MEMORIAL HOSPITAL | H01 | C | 11/08/2023 | ANNUAL 11/22 -- OTIS W/ TKE SERVICE -- EMERGENCY PHONE IS NONFUNCTIONAL -- COUNTERWEIGHT RUNBY IS 3", MINIMUM IS 6" -- PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL PHONE IS BACK IN SERVICE -- NOTE: ANNUAL TRACTION SAFETY TEST IS DUE BY THE END OF THE MONTH (Receipt #2006397) | BENH | BENH | | H01 | C | 7912903 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2023 | HO2 -- ANNUAL 11/22 -- OTIS W/ TKE SERVICE -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7754383 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - "ELEVATOR EMERGENCY POWER" INDICATOR AT THE DESIGNATED LEVEL IS NON-FUNCTIONAL. EMERGENCY OPERATIONS ON ELEVATOR STATUS PANEL IN FIRE COMMAND CENTER ARE NON-FUNCTIONAL........ THERE WILL NOT BE A COMPLIANCE DATE FOR THESE ITEMS PENDING FURTHER DIRECTION FROM THE STATE OF COLORADO DEPARTMENT OF PUBLIC SAFETY THAT IS PRESENTLY IN PROCESS OF DISCUSSION AND DECISION REGARDING REQUIREMENT FOR ELEVATOR OPERATIONS ON GENERATOR POWER. | ROBERTV | ROBERTV | | HE16 | C | 7657028 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2022 | WITNESSED AT HO1 (Receipt #1914024) | BENH | BENH | | H01 | C | 7580277 |
MEMORIAL HOSPITAL | H06 | C | 11/11/2022 | WITNESSED 5 YEAR TEST W/ TKE -- NO VISIBLE CODE ISSUES -- STILL NEED TO TEST GENERATOR POWER (Receipt #1914020) | BENH | BENH | | H06 | C | 7580264 |
MEMORIAL HOSPITAL | H02 | C | 05/24/2022 | H02 -- 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) | ROBERTV | ROBERTV | | H02 | C | 7387718 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2021 | 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. NO CODE ISSUES (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) (Receipt #1822135) | ROBERTV | ROBERTV | | H01 | C | 7173474 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. ELEVATOR EMERGENCY PHONE DOES NOT WORK WHEN CAB 110V CIRCUIT IS DISCONNECTED. | ROBERTV | ROBERTV | | H02 | C | 6980477 |
MEMORIAL HOSPITAL | H01 | C | 11/19/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/ TKE SERVICE. NEED QUARTERLY EMERGENCY PHONE TESTING LOGS ONSITE (Receipt #1730951) | ROBERTV | ROBERTV | | H01 | C | 6781644 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2020 | 5YR 11/17--ANNUAL 12/19--OTIS W/ TKE SERVICE--HO2 | CALE | CALE | | H02 | C | 6585360 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2019 | 5YR 11/17--ANNUAL 12/18--OTIS W/ TKE SERVICE--LIGHT NOT WORKING IN TOP OF HOISTWAY (Receipt #1644017) (Cat. 1 Performed 12/2019) | CALE | CALE | | H01 | C | 6397189 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2019 | H02 -- 5YR 11/17 -- ANNUAL 12/18 | ROBERTV | ROBERTV | | H02 | C | 6214106 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2018 | 5YR -- 11/17 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING DUE. (Receipt #1559838)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 6038410 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2018 | 5 YEAR 11/17 OTIS, TKE SERVICE,HO2 | ERIC | ERIC | | H02 | C | 5851103 |
MEMORIAL HOSPITAL | H06 | C | 11/13/2017 | WITNESSED 5 YEAR SAFETY TEST-NO ISSUES (Receipt #1465307) | ERIC | ERIC | | H06 | C | 5682674 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2017 | ANNUAL INSPECTION AND 5 YEAR SAFETY TEST COMPLETED AT SAME TIME, ONE HOUR OF CREDIT WILL BE GIVEN FOR 5 YEAR TESTING (Receipt #1465305) | ERIC | ERIC | | H01 | C | 5682669 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2017 | H02 - 5 YR CATEGORY 5 TESTING DUE 9/2017 | ROBERTV | ROBERTV | | H02 | C | 5503084 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2016 | 5YR--9--12--OTIS --TKE SERVICE (Receipt #1385757) | JOHNW | JOHNW | | H01 | C | 5355907 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2016 | 5 YEAR 9/12 OTIS. TKE SERVICE HO2 | ERIC | ERIC | | H02 | C | 5207938 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2015 | 5YR 9-12 OTIS (Receipt #1301570) | TOM | TOM | | H01 | C | 5088740 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2015 | HO2 | JOHNW | JOHNW | | H02 | C | 4958504 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2014 | 5YR 9-12 OTIS-TKE SERVICE--PHONE IN CAR NOT WORKING/CLEAN TRASH & DEBRIS FROM PIT/LIGHT BULB GUARDING IN CAR (Receipt #1234593) | TOM | TOM | | H01 | C | 4861792 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2014 | HO2--5YR--9--12--OTIS | JOHNW | JOHNW | | H02 | C | 4746664 |
MEMORIAL HOSPITAL | H01 | C | 11/18/2013 | 5YR 9-12-OTIS (Receipt #1168749) | TOM | TOM | | H01 | C | 4649571 |
MEMORIAL HOSPITAL | H02 | C | 05/31/2013 | 5YR 9-12--OTIS | TOM | TOM | | H02 | C | 4534877 |
MEMORIAL HOSPITAL | H01 | C | 11/12/2012 | 5YR 9-12-OTIS (Receipt #1097945) | TOM | TOM | | H01 | C | 4432149 |
MEMORIAL HOSPITAL | H06 | C | 09/04/2012 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1076104) | ERIC | ERIC | | H06 | C | 4375452 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2012 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 4317845 |
MEMORIAL HOSPITAL | H01 | C | 11/03/2011 | 5 YR 11-07--OTIS (Receipt #1015010) | TOM | TOM | | H01 | C | 4242761 |
MEMORIAL HOSPITAL | H02 | C | 05/10/2011 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 4154567 |
MEMORIAL HOSPITAL | H01 | C | 11/10/2010 | 5YR 11-07--OTIS (Receipt #948399) | TOM | TOM | | H01 | C | 4078462 |
MEMORIAL HOSPITAL | H02 | C | 05/20/2010 | 5 yr 11-07--otis | TOM | TOM | | H02 | C | 3988076 |
MEMORIAL HOSPITAL | H01 | C | 11/25/2009 | 5 YR 11-07--OTIS (Receipt #887186) | TOM | TOM | | H01 | C | 3916393 |
MEMORIAL HOSPITAL | H02 | C | 05/19/2009 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 3835984 |
MEMORIAL HOSPITAL | H01 | C | 11/22/2008 | 5yr 11-07 (Receipt #836769) | TOM | TOM | | H01 | C | 3773886 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2008 | 6 month | JOHNW | JOHNW | | H02 | C | 3685061 |
MEMORIAL HOSPITAL | H01 | C | 11/26/2007 | INITIAL INSPECTION | TOM | TOM | | H01 | C | 3646776 |