PINKARD CONSTRUCTION COMPANY | B= | C | 03/21/2008 | | BOBB | BOBB | | B= | C | 3488196 |
PINKARD CONSTRUCTION COMPANY | B= | P | 01/29/2008 | ENGINEERS LETTER ON FILE FOR STEEL STRUCTURE / NEED WELD CERTIFICATIONS TO FILE / COMPLETE OTHER FINAL INSPECTIONS. | BOBB | BOBB | | B= | P | 3488188 |
PINKARD CONSTRUCTION COMPANY | B= | P | 01/17/2008 | NEED WELD CERTIFICATIONS& ENGINEERS LETTER FOR STRUCTURAL STEEL TO FILE / COMPLETE SECURITY & COMMUNICATIONS FOR FIRE INSPECTION / COMPLETE OTHER FINAL INSPECTIONS. | BOBB | BOBB | | B= | P | 3488180 |
PINKARD CONSTRUCTION COMPANY | BFR | C | 01/17/2008 | | BOBB | BOBB | | BFR | C | 3488172 |
PINKARD CONSTRUCTION COMPANY | B= | P | 12/12/2007 | INSTALL BUILDING ADDRESS NUMBERS / COMPLETE OTHER INSPECTIONS. | BOBB | BOBB | | B= | P | 3488164 |
PINKARD CONSTRUCTION COMPANY | BFR | P | 11/16/2007 | FRAME INSPECTION OK WITH OTHER ROUGH INSPECTIONS. | BOBB | BOBB | | BFR | P | 3488156 |
PINKARD CONSTRUCTION COMPANY | B= | P | 11/15/2007 | OK 1ST FLOOR , NORTH SIDE WITH OTHER INSPECTIONS & 2ND FLOOR ROOMS; 9 TO 10.3 & B TO C LINES. | BOBB | BOBB | | B= | P | 3488148 |
PINKARD CONSTRUCTION COMPANY | BSP | T | 10/30/2007 | PAID (REC#777737)ADDITIONAL PLAN REVIEW TIME: $50.000 From: SHELBY | SHELBY | SHELBY | | BSP | T | 3488140 |
PINKARD CONSTRUCTION COMPANY | BIN | C | 10/22/2007 | OK R - 19 INSULATION ; 1 TO 6 ON B LINE & B TO D ON 1 LINE. | BOBB | BOBB | | BIN | C | 3488131 |
PINKARD CONSTRUCTION COMPANY | BFR | P | 10/22/2007 | OK EXTERIOR WALL FRAMING ; 1 TO 6 ON B LINE & B TO D ON 1 LINE. | BOBB | BOBB | | BFR | P | 3488122 |
PINKARD CONSTRUCTION COMPANY | BIN | P | 10/18/2007 | OK R - 19 INSULATION; 1 TO 6 ON B LINE & 1 TO 6 ON F LINE , 1 ST FLOOR. | BOBB | BOBB | | BIN | P | 3488114 |
PINKARD CONSTRUCTION COMPANY | BIN | P | 10/16/2007 | OK R- 19 EXTERIOR WALL INSULATION; 1 TO6 ON F & G LINES & B TO F ON 1 LINE , 2 ND FLOOR. | BOBB | BOBB | | BIN | P | 3488104 |
PINKARD CONSTRUCTION COMPANY | BFR | P | 10/16/2007 | OK EXTERIOR WALL FRAMING ; 1 TO 6 ON F& G LINES & B TO F ON 1 LINE , 2ND FLOOR. | BOBB | BOBB | | BFR | P | 3488097 |
PINKARD CONSTRUCTION COMPANY | BIN | P | 10/01/2007 | OK R- 19 INSULATION , 2ND FLOOR , NORTH HALF. | BOBB | BOBB | | BIN | P | 3488088 |
PINKARD CONSTRUCTION COMPANY | BFR | P | 09/28/2007 | OK 2ND FLOOR WALLS; 7.5 TO 12 BETWEEN A & F LINE | BOBB | BOBB | | BFR | P | 3488081 |
PINKARD CONSTRUCTION COMPANY | BFR | R | 09/27/2007 | REMOVE ALL SCREWS FOR STUDS AT SLIP TRACK | BOBB | BOBB | | BFR | R | 3488075 |
PINKARD CONSTRUCTION COMPANY | BFR | P | 09/18/2007 | OK FRAMING FOR EXTERIOR WALLS; 7.5 TO 12 BETWEEN A & F LINES | BOBB | BOBB | | BFR | P | 3488067 |
