MEMORIAL HOSPITAL | H03 | C | 03/06/2024 | WAS ON-SITE FOR RE-INSPECTION TO TEST EMERGENCY PHONE IN THE ELEVATOR AND TO CHECK ANNUAL TRACTION SAFETY REPORT -- ANNUAL 1/24 -- PHONE IS NOW FUNCTIONAL (Receipt #2040646) | BENH | BENH | | H03 | C | 8016267 |
MEMORIAL HOSPITAL | H01 | C | 11/08/2023 | ANNUAL 1/23 -- OTIS W/ TKE SERVICE -- EMERGENCY PHONE IS NONFUNCTIONAL -- PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL EMERGENCY PHONE IS BACK IN SERVICE (Receipt #2006361) | BENH | BENH | | H01 | C | 7912803 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2023 | HO2 -- ANNUAL 1/23 -- OTIS W/ TKE SERVICE -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7754391 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - "ELEVATOR EMERGENCY POWER" INDICATOR AT THE DESIGNATED LEVEL IS NON-FUNCTIONAL. EMERGENCY OPERATIONS ON ELEVATOR STATUS PANEL IN FIRE COMMAND CENTER ARE NON-FUNCTIONAL........ THERE WILL NOT BE A COMPLIANCE DATE FOR THESE ITEMS PENDING FURTHER DIRECTION FROM THE STATE OF COLORADO DEPARTMENT OF PUBLIC SAFETY THAT IS PRESENTLY IN PROCESS OF DISCUSSION AND DECISION REGARDING REQUIREMENT FOR ELEVATOR OPERATIONS ON GENERATOR POWER. | ROBERTV | ROBERTV | | HE16 | C | 7657014 |
MEMORIAL HOSPITAL | H06 | C | 01/24/2023 | WITNESSED ANNUAL 5 YEAR TEST W/ TKE -- JEWEL FOR PHASE 1 AT KEY SWITCH DOESN'T ILLUMINATE (Receipt #1928578) | BENH | BENH | | H06 | C | 7643169 |
MEMORIAL HOSPITAL | H01 | C | 11/28/2022 | WITNESSED AT HO1 (Receipt #1916906) | BENH | BENH | | H01 | C | 7592797 |
MEMORIAL HOSPITAL | H02 | C | 05/24/2022 | H02 -- 5YR -- 11/17 -- CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. CHECK PREVIOUS LISTED ITEMS AT WITNESS TEST (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) | ROBERTV | ROBERTV | | H02 | C | 7387777 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2021 | 5YR -- 11/17 -- CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. NO CODE ISSUES (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) (Receipt #1822149) | ROBERTV | ROBERTV | | H01 | C | 7173516 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. | ROBERTV | ROBERTV | | H02 | C | 6980527 |
MEMORIAL HOSPITAL | H01 | C | 11/19/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/ TKE SERVICE. NEED EMERGENCY PHONE TESTING LOGS ONSITE (Receipt #1730960) | ROBERTV | ROBERTV | | H01 | C | 6781696 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2020 | 5YR 11/17--ANNUAL 01/20--OTIS W/ TKE SERVICE--HO2 | CALE | CALE | | H02 | C | 6585376 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2019 | 5YR 11/17--ANNUAL 12/18--OTIS W/ TKE SERVICE (Receipt #1644022) (Cat. 1 Performed 01/2020) | CALE | CALE | | H01 | C | 6397199 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2019 | H02 -- 5YR 11/17 -- ANNUAL 12/18 | ROBERTV | ROBERTV | | H02 | C | 6214115 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2018 | 5YR -- 11/17 -- OTIS W/ TKE SERVICE. ESCAPE HATCH BRACKET AT ELECTRICAL SAFETY IS LOOSE. REQUIRED ANNUAL CATEGORY 1 TESTING DUE. NEED TO LOG REPAIRS MADE TO GOVERNOR IN MAINTENANCE CONTROL PROGRAM. (Receipt #1565962)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 6038525 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2018 | 5 YEAR 11/17 OTIS, TKE SERVICE,HO2 | ERIC | ERIC | | H02 | C | 5851115 |
