ELDER CONSTRUCTION, INC. | B= | C | 03/04/2008 | FIRE FINAL INSPECTION SIGNED OFF ON PERMIT BY KRISS JOHNSON ON 2/29/08 | DANF | DANF | | B= | C | 3474478 |
ELDER CONSTRUCTION, INC. | BFR | P | 01/18/2008 | FRONT ENTRY ROOF FRAMING OK/NEED MECHANICAL ROUGH COMPLETED | BERTW | BERTW | | BFR | P | 3474470 |
ELDER CONSTRUCTION, INC. | BFR | P | 12/06/2007 | ELEVATOR FURRED WALLS ON 3 FLOORS OK | DANF | DANF | | BFR | P | 3474462 |
ELDER CONSTRUCTION, INC. | BIN | P | 11/16/2007 | NEED INSULATION CERTIFICATION STAMPED BY RBD | DANF | DANF | | BIN | P | 3474455 |
ELDER CONSTRUCTION, INC. | BIN | R | 11/14/2007 | NEED COMMCHECK TO DO INSULATION ISPECTION | DANF | DANF | | BIN | R | 3474447 |
ELDER CONSTRUCTION, INC. | BFR | P | 11/14/2007 | FRAMING OF BATHS, JANITOR CLOSETS AND ELECTRICAL ROOMS OK | DANF | DANF | | BFR | P | 3474441 |
ELDER CONSTRUCTION, INC. | BLA | C | 11/06/2007 | | DANF | DANF | | BLA | C | 3474435 |
ELDER CONSTRUCTION, INC. | BLA | P | 11/02/2007 | NORTH SIDE, NORTH 1/2 OF WEST SIDE OK | DANF | DANF | | BLA | P | 3474427 |
ELDER CONSTRUCTION, INC. | BFR | P | 10/29/2007 | ENGINEER'S LETTER ON FILE FOR REVIEW OF SITE WORK COMPLETED IN ACCORDANCE WITH THE APPROVED PLANS; #16494, WILLIAM E. WHITE, HCDA ENGINEERING | DANF | DANF | | BFR | P | 3474413 |
ELDER CONSTRUCTION, INC. | BLA | P | 10/22/2007 | EAST SIDE AND SOUTH SIDE OK | DANF | DANF | | BLA | P | 3474405 |
ELDER CONSTRUCTION, INC. | BIN | P | 10/17/2007 | INSPECTION OF CEILING UNDER HVAC EQUIPMENT ON ROOF OK; MET WITH HCDA PE STEVE HORNER; RE THE 6 ITEMS NOTED DURING FRAMING INSPECTION. SEVERAL OF THE ITEMS WERE DETAILED AND SENT TO ELDER WHICH WILL BE INSPECTED AT NEXT INSPECTION PER SUPER. STEVE WILL WRITE A STAMPED LETTER TO COVER OTHER ITEMS. 3RD PARTY STRUCTURAL INSPECTION LETTER TO COME. | DANF | DANF | | BIN | P | 3474396 |
ELDER CONSTRUCTION, INC. | BFR | P | 10/09/2007 | TRUSSES OK; NEED ENGINEERING LETTER OF INSPECTION FOR ITEMS NOTED ON 14 SEPT O7 FRAME INSPECTION AND LETTER ON STRUCTURAL ELEMENTS OF BUILDING, WELDS, BOLTING AND BEAM SIZING AND COLUMNS AND BAR JOISTS | DANF | DANF | | BFR | P | 3474387 |
ELDER CONSTRUCTION, INC. | BFR | R | 10/08/2007 | TRUSS INSPECTION; 1) MISSING LATERAL BRACING AT T17, T10, T40 2) SWAY BRACE LATERAL BRACING AT T105 | DANF | DANF | | BFR | R | 3474380 |
ELDER CONSTRUCTION, INC. | BLA | P | 09/28/2007 | A TOP OF ROOF MEZ. | FRANK | FRANK | | BLA | P | 3474372 |