PINKARD CONSTRUCTION COMPANY | BIN | P | 09/18/2007 | OK INSULATION FOR EXTERIOR WALLS; 7.5 TO 12 ON F LINE , 7.5 TO 12 ON B LINE , B TO C O0N 12 LINE , & E TO F ON 12 LINE. | BOBB | BOBB | | BIN | P | 3488060 |
PINKARD CONSTRUCTION COMPANY | BFD | C | 08/16/2007 | | BOBB | BOBB | | BFD | C | 3488051 |
PINKARD CONSTRUCTION COMPANY | BFD | P | 08/10/2007 | OK FOUNDATION INSULATION & WATERPROOFING FOR SOUTH HALF OF BUILDING. | BOBB | BOBB | | BFD | P | 3488044 |
PINKARD CONSTRUCTION COMPANY | BSP | P | 08/07/2007 | OK STRUCTURAL STEEL FLOOR AT 2ND FLOOR; 1 TO 5.75 LINE . | BOBB | BOBB | | BSP | P | 3488037 |
PINKARD CONSTRUCTION COMPANY | BSP | P | 07/30/2007 | OK 2ND FLOOR STRUCTURAL STEEL ; 12 TO 5.75 LINE. | BOBB | BOBB | | BSP | P | 3488028 |
PINKARD CONSTRUCTION COMPANY | BFI | C | 06/19/2007 | | BOBB | BOBB | | BFI | C | 3488021 |
PINKARD CONSTRUCTION COMPANY | BSP | P | 06/14/2007 | OK STRUCTURAL WALL STEEL 1 THRU 9 & 30 THRU 40 & T3 , S1 & S2. | BOBB | BOBB | | BSP | P | 3488012 |
PINKARD CONSTRUCTION COMPANY | BSP | P | 06/05/2007 | OK STRUCTURAL STEEL FOR WALL PANELS ; 10 THRU 29 & T1 & T2 PANELS. | BOBB | BOBB | | BSP | P | 3488004 |
PINKARD CONSTRUCTION COMPANY | BSP | R | 06/04/2007 | RAIN DELAYED CONCRETE POUR / CONTRACTOR TO RECALL INSPECTION. | BOBB | BOBB | | BSP | R | 3487996 |
PINKARD CONSTRUCTION COMPANY | BFT | C | 04/12/2007 | OK REMAINING FOOTING ; 5.9 TO 7.1 ON A & B LINES. | BOBB | BOBB | | BFT | C | 3487988 |
PINKARD CONSTRUCTION COMPANY | BFN | P | 04/10/2007 | OK STEEL FOR ELEVATOR PIT WALLS. | BOBB | BOBB | | BFN | P | 3487980 |
PINKARD CONSTRUCTION COMPANY | BFT | C | 04/10/2007 | OK FOOTING ; A TO G ON 1 LINE | BOBB | BOBB | | BFT | C | 3487973 |
PINKARD CONSTRUCTION COMPANY | BFT | P | 04/06/2007 | OK FOOTINGS; 1 TO 6 ON A & B LINES & 1 TO 6 ON F & G LINES & B.25 ON 1 LINE. | BOBB | BOBB | | BFT | P | 3487964 |
PINKARD CONSTRUCTION COMPANY | BFT | P | 04/03/2007 | OK FOOTINGS; 1 TO 6 ON F& G LINES , 1 TO 6 ON A & B LINES, A TO G ON 1 LINE , OK ELEVATOR FOOTING PAD. | BOBB | BOBB | | BFT | P | 3487957 |
PINKARD CONSTRUCTION COMPANY | BFT | P | 03/30/2007 | OK ALL INTERIOR PADS EXCEPT ELEVATOR PAD / SEE APPROVED PLAN FOR PAD LOCATIONS. / 4500 PSF. | BOBB | BOBB | | BFT | P | 3487949 |
WISE ELECTRIC, INC. | E= | C | 01/10/2008 | | MATTHEW | MATTHEW | | E= | C | 3488481 |
WISE ELECTRIC, INC. | EP | C | 01/09/2008 | need #2 bond wire for transformer l2b5 matt will check next inspection all rest transformers & panels ok | TIMA | TIMA | | EP | C | 3488474 |
WISE ELECTRIC, INC. | E= | P | 01/09/2008 | ELECTRICAL ROOMS OK EXCEPT NEED #2 EQUIPMENT BONDING JUMPER TO PANEL L2B5 | MATTHEW | MATTHEW | | E= | P | 3488467 |
