MEMORIAL HOSPITAL | H03 | C | 03/06/2024 | WAS ON-SITE FOR RE-INSPECTION TO CHECK LOGS AND ANNUAL TRACTION SAFETY TEST HAS BEEN COMPLETED -- ANNUAL 3/24 (Receipt #2040641) | BENH | BENH | | H03 | C | 8016262 |
MEMORIAL HOSPITAL | H01 | C | 11/08/2023 | ANNUAL 11/22 -- OTIS W/ TKE SERVICE -- EMERGENCY PHONE IS NONFUNCTIONAL -- HOISTWAY DOOR ON 5TH FLOOR EXCEEDS 1" PER PANEL OPENING -- NOTE: ANNUAL TRACTION SAFETY TEST IS DUE BY THE END OF THE MONTH -- MONITOR ROUGE ELASTOMERIC BELTS IN VARIOUS LOCATIONS IN THE HOISTWAY -- PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL ITEMS LISTED HAVE BEEN ADDRESSED (Receipt #2006395) | BENH | BENH | | H01 | C | 7912891 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2023 | HO2 -- ANNUAL 11/22 -- OTIS W/ TKE SERVICE -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7754387 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - "ELEVATOR EMERGENCY POWER" INDICATOR AT THE DESIGNATED LEVEL IS NON-FUNCTIONAL. EMERGENCY OPERATIONS ON ELEVATOR STATUS PANEL IN FIRE COMMAND CENTER ARE NON-FUNCTIONAL........ THERE WILL NOT BE A COMPLIANCE DATE FOR THESE ITEMS PENDING FURTHER DIRECTION FROM THE STATE OF COLORADO DEPARTMENT OF PUBLIC SAFETY THAT IS PRESENTLY IN PROCESS OF DISCUSSION AND DECISION REGARDING REQUIREMENT FOR ELEVATOR OPERATIONS ON GENERATOR POWER. | ROBERTV | ROBERTV | | HE16 | C | 7657026 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2022 | WITNESSED AT HO1 (Receipt #1914029) | BENH | BENH | | H01 | C | 7580293 |
MEMORIAL HOSPITAL | H06 | C | 11/11/2022 | WITNESSED 5 YEAR TEST WITH TKE -- 5TH FLOOR HOISTWAY DOORS OPEN MORE THAN .8" PER PANEL -- STILL NEED TO TEST GENERATOR POWER (Receipt #1914028) | BENH | BENH | | H06 | C | 7580290 |
MEMORIAL HOSPITAL | H02 | C | 05/24/2022 | H02 -- 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. CHECK PREVIOUS LISTED ITEMS AT WITNESS TEST (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) | ROBERTV | ROBERTV | | H02 | C | 7387720 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2021 | 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. TOP OF COUNTERWEIGHT ROLLER ASSEMBLY ATTACHING HARDWARE IS LOOSE. 5TH FLOOR LEFT HOISTWAY DOOR ECCENTRIC ROLLER BEARING IS BROKEN - (DOOR CAN BE OPENED AT SILL MORE THAN 1' WHEN CAR IS AWAY FROM FLOOR).......... (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) (Receipt #1822141) | ROBERTV | ROBERTV | | H01 | C | 7173496 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. ELEVATOR EMERGENCY PHONE DOES NOT WORK WHEN CAB 110V CIRCUIT IS DISCONNECTED. | ROBERTV | ROBERTV | | H02 | C | 6980482 |
MEMORIAL HOSPITAL | H01 | C | 11/19/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/ TKE SERVICE. NEED EMERGENCY PHONE TESTING LOGS ONSITE (Receipt #1730952) | ROBERTV | ROBERTV | | H01 | C | 6781672 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2020 | 5YR 11/17--ANNUAL 12/19--OTIS W/ TKE SERVICE--HO2 | CALE | CALE | | H02 | C | 6585364 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2019 | 5YR 11/17--ANNUAL 12/18--OTIS W/ TKE SERVICE (Receipt #1644018) (Cat. 1 Performed 12/2019) | CALE | CALE | | H01 | C | 6397191 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2019 | H02 -- 5YR 12/17 -- ANNUAL 12/18 | ROBERTV | ROBERTV | | H02 | C | 6214107 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2018 | 5YR -- 12/17 -- OTIS W/ TKE SERVICE. TOP OF COUNTERWEIGHT ROLLER GUIDE BRACKETS NEED SECURED TO COUNTERWEIGHT FRAME. REQUIRED ANNUAL CATEGORY 1 TESTING DUE. (Receipt #1565966)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 6038457 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2018 | 5 YEAR 12/17 OTIS, TKE SERVICE,HO2 | ERIC | ERIC | | H02 | C | 5851106 |
