MEMORIAL HOSPITAL NORTH | H01 | C | 03/05/2024 | 5 YR 9/22 -- ANNUAL 10/23 -- OTIS W/ TKE LOCKBOX -- EMERGENCY ALARM BELL IS NONFUNCTIONAL WHEN CAB 110V IS DISCONNECTED -- PIT LIGHT IS OUT -- NOTE: ITS BELT MONITOR FAILED PER PREVIOUS TEST REPORT -- NOTE: MONITOR ROUGE BELTS FOR WIRES POKING THROUGH -- MONTHLY FIREFIGHTERS LOGS AND QUARTERLY EMERGENCY PHONE LOGS & GENERATOR LOGS W/ BUILDING FACILITIES (Receipt #2039751) | BENH | BENH | | H01 | C | 8013949 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/26/2023 | HO2 -- ANNUAL 9/22 -- OTIS W/ TKE SERVICE & LOCKBOX -- WAS ON-SITE TO CHECK MCP, FIRE SERVICE & TEST EMERGENCY PHONE IN THE ELEVATOR -- CONTACT BO W/ FACILITIES FOR FIRE SERVICE LOGS & GENERATOR TESTING LOGS -- NOTE: ANNUAL TRACTION SAFETY TEST IS DUE BY THE END OF THE MONTH (Receipt #1992051) (cat 1---10/2023, broken member and residual strength detection fails per report PM ) | BENH | BENH | | H02 | C | 7868008 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/16/2023 | 5YR 09/2022 -- OTIS WITH TKE SERVICE AND LOCKBOX --/ PROVIDE PPRBD WITH THE LOCATION OF THE MONTHLY FIRE SERVICE LOGS AND ANNUAL EMERGENCY POWER TESTING LOGS INSIDE THE CONTROL ROOM --/ CAR DOOR IS MISSING THE FACIA FLAG RESTRICTORS IN BETWEEN FLOORS #2 - #5 --/ PIT LIGHT IS OUT --/ PPRBD NOTE: MONITOR OVERHEAD SHEAVE REPAIRS OR MAINTENANCE LOGS AT NEXT VISIT (Receipt #1940061) | MIKEM | MIKEM | | H01 | C | 7688947 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/29/2022 | WITNESSED AT H02 | BENH | BENH | | H02 | C | 7534235 |
MEMORIAL HOSPITAL NORTH | H06 | C | 09/28/2022 | WITNESSED TRACTION SAFETY INSPECTION AND TESTING W/ TK - MISSING FASCIA DOOR RESTRICTOR FLAGS BETWEEN FLOORS 2-3 AND 4-5. NEED ITS BELT MONITOR INSPECTION AND RESET UNIQUE PROCEDURE ONSITE. SHEAVES IN OVERHEAD AT DRIVE MACHINE MAKING METAL ON METAL GRINDING NOISE, NEEDS DIAGNOSED. CLEAN PIT AND CAR TOP. NEED HARD COPY OF OTIS GEN2 UNIQUE TESTING PROCEDURES ONSITE. NEED LOCATION OF BUILDING MAINTAINED MONTHLY FIRE SERVICE, QUARTERLY EMERGENCY PHONE, AND ANNUAL EMERGENCY POWER TESTING LOGS POSTED IN THE CONTROL ROOM. (Receipt #1905877) | ROBERTV | ROBERTV | | H06 | C | 7545613 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/28/2022 | ANNUAL 5/21 -- OTIS W/ TKE SERVICE -- NO EMERGENCY LIGHT & ALARM BELL WHEN CAB 110V IS DISCONNECTED -- NOTICED OIL DRIPPING FROM BOTTOM OF DRIVE MACHINE -- NEED TO MONITOR BELTS THEY ARE STARTING TO ROUGE (Receipt #1853612) (Emergency Light and Bell have been addressed per TKE, check remaining items at H06 RV) | BENH | BENH | | H01 | C | 7315862 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/29/2021 | 5YR 9/17, CAT1 5/21 TKE AND LOCKBOX. HO2 | ERIC | ERIC | | H02 | C | 7123769 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/22/2021 | 5YR -- 9/17 -- CAT1 -- 4/20 -- OTIS W/ TKE LOCKBOX. EMERGENCY PHONE OPERATOR CANNOT HEAR PASSENGER. #3 BELT MONITOR IS FLASHING OUT OF NORMAL (Receipt #1758419) cat 1 5/21 | ROBERTV | ROBERTV | | H01 | C | 6905655 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/17/2020 | 5YR -- 9/17 -- CAT1 -- 4/20 -- OTIS W/ TKE LOCKBOX. MISSING LOWER SILL SAFETY RETAINER ON "B" AND "1" LEVEL HOISTWAY FAST DOORS. #3 BELT ON MONITOR IS FLASHING OUT OF NORMAL. NEED QUARTERLY EMERGENCY PHONE TEST LOG ONSITE | ROBERTV | ROBERTV | | H02 | C | 6710148 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/31/2020 | DUE TO THE COVID -19-INSPECTION CANCELED --WILL FOLLOW IN APRIL (Receipt #1670992) cat 1 4/20 | JOHNW | JOHNW | | H01 | C | 6526552 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/24/2019 | 5YR 9/17--ANNUAL 11/18--OTIS W/ TKE SERVICE--HO2 | CALE | CALE | | H02 | C | 6345198 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/29/2019 | 5 YEAR 9/17, ANNUAL 11/18 OTIS, TKE SERVICE, EMERGENCY PHONE NOT WORKING, TOP OF HOISTWAY LIGHT OUT (Receipt #1586286) | ERIC | ERIC | | H01 | C | 6149473 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/26/2018 | 5YR --9--17--OTIS --TKE SERVICE --CALL CONTACT KENT FOR ACCESS 365-6012 (cat 1 done 11/2018) | JOHNW | JOHNW | | H02 | C | 5977592 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/27/2018 | 5YR -- 9/17 -- OTIS W/ TKE SERVICE. (Receipt #1489773) | ROBERTV | ROBERTV | | H01 | C | 5799634 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/12/2017 | WITNESSED 9/17 | ERIC | ERIC | | H02 | C | 5623389 |