WISE ELECTRIC, INC. | E= | P | 01/08/2008 | INSPECTED SECOND FLOOR, FIRST FLOOR NORTH, RTU'S AND PARKING LOT; EXCLUDING ELEC ROOMS AND FURNITURE HOOK UPS: NEED HANDLE TIES FOR 2 CIRCUITS ON SAME YOKE, 3 WAYS SECOND FLOOR SOUTH WIRED WRONG, NO POWER SECOND FLOOR CONFRENCE ROOM NORTH OUTLET | MATTHEW | MATTHEW | | E= | P | 3488460 |
WISE ELECTRIC, INC. | ER | C | 01/03/2008 | | MATTHEW | MATTHEW | | ER | C | 3488452 |
WISE ELECTRIC, INC. | ER | P | 12/14/2007 | CEILINGS 1ST FLOOR COLUMN LINE 6 SOUTH OK | TIMA | TIMA | | ER | P | 3488443 |
WISE ELECTRIC, INC. | ER | P | 12/04/2007 | SECOND FLOOR CEILING 6 LINE SOUTH | MATTHEW | MATTHEW | | ER | P | 3488435 |
WISE ELECTRIC, INC. | ER | P | 11/26/2007 | 2ND FLOOR CEILINGS COLUMN LINE 7 TO THE NORTH OK | TIMA | TIMA | | ER | P | 3488428 |
WISE ELECTRIC, INC. | ER | P | 11/21/2007 | CEILINGS, HIGHLIGHTED, DATED, DALLENS' PRINT IN WISE OFFICE | GARYL | GARYL | | ER | P | 3488420 |
WISE ELECTRIC, INC. | ER | P | 11/16/2007 | GRID CEILING ON FIRST FLOOR 7 TO 12 AND B TO F, HARDLIDS MARKED ON E 1.1 AND E 1.2 OK | MATTHEW | MATTHEW | | ER | P | 3488412 |
WISE ELECTRIC, INC. | ER | P | 11/15/2007 | HARDLID MARKED ON E 1.2 OK | MATTHEW | MATTHEW | | ER | P | 3488403 |
WISE ELECTRIC, INC. | ER | P | 11/05/2007 | ALL WALLS OK: HARD LIDS-- FIRST FLOOR LOBBY AND SE HALLWAY AND SECOND FLOOR SE HALLWAY HARDLIDS OK | MATTHEW | MATTHEW | | ER | P | 3488397 |
WISE ELECTRIC, INC. | ES | C | 10/31/2007 | COMMERCIAL SERVICE: 2 - 1,000 AMP 3 PHASE 480 V CT METERED SERVICES FOR COMMERCIAL OFFICES BY WISE ELECTRIC: SET METERS FOR 1055 A AND 1055 B | MATTHEW | MATTHEW | | ES | C | 3488389 |
WISE ELECTRIC, INC. | ES | R | 10/26/2007 | NEED GFCI TEST ON 1000 AMP 480 V BREAKER, BUILD TO APPROVED PLANS OR RESUBMITT | MATTHEW | MATTHEW | | ES | R | 3488380 |
WISE ELECTRIC, INC. | ER | P | 10/26/2007 | SECOND FLOOR NORTH HARDLIDS MARKED ON E1.2 | MATTHEW | MATTHEW | | ER | P | 3488373 |
WISE ELECTRIC, INC. | ES | R | 10/24/2007 | NEED 3/0 GEC, INSTALL MAIN BONDING JUMPER AT DISCONNECT, COMPLETE GFCI TEST, BOND NEUTRAL IN CT CAN, BOND METER CAN, JUMPER WATER METER | MATTHEW | MATTHEW | | ES | R | 3488363 |
WISE ELECTRIC, INC. | ER | P | 10/22/2007 | FIRST FLOOR WALLS COLUMN LINE 6 SOUTH OK | MATTHEW | MATTHEW | | ER | P | 3488355 |
WISE ELECTRIC, INC. | ER | P | 10/12/2007 | SECOND FLOOR WALLS COLUMN LINE 6 SOUTH AND HARDLIDS ON FIRST FLOOR MARKED ON PLANS E1.1 OK | MATTHEW | MATTHEW | | ER | P | 3488346 |
WISE ELECTRIC, INC. | ER | P | 09/26/2007 | second floor walls from column line 7 north | MATTHEW | MATTHEW | | ER | P | 3488338 |