MEMORIAL HOSPITAL | H06 | C | 12/28/2017 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS NOT WORKING | ERIC | ERIC | | H06 | C | 5723759 |
MEMORIAL HOSPITAL | H06 | C | 11/13/2017 | 5 YEAR SAFETY TEST COULD NOT BE COMPLETED DUE TO GEN2 SOFTWARE ISSUE. NEED TO GET IT CORRECTED AND TEST COMPLETED BY 12/31/17 (Receipt #1465302) | ERIC | ERIC | | H06 | C | 5682656 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2017 | ANNUAL INSPECTION AND 5 YEAR SAFETY TEST COMPLETED AT SAME TIME, ONE HOUR OF CREDIT WILL BE GIVEN FOR 5 YEAR TESTING (Receipt #1465300) | ERIC | ERIC | | H01 | C | 5682648 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2017 | H02 - 5 YR CATEGORY 5 TESTING DUE 9/2017 | ROBERTV | ROBERTV | | H02 | C | 5503087 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2016 | 5YR--9--12--OTIS AND LOCKBOX (Receipt #1385760) | JOHNW | JOHNW | | H01 | C | 5355912 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2016 | 5 YEAR 9/12 OTIS. TKE SERVICE HO2 | ERIC | ERIC | | H02 | C | 5207939 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2015 | 5YR 9-12 OTIS--ALARM IN CAR NOT WORKING / BELT MONITOR HAS ONE CHECK LIGHT NOT WORKING (Receipt #1301571) | TOM | TOM | | H01 | C | 5088741 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2015 | HO2 | JOHNW | JOHNW | | H02 | C | 4958505 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2014 | 5YR 9-12 OTIS-TKE SERVICE--ALARM IN CAR NOT WORKING/LIGHT BULB GUADING IN CAR/CHECK BELT MONITOR, ONE MONITOR LIGHT IS OUT (Receipt #1234594 from 11/30/2014) | TOM | TOM | | H01 | C | 4861793 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2014 | HO2--5YR--9--12--OTIS | JOHNW | JOHNW | | H02 | C | 4746665 |
MEMORIAL HOSPITAL | H01 | C | 11/18/2013 | 5YR 9-12-OTIS ALARN IN CAR NOT WORKING (Receipt #1168750) | TOM | TOM | | H01 | C | 4649572 |
MEMORIAL HOSPITAL | H02 | C | 05/31/2013 | 5YR 9-12-OTIS | TOM | TOM | | H02 | C | 4534878 |
MEMORIAL HOSPITAL | H01 | C | 11/12/2012 | 5YR 9-12-OTIS--ALARM & EMERGENCY LIGHTING IN CAR NOT WORKING / CHECK BELT MONITOR (Receipt #1097946) | TOM | TOM | | H01 | C | 4432150 |
MEMORIAL HOSPITAL | H06 | C | 09/05/2012 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS AND ALARM BELL NOT WORKING AND 1 SUSPENSION BELT IS NOT CONNECTED TO BELT MONITOR (Receipt #1076586) | ERIC | ERIC | | H06 | C | 4376331 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2012 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 4317860 |
MEMORIAL HOSPITAL | H01 | C | 11/03/2011 | 5 YR 11-07--OTIS (Receipt #1015011) | TOM | TOM | | H01 | C | 4242764 |
MEMORIAL HOSPITAL | H02 | C | 05/10/2011 | 5 YR 11-07--OTIS LEVELING CORRECTED @ 1ST LANDING | TOM | TOM | | H02 | C | 4154569 |
MEMORIAL HOSPITAL | H01 | C | 11/10/2010 | 5YR 1107--OTIS CHECK LEVELING AT FIRST LANDING (Receipt #948400) | TOM | TOM | | H01 | C | 4078463 |
MEMORIAL HOSPITAL | H02 | C | 05/20/2010 | 5 yr 11-07--otis | TOM | TOM | | H02 | C | 3988077 |
MEMORIAL HOSPITAL | H01 | C | 11/25/2009 | 5 YR 11-07--OTIS CK PHONE NEXT INSP (Receipt #887187) | TOM | TOM | | H01 | C | 3916394 |
MEMORIAL HOSPITAL | H02 | C | 05/19/2009 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 3835985 |
MEMORIAL HOSPITAL | H01 | C | 11/22/2008 | 5yr 11-07 (Receipt #836770) | TOM | TOM | | H01 | C | 3773887 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2008 | 6 month | JOHNW | JOHNW | | H02 | C | 3685063 |
MEMORIAL HOSPITAL | H01 | C | 11/26/2007 | INITIAL INSPECTION | TOM | TOM | | H01 | C | 3646784 |