MEMORIAL HOSPITAL | HE16 | C | 12/06/2017 | GOVERNOR REPLACED AND TESTING COMPLETED, EMERGENCY LIGHTS NOT WORKING | ERIC | ERIC | | HE16 | C | 5704456 |
MEMORIAL HOSPITAL | H06 | C | 11/13/2017 | WITNESSED 5 YEAR SAFETY TEST. FAILED GOVERNOR PULL THROUGH TEST, GOVERNOR MUST BE REPLACED AND 5 YEAR TESTING WILL HAVE TO BE COMPLETED. GOVERNOR MUST BE REPLACED WITHIN 30 DAYS. ALSO EMERGENCY LIGHTS DO NOT WORK (Receipt #1465290) | ERIC | ERIC | | H06 | C | 5682591 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2017 | ANNUAL INSPECTION AND 5 YEAR SAFETY TEST COMPLETED AT SAME TIME, ONE HOUR OF CREDIT WILL BE GIVEN FOR 5 YEAR TESTING (Receipt #1465282) | ERIC | ERIC | | H01 | C | 5682565 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2017 | H02 - 5 YR CATEGORY 5 TESTING DUE 9/2017 | ROBERTV | ROBERTV | | H02 | C | 5503090 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2016 | 5YR--9--12--OTIS --TKE SERVICE (Receipt #1385784) | JOHNW | JOHNW | | H01 | C | 5355932 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2016 | 5 YEAR 9/12 OTIS. TKE SERVICE HO2 | ERIC | ERIC | | H02 | C | 5207942 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2015 | 5YR 9-12 OTIS (Receipt #1301574) | TOM | TOM | | H01 | C | 5088744 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2015 | HO2 | JOHNW | JOHNW | | H02 | C | 4958509 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2014 | 5YR 9-12 OTIS-TKE SERVICE--LIGHTBULB GUARDING IN CAR (Receipt #1234597) | TOM | TOM | | H01 | C | 4861797 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2014 | HO2--9--12--OTIS | JOHNW | JOHNW | | H02 | C | 4746690 |
MEMORIAL HOSPITAL | H01 | C | 11/19/2013 | 5YR 9-12-OTIS OTIS CIRCIUT BOARD IS LAYING ON PIT FLOOR (Receipt #1168752) | TOM | TOM | | H01 | C | 4649575 |
MEMORIAL HOSPITAL | H02 | C | 05/31/2013 | 5YR 9-12-OTIS | TOM | TOM | | H02 | C | 4534881 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2012 | 5YR 9-12-OTIS (Receipt #1097949) | TOM | TOM | | H01 | C | 4432153 |
MEMORIAL HOSPITAL | H06 | C | 09/07/2012 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1077211) | ERIC | ERIC | | H06 | C | 4377858 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2012 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 4317866 |
MEMORIAL HOSPITAL | H01 | C | 11/03/2011 | 5 YR 11-07--OTIS (Receipt #1015015) | TOM | TOM | | H01 | C | 4242768 |
MEMORIAL HOSPITAL | H02 | C | 05/10/2011 | 5 YR II-07--OTIS | TOM | TOM | | H02 | C | 4154572 |
MEMORIAL HOSPITAL | H01 | C | 11/10/2010 | 5YR 11-07-OTIS (Receipt #948403) | TOM | TOM | | H01 | C | 4078466 |
MEMORIAL HOSPITAL | H02 | C | 05/20/2010 | 5 yr 11-07--otis | TOM | TOM | | H02 | C | 3988087 |
MEMORIAL HOSPITAL | H01 | C | 11/25/2009 | 5 YR 11-07--OTIS (Receipt #887191) | TOM | TOM | | H01 | C | 3916398 |
MEMORIAL HOSPITAL | H02 | C | 05/19/2009 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 3835988 |
MEMORIAL HOSPITAL | H01 | C | 11/22/2008 | 5yr 11-07 (Receipt #836767) | TOM | TOM | | H01 | C | 3773884 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2008 | 6 month | JOHNW | JOHNW | | H02 | C | 3685069 |
MEMORIAL HOSPITAL | H01 | C | 11/27/2007 | INITIAL INSPECTION | TOM | TOM | | H01 | C | 3617981 |