WISE ELECTRIC, INC. | ER | P | 09/14/2007 | WALLS COLUMN LINE 7 NORTH | MATTHEW | MATTHEW | | ER | P | 3488330 |
WISE ELECTRIC, INC. | EUG | C | 08/13/2007 | | MATTHEW | MATTHEW | | EUG | C | 3488323 |
WISE ELECTRIC, INC. | EUG | P | 08/03/2007 | PARKING LOT LIGHTS OK | MATTHEW | MATTHEW | | EUG | P | 3488314 |
WISE ELECTRIC, INC. | EUG | P | 07/30/2007 | PARKING LOT MARKED ON PLANS ES1.1 | MATTHEW | MATTHEW | | EUG | P | 3488306 |
WISE ELECTRIC, INC. | EUG | P | 07/25/2007 | PARKING LOT MARKED ON PLANS ES1.1 | MATTHEW | MATTHEW | | EUG | P | 3488298 |
WISE ELECTRIC, INC. | EUG | P | 07/20/2007 | PARKING LOT MARKED ON PLANS ES1.1 | MATTHEW | MATTHEW | | EUG | P | 3488291 |
WISE ELECTRIC, INC. | EUG | P | 07/17/2007 | PARKING LOT MARKED ON PLANS ES1.1 | MATTHEW | MATTHEW | | EUG | P | 3488283 |
WISE ELECTRIC, INC. | ESL | C | 05/10/2007 | CT'S TO MDP'S AND FEEDERS TO FIRST AND SECOND FLOOR ELECTRIC ROOM OK- FLOOR BOXES OK- UFER'S OK | MATTHEW | MATTHEW | | ESL | C | 3488275 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | C | 03/21/2008 | GAS FINAL. | JON | JON | | H= | C | 3488506 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 01/11/2008 | SHELL HVAC FINAL. | JON | JON | | H= | C | 3487942 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 12/21/2007 | ENTRY WAYS BOTH FLOORS OK FOR COVER. NEED BLANCE REPORT INTERLOCKS, ROOF INSPECTION. CO SENSORS SEE OTHER NOTES. | JON | JON | | H= | P | 3487933 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 12/13/2007 | OK FOR CEILING AT 1ST AND 2ND FLOOR SOUTH EXCEPT FOR ROOM 2K 21 AS THERE IS NO RETURN PATH. CONDENSATE FOR SEVER ROOM ON 2ND FLOOR TO RUN TO APPROVED LOCATION AND NOT TO TIE INTO PLUMBING VENT ON 2ND FLOOR. NEED CO SENSORS INSTALLED AND VERIFIED. NEED INTERLOCK FOR EF-1 WITH BOTH ROOF TOP UNITS THAT FEED BATHROOMS..... BALANCE REPORT. | JON | JON | | H= | P | 3487926 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 11/14/2007 | NORTH SIDE 1ST AND 2ND FLOOR OK FOR COVER. FIRESMOKE DAMPERS NOW COMPLETE. | JON | JON | | H= | P | 3487915 |
HARMON - BONDED PLUMBING & HEATING, INC. | HC | C | 10/30/2007 | 60 LB TEST OK FOR METER. NEED 2# SYSTEM RELEASE FROM CSPU TO RBD OFFICE BEFORE FINAL INSPECTION. | JON | JON | | HC | C | 3488500 |
HARMON - BONDED PLUMBING & HEATING, INC. | HI | C | 10/30/2007 | 60 LB TEST GAS TO PLANS. | JON | JON | | HI | C | 3488494 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 10/03/2007 | SEE OTHER INSPECTION DUPLICATE. | JON | JON | | HD | P | 3487907 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 10/03/2007 | FIRESMOKES ON FIRST FLOOR SHELL IN WALLS OK.. ALL SHAFT DAMPERS NEED BREAK AWAY CONNECTIONS TO INSTRUCTIONS. NORTH HARD LID OK FOR COVER 1ST FLOOR. STILL NEED FIRE SMOKE FRAMING 2ND FLOOR WHEN READY X3. QUESTION VENTILATION AIR FOR ELECTRICAL ROOM 1ST FLOOR APPEARS TO NOT COMMUNICATE WITH BUILDING, CONTRACTOR CHECKING ON THIS. | JON | JON | | HD | P | 3487900 |
