FRY CONSTRUCTION COMPANY | B= | C | 01/09/2007 | | JIMA | JIMA | | B= | C | 3403421 |
FRY CONSTRUCTION COMPANY | B= | P | 01/08/2007 | PIPE PROTECTION UNDER SINKS / BATHROOM WALLS OK PER JIM PEPPER AROUND WATER CLOSETS AND URNALS | JIMA | JIMA | | B= | P | 3403411 |
FRY CONSTRUCTION COMPANY | BSP | P | 11/03/2006 | NEED ENG REPORT FOR STRUCTURAL AND WELDING | BLAKE | BLAKE | | BSP | P | 3403403 |
FRY CONSTRUCTION COMPANY | BIN | C | 10/12/2006 | OK INSULATON, PERSCRIPTIVE METHOD CALLS FOR R5- R11 INSTALLED | JIMP | JIMP | | BIN | C | 3403396 |
FRY CONSTRUCTION COMPANY | BIN | P | 10/09/2006 | ROCK AT OWN RISK N EXT. WALLS --- NEED RES CK OKING R-11 AT XT. WALLS / OR NOTE IN COMPUTER FROM PLAN CK DEPT STATING INSU. REQUIREMENTS N/A | JIMA | JIMA | | BIN | P | 3403389 |
FRY CONSTRUCTION COMPANY | BFR | P | 09/25/2006 | OK PENDING OTHER TRADES | BLAKE | BLAKE | | BFR | P | 3403380 |
FRY CONSTRUCTION COMPANY | BFT | C | 09/25/2006 | | BLAKE | BLAKE | | BFT | C | 3403372 |
FRY CONSTRUCTION COMPANY | E= | C | 01/22/2007 | CONTRACTOR SENT IN GFCI TEST REPORT ON NEW MAIN BREAKER, HAS BEEN SCANNED INTO IMAGES. | DEAN | DEAN | | E= | C | 3403427 |
KENNY ELECTRIC SERVICE, INC. | E= | C | 01/08/2007 | CONTRACTOR TO SEND RBD THE GFCI TEST REPORT. | DEAN | DEAN | | E= | C | 3403365 |
KENNY ELECTRIC SERVICE, INC. | E= | P | 01/04/2007 | ---------OK TO OCCUPY SPACE----------------ITEMS TO BE COMPLETED: RTU-1 MAX BREAKER 60-AMP, CLARIFY PANEL SCHEDULES FOR RECEPTS, INSTALL HANDLE TIES FOR BREAKERS FEEDING FURNITURE, PROVIDE GFCI TEST REPORT FOR NEW SERVICE. | DEAN | DEAN | | E= | P | 3403356 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 01/02/2007 | FLEX SUPPORTED ABOVE CEILING FOR POWER POLES OK. | DEAN | DEAN | | ER | P | 3403348 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 12/19/2006 | CEILINGS MARKED ON PRINTS, STILL NEED TO SEE SUPPORT ON FLEX TO 2 POWER POLES, ID ON PRINTS. | DEAN | DEAN | | ER | P | 3403341 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 12/15/2006 | ABOVE CEILING IN BIG LAB ROOM | GARY | GARY | | ER | P | 3403332 |
KENNY ELECTRIC SERVICE, INC. | ES | C | 12/08/2006 | COMMERCIAL SERVICE: 2500-AMP 4 WIRE NEW SERVICE BY KENNY ELEC. | DEAN | DEAN | | ES | C | 3403324 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 12/05/2006 | ------------------FOR FINAL HAVE GFCI TEST REPORT ON SITE------------------------ABOVE CEILING, AREA MARKED ON PRINTS. | DEAN | DEAN | | ER | P | 3403316 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 12/01/2006 | CEILINGS MARKED ON PRINTS. | DEAN | DEAN | | ER | P | 3403308 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 11/13/2006 | HARD LID FOR LONG HALL BY ELECTRIC ROOM | JERRY | JERRY | | ER | P | 3403300 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 10/20/2006 | SOFFITS AND HARD LIDS | GARY | GARY | | ER | P | 3403293 |
KENNY ELECTRIC SERVICE, INC. | ES | P | 10/12/2006 | COMMERCIAL SERVICE: OK TO SUB FEED MDP 3 FROM MDP1 UNTIL TRANSFORMER AND NEW GEAR IS CONPLETE, TRANSFORMER TO CHANGE IS 300-15342266-CNOB-5 | GARY | GARY | | ES | P | 3403285 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 09/27/2006 | NORTH OFFICES AND LAB WALLS ONLY | GARY | GARY | | ER | P | 3403276 |