ELDER CONSTRUCTION, INC. | BSP | P | 09/28/2007 | FRAMING OK AT ALL ELECTRIC ROOMS ONLY ALL FLOORS | FRANK | FRANK | | BSP | P | 3474363 |
ELDER CONSTRUCTION, INC. | BLA | R | 09/27/2007 | WEEP SCREED ISN INCORRECT / NEEDS TO BE 3 1/2'' ON THE VERTICAL NOT 1'' | JEREMY | JEREMY | | BLA | R | 3474355 |
ELDER CONSTRUCTION, INC. | BFR | P | 09/14/2007 | EXTERIOR WALL FRAMING; NEED THE FOLLOWING; 1) DETAIL TO USE WALL CLIPS INSTEAD OF WELDS 2) LETTER TO USE JAB STUDS AS KINGSTUDS 3) DETAIL FOR HEADER CLIPS 4) NEED TOP OF WALL ATTACHMENT AT SOFFET; SCREWS IN SOFFET AND SPACING 5) DETAIL FOR TRACK TO STEEL BEAM ATTACHMENT 6) TOP OF WALL ATTACHMENT OF STUDS TO STEEL BEAM FOR CONTINIOUS STUDS | DANF | DANF | | BFR | P | 3474347 |
ELDER CONSTRUCTION, INC. | BSP | T | 08/30/2007 | PAID (REC#768063)ADDITIONAL PLAN REVIEW TIME: $50.000 From: DALEH plan splice for m-1 and m-2 sheets | DALEH | DALEH | | BSP | T | 3474340 |
ELDER CONSTRUCTION, INC. | BFR | P | 08/24/2007 | STRUCTURAL FASCIA CONNETIONS OK TO COVER /NEED ENGINEER STAMP ON REVISION TO DETAIL 11 ON SHEET S4 FOR OUSTIDE CORNERS TO 2-PLY HIP CONNECTION BRACKET | BERTW | BERTW | | BFR | P | 3474332 |
ELDER CONSTRUCTION, INC. | BFI | C | 07/05/2007 | UNDER SLAB | DANF | DANF | | BFI | C | 3474323 |
ELDER CONSTRUCTION, INC. | BFD | C | 06/06/2007 | DAYLITE SOUTHEAST CORNER OF BUILDING | DANF | DANF | | BFD | C | 3474315 |
ELDER CONSTRUCTION, INC. | BFN | C | 05/31/2007 | UFER OK | DANF | DANF | | BFN | C | 3474307 |
ELDER CONSTRUCTION, INC. | BFD | P | 05/31/2007 | NORTH 1/2 OF BUILDING OK SEE SHEET S1 OF APPROVED PLANS | DANF | DANF | | BFD | P | 3474299 |
ELDER CONSTRUCTION, INC. | BFN | P | 05/24/2007 | SEE APPROVED PLANS SHEET S1 | DANF | DANF | | BFN | P | 3474291 |
ELDER CONSTRUCTION, INC. | BFT | C | 05/17/2007 | | DANF | DANF | | BFT | C | 3474282 |
ELDER CONSTRUCTION, INC. | BBB | P | 05/14/2007 | NEED ENGINEERING REPORT FOR BOND BEAMS @ ELEVATOR SHAFT CMU | BERTW | BERTW | | BBB | P | 3474274 |
ELDER CONSTRUCTION, INC. | BFT | P | 05/14/2007 | SEE SHEET S.1 FOR AREAS INSPECTED | BERTW | BERTW | | BFT | P | 3474266 |
ELDER CONSTRUCTION, INC. | BBB | P | 05/04/2007 | BEAM NOT READY; ENGINEER WILL DO ISNPECTION AT 10' | DANF | DANF | | BBB | P | 3474260 |
ELDER CONSTRUCTION, INC. | BFN | P | 04/19/2007 | ELEVATOR FOUNDATION WALLS AND INTERIOR FDN WALL OK; SEE APPROVED PLANS SHEET S1 | DANF | DANF | | BFN | P | 3474253 |
