MEMORIAL HOSPITAL | HE16 | C | 04/11/2024 | SEE PERMIT P23919 FOR VALVE REPLACEMENT. | MATTM | MATTM | | HE16 | C | 8050327 |
MEMORIAL HOSPITAL | H03 | C | 11/08/2023 | WAS ON-SITE FOR RE-INSPECTION AND EMERGENCY PHONE IS NONFUNCTIONAL (Receipt #2006408) | BENH | BENH | | H03 | C | 7912940 |
MEMORIAL HOSPITAL | H01 | C | 09/18/2023 | ANNUAL 5/23 -- OTIS W/ TKE SERVICE -- COULD NOT ESTABLISH TWO WAY COMMUNICATION -- 30 DAYS TO ADDRESS (Receipt #1989295) | BENH | BENH | | H01 | C | 7859823 |
MEMORIAL HOSPITAL | H02 | C | 05/31/2023 | WITNESSED AT HO2 | BENH | BENH | | H02 | C | 7757975 |
MEMORIAL HOSPITAL | H06 | C | 05/31/2023 | WITNESSED 5 YEAR TEST W/ TKE -- EMERGENCY PHONE IS NONFUNCTIONAL IN NORMAL OPERATION OR WHEN CAB 110V IS DISCONNECTED -- SUMP PUMP IS NONFUNCTIONAL AND THERE IS WATER ON THE PIT FLOOR -- "RUN - STOP" KEY SWITCH & "PHASE 2 FIRE SERVICE KEY SWITCH LETTERING HAS BEEN RUBBED OFF | BENH | BENH | | H06 | C | 7757968 |
MEMORIAL HOSPITAL | HE= | T | 05/26/2023 | PAID (REC#1957338) AFTER-HOURS INSPECTION: $200 From: JANE Per Robert | JANE | JANE | | HE= | T | 7755781 |
MEMORIAL HOSPITAL | H01 | C | 11/28/2022 | ANNUAL 5/22 -- OTIS W/ TKE SERVICE (Receipt #1916910) moved H06 to align with H02, DS | BENH | BENH | | H01 | C | 7592808 |
MEMORIAL HOSPITAL | H02 | C | 05/24/2022 | H02 -- 5YR -- 11/17 -- CAT1 -- 5/22 -- OTIS W/ TKE SERVICE. CHECK PREVIOUS LISTED ITEMS AT WITNESS TEST (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) | ROBERTV | ROBERTV | | H02 | C | 7387771 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2021 | CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. LETTERING FOR ELEVATOR # AND CAPACITY HAS WORN OFF ON THE IN CAR PLATE........... (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) (Receipt #1822146) cat 1 5/22 | ROBERTV | ROBERTV | | H01 | C | 7173513 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2021 | CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. ELEVATOR EMERGENCY PHONE DOES NOT WORK WHEN THE CAB 110V IS DISCONNECTED. EMERGENCY PHONE OPERATION JEWEL IS MISSING OR NOT WORKING. | ROBERTV | ROBERTV | | H02 | C | 6980493 |
MEMORIAL HOSPITAL | H01 | C | 11/19/2020 | CAT1 -- 4/20 -- OTIS W/ TKE SERVICE. EMERGENCY PHONE NOT WORKING WHEN CAB 110V IS DISCONNECTED. NEED QUARTERLY EMERGENCY PHONE TESTING LOGS ONSITE (Receipt #1730958) cat 1 4/21 | ROBERTV | ROBERTV | | H01 | C | 6781695 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2020 | 5YR 3/18--ANNUAL 3/19--OTIS W/ TKE SERVICE--HO2 cat 1 4/20 | CALE | CALE | | H02 | C | 6585371 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2019 | 5YR 3/18--ANNUAL 3/19--OTIS W/ TKE SERVICE (Receipt #1644020) | CALE | CALE | | H01 | C | 6397198 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2019 | H02 -- RP 3/19 | ROBERTV | ROBERTV | | H02 | C | 6214110 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2018 | RP -- 3/18 -- OTIS W/ TKE SERVICE. WATER IN PIT IS STILL A PROBLEM, PLEASE CONTACT INSPECTOR AS THIS WAS DISCUSSED TO BE REMEDIED PREVIOUSLY. ESCAPE HATCH ELECTRICAL SAFETY NOT WORKING. CAR SHUDDERS BADLY WHEN ASCENDING NEAR THE TOP LEVEL. (Receipt #1562380)--(RP 3/19, Elevator Pit has been sealed) | ROBERTV | ROBERTV | | H01 | C | 6038503 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2018 | RP 3/18 OTIS, TKE SERVICE,HO2. WATER IN PIT ISSUE HAS BEEN ADDRESSED | ERIC | ERIC | | H02 | C | 5851111 |
