GERALD H PHIPPS INC | B= | C | 08/03/2007 | | BERTW | BERTW | | B= | C | 3494839 |
GERALD H PHIPPS INC | BFR | C | 06/21/2007 | WOOD FRAMING IN MRI ROOM | TERRYB | TERRYB | | BFR | C | 3494832 |
GERALD H PHIPPS INC | BFR | P | 05/24/2007 | WALLS OK WHEN ELECTRIC AND PLUMBING ARE SIGNED OFF | TERRYB | TERRYB | | BFR | P | 3494825 |
GERALD H PHIPPS INC | BSP | P | 05/18/2007 | SLAB FOR ROOMS 105 AND 106 8" VOID WITH 5"X5"XOPENINGS TO EXISTING FLOOR 4' ON CENTER AND 2' FROM WALL | TERRYB | TERRYB | | BSP | P | 3494817 |
WISE ELECTRIC, INC. | E= | C | 07/27/2007 | | THOMAS | THOMAS | | E= | C | 3495046 |
WISE ELECTRIC, INC. | ER | C | 07/20/2007 | | THOMAS | THOMAS | | ER | C | 3495041 |
WISE ELECTRIC, INC. | E= | P | 07/20/2007 | RESUPPORT LIGHTS IN MRI ROOM AND ELECTRIC ROOM, CORRECT ISOLATED GROUNDING FOR MRI | MATTHEW | MATTHEW | | E= | P | 3495033 |
WISE ELECTRIC, INC. | ER | R | 07/16/2007 | COMPLETE MAKE UP & SUPPORT PIPE & BOX [ONE LOCATION] | THOMAS | THOMAS | | ER | R | 3495025 |
WISE ELECTRIC, INC. | E= | T | 07/16/2007 | PAID (REC#761438)NOT COMPLETE---ADD PIPE & BOX SUPPORTS IN GRID CIELINGS---COMPLETE MRI LIGHTING---TRANSFORMER NOT GROUNDED---TRANSFORMER PROBABLY WIL BE RELOCATED TO UNDER CIELING---LABEL ALL PANELS & DISCONNECTS [INCLUDING ELECTRIC ROOM DISCONNECTS]---REMOVE BOND SCREW IN MRI BREAKER ENCLOSURE---CHECK BREAKER ENCLOSURE IN ELECTRIC ROOM FOR NEUTRAL BONDING---CALIBRATE GFI [MTI BREAKER ELECTRIC ROOM | THOMAS | THOMAS | | E= | T | 3495017 |
WISE ELECTRIC, INC. | E= | P | 07/12/2007 | DRESSING ROOM, A105, A111, A110 OK | MATTHEW | MATTHEW | | E= | P | 3495009 |
WISE ELECTRIC, INC. | ER | P | 07/12/2007 | BATH HARDLID OK | MATTHEW | MATTHEW | | ER | P | 3495001 |
WISE ELECTRIC, INC. | ER | P | 06/21/2007 | CEILING MARKED ON PLANS E2--- DO NOT CLOSE CEILING UNTIL F/A HAS BEEN INSPECTED--- VERIFY TEMP LIGHTS REMOVED AT THIS TIME----- | MATTHEW | MATTHEW | | ER | P | 3494993 |
WISE ELECTRIC, INC. | ER | P | 06/20/2007 | WALLS GOOD MRI ROOM | THOMAS | THOMAS | | ER | P | 3494985 |
WISE ELECTRIC, INC. | ER | R | 06/15/2007 | CONTRACTOR USED PVC AS WIRING METHOD | MATTHEW | MATTHEW | | ER | R | 3494977 |
WISE ELECTRIC, INC. | ER | P | 05/24/2007 | WALLS COMPLETE EXCLUDING MRI ROOM | THOMAS | THOMAS | | ER | P | 3494968 |
WISE ELECTRIC, INC. | ER | P | 05/23/2007 | WALLS WEST SIDE TO MRI ROOM----ALL EMT | THOMAS | THOMAS | | ER | P | 3494955 |
WISE ELECTRIC, INC. | ES | P | 04/13/2007 | COMMERCIAL SERVICE: 150 AMP 3/W FOR MOBILE MRI TRAILOR BY WISE ELECTRIC: NEED SERVICE; METER LOCATED SW CORNER OF BOULDER AND BOB PETERS GV: COORDINATE WITH CONTRACTOR | MATTHEW | MATTHEW | | ES | P | 3494948 |
WISE ELECTRIC, INC. | EUG | P | 04/11/2007 | NEED CITY INSPECTION | MATTHEW | MATTHEW | | EUG | P | 3494936 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 08/01/2007 | RECEIVED BALANCE REPORT FROM MIDWEST/COLORADO SPRINGS, INC. | LYNNS | LYNNS | | H= | C | 3494885 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 07/16/2007 | NEED BALANCE REPORT FOR FINAL. | LYNNS | LYNNS | | H= | P | 3494877 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 06/15/2007 | ROUGH DUCT IN MRI ROOM OK TO COVER. | LYNNS | LYNNS | | HD | P | 3494870 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 06/06/2007 | ROUGH DUCT ABOVE CEILING IN BATHROOM OK TO COVER. | LYNNS | LYNNS | | HD | P | 3494863 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 05/21/2007 | 4 COILS, TRUNK LINES TO COILS AND LATERALS IN MRI SUITE OK TO WRAP. | NANCY | NANCY | | HD | P | 3494855 |
HEATING & PLUMBING ENGINEERS, INC | P= | C | 07/10/2007 | | JEFF | JEFF | | P= | C | 3494929 |
HEATING & PLUMBING ENGINEERS, INC | P= | P | 07/09/2007 | TIE DOWN CLIPS LEFT OFF SS SINK?, REST OK | JEFF | JEFF | | P= | P | 3494921 |
HEATING & PLUMBING ENGINEERS, INC | P= | T | 07/06/2007 | PAID (REC#759333)TRIP FEE, NOT READY | JEFF | JEFF | | P= | T | 3494914 |
HEATING & PLUMBING ENGINEERS, INC | PTO | C | 06/06/2007 | SEE SCANNED LETTER FOR DELETION OF FLOOR DRAIN | JEFF | JEFF | | PTO | C | 3494906 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 06/04/2007 | SECURE DRAIN BOX IN WALL, WASTE ARM TO DRAIN BOX BACK GRADED, SECURE CLOSET FLANGE AS NOTED BEFORE | JEFF | JEFF | | PTO | P | 3494900 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 05/24/2007 | ANCHOR CLOSET FLANGE, CAP VENT BRANCHS X 2, 1/2 BATH ONLY | JEFF | JEFF | | PTO | P | 3494893 |