HARMON - BONDED PLUMBING & HEATING, INC. | HI | P | 10/02/2007 | WALLS ONLY THROUGH ROOF. 2 1/2'' 60 LB TEST AND NEED RELEASE FROM CSPU FOR 2# SYSTEM. | JON | JON | | HI | P | 3488488 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 09/17/2007 | FIRESMOKE DAMPERS X6 OK. | JON | JON | | HD | P | 3487892 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 09/07/2007 | OK FOR WRAP ON 2ND FLOOR MEDIUM PRESSURE. 4- FIRE SMOKE DAMPERS FOR RTUS ONLY. NEED ISSUES WITH REMAINDER OF FIRE SMOKE DAMPERS RESOLVED AS HOLES ARE TO LARGE PER INSTRUCTIONS AT FLOOR PENETRATIONS. NEED TENNANT FINISH DUCT INSPECTIONS CALLED UNDER THAT PERMIT NUMBER. | JON | JON | | HD | P | 3487884 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 09/04/2007 | PLEASE PROVIDE CALL AHEAD ON INSPECTIONS. PLANS LOCKED REVIEW NEXT TRIP. OK FOR WRAP ON 1ST FLOOR NORTH VAV'S X4. FRAMING FOR 2 FIRESMOKE DAMPERS NORTH END. | JON | JON | | HD | P | 3487876 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 08/17/2007 | PLEASE PROIVIDE CALL AHEAD TO AARON ON FUTURE INSPECTIONS... OK FOR WRAP AT 1ST FLOOR MEDIUM PRESSURE ONLY. | JON | JON | | HD | P | 3487869 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | C | 12/18/2007 | | MICK | MICK | | P= | C | 3488545 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | C | 10/19/2007 | | MICK | MICK | | PTO | C | 3488538 |
HARMON - BONDED PLUMBING & HEATING, INC. | PRD | C | 10/02/2007 | | MICK | MICK | | PRD | C | 3488532 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | P | 10/02/2007 | FIRST FLOOR NORTH 1/2 WATER & DWV TESTED AND OK. DWV VENTS FOR FIRST FLOOR ON NORTHEND OF NORTH 1/2 COMPLETED THROUGH ROOF. | MICK | MICK | | PTO | P | 3488524 |
HARMON - BONDED PLUMBING & HEATING, INC. | PB | C | 05/01/2007 | | MICK | MICK | | PB | C | 3488517 |
HARMON - BONDED PLUMBING & HEATING, INC. | PB | P | 04/30/2007 | DWV IS OK. RUN WATER LINE. | SCOTT | SCOTT | | PB | P | 3488512 |
PINKARD CONSTRUCTION COMPANY | V= | C | 01/29/2008 | ELEVATOR COMPLETE PER TOM E. | JOHNW | JOHNW | | V= | C | 3488268 |
PINKARD CONSTRUCTION COMPANY | V= | P | 01/15/2008 | SCHINDLER---LABEL DISCONNECTS--M/R DOOR SIGN--FINISHED FLOOR IN CAR--OPEN J-BOX IN M/R--GUARDRAILS ON CAR TOP--HANDRAILS IN CAR--DO NOT COVER VENTS AT BOTTOM OF WALLS IN CAR--OK FOR TCO WHILE FINISHING ABOVE ITEMS | TOM | TOM | | V= | P | 3488259 |