MEMORIAL HOSPITAL | H06 | C | 03/16/2018 | WITNESSED 5 YEAR SAFETY TEST. WATER STANDING IN PIT MUST BE ADDRESSED, CRITICAL ELEVATOR COMPONENTS ARE RAPIDLY DETERIORATING | ERIC | ERIC | | H06 | C | 5791145 |
MEMORIAL HOSPITAL | H01 | C | 11/21/2017 | RP 1/17 OTIS, TKE SERVICE. NEED 5 YEAR WITNESSED TEST BY JANUARY 2018, WATER IN PIT ELEVATOR COMPONENTS GETTING RUSTY (Receipt #1467175) | ERIC | ERIC | | H01 | C | 5692016 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2017 | H02 - 5 YR CATEGORY 5 TESTING DUE 9/2017 | ROBERTV | ROBERTV | | H02 | C | 5503089 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2016 | RP--2--16--OTIS AND TKE SERVICE------------------------------LOCKBOX ON THIS ELEVATOR MACHINE ROOM 1ST FLOOR FLOOR (Receipt #1385764) | JOHNW | JOHNW | | H01 | C | 5355918 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2016 | 5 YEAR 9/12 OTIS. TKE SERVICE HO2 | ERIC | ERIC | | H02 | C | 5207941 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2015 | RP 2-15 OTIS--PHONE IN CAR NOT WORKING (Receipt #1301573) | TOM | TOM | | H01 | C | 5088743 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2015 | HO2 | JOHNW | JOHNW | | H02 | C | 4958508 |
MEMORIAL HOSPITAL | H06 | C | 02/26/2015 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY PHONE, ALARM BELL AND EMERGENCY LIGHTS NOT WORKING, NEED PHASE 1 INSTRUCTION PLACARD, COP KEY SWITCH BEZEL LETTERING IS WORN OFF, | ERIC | ERIC | | H06 | C | 4909368 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2014 | RP 4-14 OTIS-TKE SERVICE--REMOVE ALL WATER IN PIT, CLEAN OR REPLACE RUSTED EQUIPMENT IN PIT/IDENTIFY AND REPLACE ALL LETTERING THAT IS WORN OFF OF KEY SWITCHES IN CAR (Receipt #1234596) | TOM | TOM | | H01 | C | 4861796 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2014 | HO2-- | JOHNW | JOHNW | | H02 | C | 4746688 |
MEMORIAL HOSPITAL | H01 | C | 11/18/2013 | RP 12-12-WATER IN PIT / SUMP GRATE MISSING / PHONE IN CAR NOT WORKING / IDENTIFY & REPLACE LETTERING THAT IS WORN OFF OF KEY SWITCHES IN CAR (Receipt #1168751) | TOM | TOM | | H01 | C | 4649574 |
MEMORIAL HOSPITAL | H02 | C | 05/31/2013 | RP 12-12-OTIS | TOM | TOM | | H02 | C | 4534880 |
MEMORIAL HOSPITAL | H01 | C | 11/12/2012 | RP EXP--LAST TEST 4-11--APPROX 3' OF WATER IN PIT, FACILITIES IS MITIGATING PROBLEM (Receipt #1097948) | TOM | TOM | | H01 | C | 4432152 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2012 | 5 YR 11-07--OTIS not a traction tom, it's a hydro | TOM | TOM | | H02 | C | 4317863 |
MEMORIAL HOSPITAL | H01 | C | 11/03/2011 | 5 YR 11-07--OTIS--ALARM BELL WORKED INTERMITTENTLY CHECK NEXT INSPECTION (Receipt #1015014) | TOM | TOM | | H01 | C | 4242767 |
MEMORIAL HOSPITAL | H02 | C | 05/10/2011 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 4154571 |
MEMORIAL HOSPITAL | H01 | C | 11/10/2010 | 5YR 11-07-OTIS (Receipt #948402) | TOM | TOM | | H01 | C | 4078465 |
MEMORIAL HOSPITAL | H02 | C | 05/20/2010 | 5 yr 11-07--otis | TOM | TOM | | H02 | C | 3988085 |
MEMORIAL HOSPITAL | H01 | C | 11/25/2009 | 5 YR 11-07--OTIS (Receipt #887190) | TOM | TOM | | H01 | C | 3916397 |
MEMORIAL HOSPITAL | H02 | C | 05/19/2009 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 3835987 |
MEMORIAL HOSPITAL | H01 | C | 11/22/2008 | 5yr 11-07 check phone next insp (Receipt #836766) | TOM | TOM | | H01 | C | 3773883 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2008 | 6 month | JOHNW | JOHNW | | H02 | C | 3685066 |
MEMORIAL HOSPITAL | H01 | C | 11/27/2007 | INITIAL INSPECTION | TOM | TOM | | H01 | C | 3617973 |