/22/2007 | FRONT GROCERY AREA AND TRUNK TO SUBWAY | TIM | TIM | | PB | P | 3396722 |
INTERSTATE MECHANICAL, INC. | PB | P | 01/09/2007 | REAR COOLER SECTION FLOOR DRAINS VENTS AND CLEANOUTS YELLOW HIGH LIGHT MASTER PLAN | TIM | TIM | | PB | P | 3396716 |
INTERSTATE MECHANICAL, INC. | PB | P | 12/19/2006 | TRUNK LINE AND RISERS NORTH SIDE EAST TO WEST GREASE AND WASTE...YELLOW HIGH LIGHT MASTER PLAN | TIM | TIM | | PB | P | 3396711 |
INTERSTATE MECHANICAL, INC. | PB | P | 12/14/2006 | LINE TO FISH TANK AREA, LINE TO GARDEN CENTER, LINE TO GREASE TRAP, LINE AND BATH GROUP IN TLE (TIRE LUBE EXPRESS) | TIM | TIM | | PB | P | 3396703 |
INTERSTATE MECHANICAL, INC. | PB | P | 12/08/2006 | MAIN TRUNCK AND RISERS GM PORTION (SOUTH END OF BUILDING) COMPLETE FROM EAST TO WEST FOUNDATION HIGHLIGHTED IN BLUE MASTER SET | TIM | TIM | | PB | P | 3396694 |