MEMORIAL HOSPITAL NORTH | H06 | C | 09/07/2017 | WITNESSED 5 YEAR SAFETY TEST. BELT MONITOR TEST FAILED. (Receipt #1452347) | ERIC | ERIC | | H06 | C | 5623226 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/28/2017 | 5YR -- 5/12 -- ANNUAL 7/16 -- OTIS W/ TKE LOCKBOX. ERASED CAR OPERATION SWITCH ESCUTCHEONS AND SIGNAGE HAVE YET TO BE REPLACED, NEED BELT MONITOR LED FAULT/OPERATION INFORMATION ATTACHED TO DEVICE, 5 YEAR WITNESS TEST DUE 5/2017 (Receipt #1412841) | ROBERTV | ROBERTV | | H01 | C | 5458120 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/26/2016 | 5YR--5--12--OTIS--7--16--ANNUAL --TKE LOCKBOX--ESCUTCHEONS ARE ON ORDER | JOHNW | JOHNW | | H02 | C | 5302868 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/30/2016 | 5YR -- 5/12 -- OTIS W/ TKE SERVICE. CAB DOOR RESTRICTOR BAR IS OUT OF ADJUSTMENT, MULTIPLE C.O.P. SWITCH ESCUTCHEONS AND SIGNAGE HAS LETTERING THAT IS WORN OFF. NEED ANNUAL CATEGORY 1 TESTING COMPLETED, NEED MAINTENANCE CONTROL PROGRAM ONSITE. (Receipt #1321013 from 03/30/2016) | ROBERTV | ROBERTV | | H01 | C | 5166214 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/16/2015 | 5 YEAR 5/12 OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 5036971 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/31/2015 | 5YR 5-12-OTIS LETTERING WORN OFF OF KEY SWITCHES AND PHASE II FIRE SERVICE INSTRUCTIONS IN CAR (Receipt #1253661) | TOM | TOM | | H01 | C | 4927125 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/29/2014 | 5YR--5--12---OTIS --LETTERING REMOVED FOR IN CAB SWITCHES--CAR TOP STOP BUTTON BROKEN | JOHNW | JOHNW | | H02 | C | 4824359 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/27/2014 | 5YR 5-12-OTIS (Receipt #1186695) | TOM | TOM | | H01 | C | 4712157 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/13/2013 | 5YR 5-12-OTIS | TOM | TOM | | H02 | C | 4612732 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/23/2013 | 5YR 5-12--OTIS (Receipt #1120240) | TOM | TOM | | H01 | C | 4496945 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/18/2012 | 5 YR 5-12--OTIS | TOM | TOM | | H02 | C | 4392023 |
MEMORIAL HOSPITAL NORTH | H06 | C | 06/01/2012 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1049030) | ERIC | ERIC | | H06 | C | 4320263 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/01/2012 | 5YR 2-07--OTIS (Receipt #1036418) | TOM | TOM | | H01 | C | 4290388 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/05/2011 | 5 YR 2-07--OTIS | TOM | TOM | | H02 | C | 4215407 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/28/2011 | 5 YR 2-07--OTIS--STOP SWITCH IN PIT HANGING FROM BRACKET (Receipt #966533) | TOM | TOM | | H01 | C | 4129268 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/23/2010 | 5 YR 2-07--OTIS | TOM | TOM | | H02 | C | 4049253 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/16/2010 | 5 yr 2-07--otis (Receipt #901695) | TOM | TOM | | H01 | C | 3958210 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/30/2009 | 5YR 2-07 OTIS MACHINE ROOM STORAGE REMOVED | TOM | TOM | | H02 | C | 3892348 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/31/2009 | 5YR 2-07--OTIS--CK FOR MACH RM STORAGE NEXT INSP (Receipt #852327) | TOM | TOM | | H01 | C | 3818734 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/29/2008 | 5yr--2--07--otis #5 and lockbox | TOM | TOM | | H02 | C | 3747933 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/12/2008 | 5YR--2-07--OTIS | JOHNW | JOHNW | | H01 | C | 3503481 |
MEMORIAL HOSPITAL NORTH | H02 | C | 09/28/2007 | 5YR--2--07--OTIS AND LOCKBOX | JOHNW | JOHNW | | H02 | C | 3503473 |
MEMORIAL HOSPITAL NORTH | H01 | C | 03/22/2007 | INITIAL INSPECTION--PERMIT ISSUED | TOM | TOM | | H01 | C | 3503466 |