ELDER CONSTRUCTION, INC. | BFT | P | 04/16/2007 | SEE APPROVED PLANS SHEET S1; DRAIN, ENTIRE; NEED COMPACTION TESTS | DANF | DANF | | BFT | P | 3474245 |
MATRIX ELECTRIC, INC. | E= | C | 02/01/2008 | | MIKEC | MIKEC | | E= | C | 3474709 |
MATRIX ELECTRIC, INC. | ER | C | 01/10/2008 | DROPPED CEILINGS AND ENTRY SOFFITT | MIKEC | MIKEC | | ER | C | 3474701 |
MATRIX ELECTRIC, INC. | EUG | P | 11/16/2007 | WEST SIDEWALL LIGHTS CONDUITS | MIKEC | MIKEC | | EUG | P | 3474693 |
MATRIX ELECTRIC, INC. | ER | P | 11/09/2007 | BATHROOM SOFFITTS | MIKEC | MIKEC | | ER | P | 3474687 |
MATRIX ELECTRIC, INC. | ER | P | 11/06/2007 | STAIRWELLS AND BATH WALLS | MIKEC | MIKEC | | ER | P | 3474680 |
MATRIX ELECTRIC, INC. | ER | P | 10/31/2007 | SOFFITT LIGHTS | MIKEC | MIKEC | | ER | P | 3474673 |
MATRIX ELECTRIC, INC. | ES | P | 10/29/2007 | COMMERCIAL SERVICE: NEED PAPER WORK ON GFI TEST | MIKEC | MIKEC | | ES | P | 3474665 |
MATRIX ELECTRIC, INC. | EUG | C | 10/26/2007 | | MIKEC | MIKEC | | EUG | C | 3474656 |
MATRIX ELECTRIC, INC. | ER | P | 10/24/2007 | SEE PLANS | MIKEC | MIKEC | | ER | P | 3474646 |
MATRIX ELECTRIC, INC. | ES | P | 10/04/2007 | COMMERCIAL SERVICE: 1000 AMP 480V C-T METERED MATRIX ELEC | MIKEC | MIKEC | | ES | P | 3474639 |
MATRIX ELECTRIC, INC. | ER | P | 09/26/2007 | UFER CADWELDED | MIKEC | MIKEC | | ER | P | 3474630 |
MATRIX ELECTRIC, INC. | EUG | C | 09/11/2007 | POLE LIGHT CONDUITS | MIKEC | MIKEC | | EUG | C | 3474622 |
MATRIX ELECTRIC, INC. | ESL | C | 07/05/2007 | | MIKEC | MIKEC | | ESL | C | 3474614 |
MATRIX ELECTRIC, INC. | EUG | P | 06/06/2007 | SECONDARY CONDUITS | MIKEC | MIKEC | | EUG | P | 3474606 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | C | 02/19/2008 | | JACK | JACK | | H= | C | 3474525 |
COLORADO SHEET METAL CO., INC. | HD | C | 01/24/2008 | | JACK | JACK | | HD | C | 3474238 |
COLORADO SHEET METAL CO., INC. | H= | C | 01/24/2008 | SHELL ONLY | JACK | JACK | | H= | C | 3474230 |
COLORADO SHEET METAL CO., INC. | HD | P | 11/19/2007 | FIRE/SMOKE DAMPER FRAMING ON 2ND AND 3RD FLOORS OK. | LYNNS | LYNNS | | HD | P | 3474222 |
COLORADO SHEET METAL CO., INC. | HD | P | 10/26/2007 | SEE PAGES M-1, M-2 AND M-3 FOR DUCTS AND DATES INSPECTED. SUPPLY AIR SMOKE AND FIRE DAMPER AT 1ST FLOOR PENETRATION OK, OK TO WRAP ALL SUPPLY AIR 1ST FLOOR. SUPPLY AIR IN SHAFT, 2ND AND 3RD FLOOR, OK TO WRAP..OK TO WRAP ALL 3RD FLOOR SUPPLY. RETURN AIR FIRE/SMOKE IN 2ND FLOOR SHAFT OK. RETURN AIR 1ST FLOOR ABOVE BATHROOMS OK. EXHAUST DUCT ABOVE 1ST AND 2ND FLOOR BATHROOMS OK. FIRE/SMOKE DAMPERS ON EXHAUST DUCT 1ST AND 2ND FLOOR OK. | NANCY | NANCY | | HD | P | 3474214 |