KENNY ELECTRIC SERVICE, INC. | ER | P | 09/22/2006 | NORTH WALLS, CONFERENCE ROOM WALLS, OFFICES WALLS | GARY | GARY | | ER | P | 3403269 |
KENNY ELECTRIC SERVICE, INC. | EUG | P | 09/13/2006 | UNDER SLAB | GARY | GARY | | EUG | P | 3403261 |
HVAC SOLUTIONS, INC. | H= | C | 01/04/2007 | RECEIVED BALANCE REPORT FROM HVAC SOLUTIONS, INC. | LYNNS | LYNNS | | H= | C | 3403537 |
HVAC SOLUTIONS, INC. | H= | P | 01/02/2007 | HVAC FINAL PENDING BALANCE REPORT. | LYNNS | LYNNS | | H= | P | 3403529 |
ARTISAN PIPE SYSTEMS, INC. | H= | C | 12/28/2006 | GAS FINAL. | LYNNS | LYNNS | | H= | C | 3403553 |
HVAC SOLUTIONS, INC. | H= | P | 12/15/2006 | BOTH LABS OK FOR TILE. | LYNNS | LYNNS | | H= | P | 3403522 |
HVAC SOLUTIONS, INC. | HD | P | 12/11/2006 | ROUGH DUCT IN EAST LAB OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3403514 |
ARTISAN PIPE SYSTEMS, INC. | HI | C | 12/11/2006 | 10# TEST AND DESIGN OK. | LYNNS | LYNNS | | HI | C | 3403546 |
HVAC SOLUTIONS, INC. | HD | P | 12/07/2006 | ROUGH DUCT COMPLETE IN LAB 267, OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3403505 |
HVAC SOLUTIONS, INC. | H= | P | 12/01/2006 | OFFICE AREA OK TO DROP TILE. | LYNNS | LYNNS | | H= | P | 3403498 |
HVAC SOLUTIONS, INC. | HD | P | 11/30/2006 | ALL DUCT EXCEPT FOR NORTH RUN IN LAB 267 OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3403490 |
HVAC SOLUTIONS, INC. | HD | P | 11/20/2006 | SUPPLY DUCTS IN LAB 267 OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3403482 |
HVAC SOLUTIONS, INC. | HD | P | 11/13/2006 | 58/34 SUPPLY DUCT ON SOUTH SIDE OF LAB 267 OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3403474 |
HVAC SOLUTIONS, INC. | HD | P | 11/06/2006 | ROUGH DUCT ON RETURN AIR 58/34 FROM COL. 6 1/2 TO 5 OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3403465 |
HVAC SOLUTIONS, INC. | HD | P | 11/02/2006 | 58/34 RETURN DUCT FROM COL. 6 1/2 TO 9 OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3403457 |
HVAC SOLUTIONS, INC. | HD | P | 10/11/2006 | ROUGH DUCT IN UPS ROOM AND TWO ROOMS NORTH OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3403449 |
HVAC SOLUTIONS, INC. | HD | P | 10/05/2006 | PARTIAL ROUGH DUCT ON SOUTH/WEST AREA, OK TO INSULATE. | LYNNS | LYNNS | | HD | P | 3403442 |
HVAC SOLUTIONS, INC. | HD | P | 10/02/2006 | PARTIAL ROUGH DUCT ON NORTH HALF OF BUILDING, OK TO INSULATE. NEED TO SEE ALL FINAL CONNECTIONS TO RTU'S. | LYNNS | LYNNS | | HD | P | 3403435 |
ARTISAN PIPE SYSTEMS, INC. | P= | C | 01/02/2007 | | SCOTT | SCOTT | | P= | C | 3403593 |
ARTISAN PIPE SYSTEMS, INC. | P= | P | 12/28/2006 | ADD 2- WATER HEATERS TO JOB DISCRIPTION PLEASE, W/H ABOVE MOP SINK LACKS EXPANSION DEVICE, ALSO APPEARS T&P LACKS 1" AIR GAP AT PAN, OTHER W/H ABOVE RESTROOM NEEDS TO BE RAISED UP IN PAN WHEN PIPING EXPANSION DEVICE TUBING INTO IT | LEE | LEE | | P= | P | 3403585 |
ARTISAN PIPE SYSTEMS, INC. | PTO | C | 10/02/2006 | MENS, AND LADIES ROOM DWV, AND WATER OK. MODIFIED JANITORS SINK, AND FLOOR SINK VENT. | SCOTT | SCOTT | | PTO | C | 3403577 |
ARTISAN PIPE SYSTEMS, INC. | PTO | P | 09/28/2006 | BREAK ROOM H20 AND DWV OK | LEE | LEE | | PTO | P | 3403569 |
ARTISAN PIPE SYSTEMS, INC. | PB | C | 09/13/2006 | WILL CHECK TRAP PRIMERS ON PTO (PER DRAWINGS), REQUIRED C/OUTS AT RESTROOM (4" EOL) AND MOP SINK VENT | LEE | LEE | | PB | C | 3403561 |