MEMORIAL HOSPITAL | H03 | C | 03/06/2024 | WAS ON-SITE FOR RE INSPECTION AND TRACTION SAFETY TEST HAS BEEN COMPLETED BUT THERE ARE NO ENTRIES IN M.C.P. FOR THE BELTS THAT HAVE BEEN REPLACED (Receipt #2040637) | BENH | BENH | | H03 | C | 8016257 |
MEMORIAL HOSPITAL | H03 | C | 11/13/2023 | WAS ON-SITE W/ TKE MECHANIC TO INVESTIGATE BELTS & PULSE BELT MONITOR -- WAS ABLE TO GET BELT MONITOR TO FAULTS OUT ON TEST MODE BUT NOT IN NORMAL OPERATION -- ELEVATOR WAS LOCKED BACK OUT AND WILL NOT BE ABLE TO BE BROUGHT BACK IN SERVICE UNTIL BELTS ARE REPLACED AND CONTRACTOR/OWNER HAVE CONTACTED P.P.R.B.D. FOR RE-INSPECTION (Receipt #2007826) (Belts have been replaced per TKE, need to setup reinspection with Memorial RV) | BENH | BENH | | H03 | C | 7917249 |
MEMORIAL HOSPITAL | H05 | C | 11/08/2023 | ELEVATOR WAS SHUTDOWN & LOCKED OUT DUE TO UNSAFE CONDITION OF THE ELASTOMERIC SUSPENSION BELTS | BENH | BENH | | H05 | C | 7912880 |
MEMORIAL HOSPITAL | H01 | C | 11/08/2023 | 5 YEAR 11/22 -- ANNUAL 11/22 -- OTIS W/ TKE SERVICE -- BELTS BETWEEN 4TH & 5TH FLOOR ARE MELTED TO THE STEEL WIRE AND DUE TO THAT UNSAFE CONDITION ELEVATOR WAS REMOVED FROM SERVICE -- PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL BELTS HAVE BEEN REPLACED -- EMERGENCY PHONE IS NONFUNCTIONAL -- EMERGENCY LIGHT IS NONFUNCTIONAL -- COUNTERWEIGHT RUNBY IS 3" & MINIMUM IS 6" -- NOTE: ANNUAL TRACTION SAFETY TEST IS DUE BY THE END OF THE MONTH (Receipt #2006387) | BENH | BENH | | H01 | C | 7912872 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2023 | HO2 -- ANNUAL 11/22 -- OTIS W/ TKE SERVICE -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7754389 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - "ELEVATOR EMERGENCY POWER" INDICATOR AT THE DESIGNATED LEVEL IS NON-FUNCTIONAL. EMERGENCY OPERATIONS ON ELEVATOR STATUS PANEL IN FIRE COMMAND CENTER ARE NON-FUNCTIONAL........ THERE WILL NOT BE A COMPLIANCE DATE FOR THESE ITEMS PENDING FURTHER DIRECTION FROM THE STATE OF COLORADO DEPARTMENT OF PUBLIC SAFETY THAT IS PRESENTLY IN PROCESS OF DISCUSSION AND DECISION REGARDING REQUIREMENT FOR ELEVATOR OPERATIONS ON GENERATOR POWER. | ROBERTV | ROBERTV | | HE16 | C | 7657023 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2022 | WITNESSED AT HO1 (Receipt #1914008) | BENH | BENH | | H01 | C | 7580220 |
MEMORIAL HOSPITAL | H06 | C | 11/11/2022 | WITNESSED ANNUAL 5 YEAR TEST W/ TKE -- EMERGENCY LIGHT IS NONFUNCTIONAL -- STILL NEED TO TEST GENERATOR POWER (Receipt #1914006) | BENH | BENH | | H06 | C | 7580218 |
MEMORIAL HOSPITAL | H02 | C | 05/24/2022 | H02 -- 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. CHECK PREVIOUS LISTED ITEMS AT WITNESS TEST (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) | ROBERTV | ROBERTV | | H02 | C | 7387768 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2021 | 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. COULD NOT HEAR EMERGENCY PHONE OPERATOR WHEN TESTING ELEVATOR PHONE.......... (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) (Receipt #1822145) | ROBERTV | ROBERTV | | H01 | C | 7173505 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. | ROBERTV | ROBERTV | | H02 | C | 6980488 |