HARMON - BONDED PLUMBING & HEATING, INC. | HC | C | 10/26/2007 | OK FOR METER. | LYNNS | LYNNS | | HC | C | 3474517 |
COLORADO SHEET METAL CO., INC. | HD | P | 10/25/2007 | 2ND FLOOR RETURN AIR FIRE/SMOKE DAMPER: ANNULAR SPACE AND FRAMING OK. NO OTHER FIRE/SMOKE DAMPERS INSPECTED. 1ST AND 2ND FLOOR SUPPLY AIR DUCTS OUTSIDE OF SHAFT OK TO WRAP. 3RD FLOOR SUPPLY AIR DUCTS OUTSIDE OF SHAFT OK TO WRAP EXCEPT FOR HI PRESSURE SIDE TO VAV 308. | NANCY | NANCY | | HD | P | 3474205 |
HARMON - BONDED PLUMBING & HEATING, INC. | HI | C | 10/12/2007 | 60# TEST ON ELEVATED PRESSURE GAS AND DESIGN OK. | LYNNS | LYNNS | | HI | C | 3474509 |
COLORADO SHEET METAL CO., INC. | HD | P | 10/05/2007 | F/S DAMPER FRAMING AND DAMPERS IN THE ELEVATOR EQUIPTMENT ROOM OK. | LYNNS | LYNNS | | HD | P | 3474196 |
COLORADO SHEET METAL CO., INC. | HD | P | 09/13/2007 | 3RD FLOOR RISER DUCT TO RTU OK TO COVER. | LYNNS | LYNNS | | HD | P | 3474185 |
COLORADO SHEET METAL CO., INC. | HD | P | 09/13/2007 | 3RD FLOOR RISER DUCT TO RTU OK TO COVER. | LYNNS | LYNNS | | HD | P | 3474177 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | C | 02/07/2008 | | MARTY | MARTY | | P= | C | 3474590 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | P | 02/04/2008 | INSULATION ON LAV TRAPS AND WATER,RAISE W/HEATER OUT OF PAN. | MARTY | MARTY | | P= | P | 3474582 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | C | 11/29/2007 | | MARTY | MARTY | | PTO | C | 3474575 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | P | 11/14/2007 | ALL BATHS, NEXT TIME ALL COMPLETE. | MARTY | MARTY | | PTO | P | 3474566 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | R | 11/13/2007 | NOT READY | MARTY | MARTY | | PTO | R | 3474557 |
HARMON - BONDED PLUMBING & HEATING, INC. | PRD | C | 10/11/2007 | | MARTY | MARTY | | PRD | C | 3474549 |
HARMON - BONDED PLUMBING & HEATING, INC. | PB | C | 06/11/2007 | | MARTY | MARTY | | PB | C | 3474542 |
HARMON - BONDED PLUMBING & HEATING, INC. | PRD | P | 06/11/2007 | UNDERGROUND. | MARTY | MARTY | | PRD | P | 3474534 |
KONE, INC. | V= | C | 02/20/2008 | ELEVATOR COMPLETE | JOHNW | JOHNW | | V= | C | 3474598 |