MEMORIAL HOSPITAL | H01 | C | 11/19/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/ TKE SERVICE. COULD NOT ESTABLISH TWO-WAY COMMUNICATION ON EMERGENCY PHONE. EMERGENCY LIGHT AND ALARM BELL NOT WORKING. NEED EMERGENCY PHONE TESTING LOGS ONSITE (Receipt #1730956) | ROBERTV | ROBERTV | | H01 | C | 6781683 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2020 | 5YR 11/17--ANNUAL 12/19--OTIS W/ TKE SERVICE--HO2 | CALE | CALE | | H02 | C | 6585367 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2019 | 5YR 11/17--ANNUAL 12/18--OTIS W/ TKE SERVICE (Receipt #1644019) (Cat. 1 Performed 12/2019) | CALE | CALE | | H01 | C | 6397193 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2019 | H02 -- 5YR 11/17 -- ANNUAL 12/18 | ROBERTV | ROBERTV | | H02 | C | 6214109 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2018 | 5YR -- 11/17 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING DUE (Receipt #1565961)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 6038473 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2018 | 5 YEAR 11/17 OTIS, TKE SERVICE,HO2 | ERIC | ERIC | | H02 | C | 5851108 |
MEMORIAL HOSPITAL | H06 | C | 11/13/2017 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY PHONE, ALARM BELL AND EMERGENCY LIGHTS NOT WORKING (Receipt #1465297) | ERIC | ERIC | | H06 | C | 5682645 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2017 | ANNUAL INSPECTION AND 5 YEAR SAFETY TEST COMPLETED AT SAME TIME, ONE HOUR OF CREDIT WILL BE GIVEN FOR 5 YEAR TESTING (Receipt #1465296) | ERIC | ERIC | | H01 | C | 5682639 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2017 | H02 - 5 YR CATEGORY 5 TESTING DUE 9/2017 | ROBERTV | ROBERTV | | H02 | C | 5503088 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2016 | 5YR--9--12--OTIS --TKE LOCKBOX--ELEVATOR WAS DOWN AT TIME OF IN INSPECTIONS (Receipt #1385783) | JOHNW | JOHNW | | H01 | C | 5355930 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2016 | 5 YEAR 9/12 OTIS. TKE SERVICE HO2 | ERIC | ERIC | | H02 | C | 5207940 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2015 | 5YR 9-12--PHONE IN CAR NOT WORKING (Receipt #1301572) | TOM | TOM | | H01 | C | 5088742 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2015 | HO2 | JOHNW | JOHNW | | H02 | C | 4958507 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2014 | 5YR 9-12 OTIS-TKE SERVICE--PHONE IN CAR NOT WORKING/LIGHT BULB GUARDING IN CAR (Receipt #1197346 from 05/28/2014) | TOM | TOM | | H01 | C | 4861795 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2014 | HO2-- 5YR--9--12--OTIS | JOHNW | JOHNW | | H02 | C | 4746682 |
MEMORIAL HOSPITAL | H01 | C | 11/18/2013 | 5YR 9-12-OTIS (Receipt #1197346) | TOM | TOM | | H01 | C | 4649573 |
MEMORIAL HOSPITAL | H02 | C | 05/31/2013 | 5YR 9-12-OTIS | TOM | TOM | | H02 | C | 4534879 |
MEMORIAL HOSPITAL | H01 | C | 11/12/2012 | 5YR 9-12-OTIS (Receipt #1097947) | TOM | TOM | | H01 | C | 4432151 |
MEMORIAL HOSPITAL | H06 | C | 09/06/2012 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS NOT WORKING (Receipt #1076845) | ERIC | ERIC | | H06 | C | 4376985 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2012 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 4317861 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2011 | 5 YR 11-07--OTIS (Receipt #1015013) | TOM | TOM | | H01 | C | 4242766 |
MEMORIAL HOSPITAL | H02 | C | 05/10/2011 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 4154570 |
MEMORIAL HOSPITAL | H01 | C | 11/10/2010 | 5YR 11-07--OTIS (Receipt #948401) | TOM | TOM | | H01 | C | 4078464 |
MEMORIAL HOSPITAL | H02 | C | 05/20/2010 | 5 yr 11-07--otis | TOM | TOM | | H02 | C | 3988081 |
MEMORIAL HOSPITAL | H01 | C | 11/25/2009 | 5 YR 11-07--OTIS (Receipt #887188) | TOM | TOM | | H01 | C | 3916396 |
MEMORIAL HOSPITAL | H02 | C | 05/19/2009 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 3835986 |
MEMORIAL HOSPITAL | H01 | C | 11/22/2008 | 5yr 11-07 (Receipt #836765) | TOM | TOM | | H01 | C | 3773882 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2008 | 6 month | JOHNW | JOHNW | | H02 | C | 3685064 |
MEMORIAL HOSPITAL | H01 | C | 11/27/2007 | INITIAL INSPECTION | TOM | TOM | | H01 | C | 3617957 |