MEMORIAL HOSPITAL | H02 | C | 05/23/2024 | 5YR - 11/2022 -- CAT1 - 1/2024 -- OTIS W/ TKE SERVICE. CATEGORY 1 TEST REPORT INDICATES I.T.S SUSPENSION BELT MONITOR FAILED WHEN TESTING PER UNIQUE PROCEDURE. NEED TO PROVIDE UP TO DATE I.T.S. BELT MONITOR UNIQUE TESTING PROCEDURE NOW AVAILABLE FROM TKE AND TEST WITHIN NEXT 60 DAYS AND PROVIDE DOCUMENTED PASSING RESULT TO AVOID RED TAG SHUTDOWN. ALSO, PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. (Receipt #2067377) | ROBERTV | ROBERTV | | H02 | C | 8093395 |
MEMORIAL HOSPITAL | H03 | C | 03/06/2024 | WAS ON-SITE FOR RE-INSPECTION OF NONFUNCTIONAL EMERGENCY PHONE IN THE ELEVATOR AND TO CHECK ANNUAL TRACTION SAFETY TEST REPORT -- ANNUAL 1/24 AND PHONE IS FUNCTIONAL (Receipt #2040648) | BENH | BENH | | H03 | C | 8016277 |
MEMORIAL HOSPITAL | H01 | C | 11/08/2023 | ANNUAL 1/23 -- OTIS W/ TKE SERVICE -- EMERGENCY PHONE IS NONFUNCTIONAL -- PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL EMERGENCY PHONE IS BACK IN SERVICE (Receipt #2006358) | BENH | BENH | | H01 | C | 7912785 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2023 | HO2 -- ANNUAL 1/ 23 -- OTIS W/ TKE SERVICE -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7754395 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - "ELEVATOR EMERGENCY POWER" INDICATOR AT THE DESIGNATED LEVEL IS NON-FUNCTIONAL. EMERGENCY OPERATIONS ON ELEVATOR STATUS PANEL IN FIRE COMMAND CENTER ARE NON-FUNCTIONAL........ THERE WILL NOT BE A COMPLIANCE DATE FOR THESE ITEMS PENDING FURTHER DIRECTION FROM THE STATE OF COLORADO DEPARTMENT OF PUBLIC SAFETY THAT IS PRESENTLY IN PROCESS OF DISCUSSION AND DECISION REGARDING REQUIREMENT FOR ELEVATOR OPERATIONS ON GENERATOR POWER. | ROBERTV | ROBERTV | | HE16 | C | 7657012 |
MEMORIAL HOSPITAL | H06 | C | 01/24/2023 | WITNESSED ANNUAL 5 YEAR TESTING W/ TKE -- GOVERNOR ROPE NEEDS TO BE SHORTENED DUE TO GOVERNOR TAIL SHEAVE CONTACT ENGAGING AND FAULTING OUT CAR -- MISSING SAFETY RETAINER ON 5TH FLOOR HOISTWAY DOOR -- NOTE: PER INSPECTION REPORT ELEVATOR WAS GOING TO SHUTDOWN DUE TO BELT MONITOR NOT WORKING PROPERLY, PER DISCUSSION WITH MECHANIC, BELT MONITOR IS FUNCTIONING PROPERLY AND TESTING PROCEDURE IS IN MCP--- * STILL NEED TO COMPLETE GENERATOR TESTING (Receipt #1928587) | BENH | BENH | | H06 | C | 7643232 |
MEMORIAL HOSPITAL | H01 | C | 11/28/2022 | WITNESSED AT HO1 (Receipt #1916909) | BENH | BENH | | H01 | C | 7592804 |
MEMORIAL HOSPITAL | H02 | C | 05/24/2022 | H02 -- 5YR -- 11/17 -- CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. CHECK PREVIOUS LISTED ITEMS AT WITNESS TEST (NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) | ROBERTV | ROBERTV | | H02 | C | 7387778 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2021 | 5YR -- 11/17 -- CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. ESCAPE HATCH BRACKET IS MISSING HARDWARE.......(NOTE: ELEVATOR CAB 110V CIRCUITS ARE CONNECTED TO GENERATOR POWER) (Receipt #1822150) | ROBERTV | ROBERTV | | H01 | C | 7173518 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. | ROBERTV | ROBERTV | | H02 | C | 6980538 |
MEMORIAL HOSPITAL | H01 | C | 11/19/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/ TKE SERVICE. #3 ON BELT MONITOR IS FLASHING ABNORMALLY. 5TH FLOOR HOISTWAY DOOR NEEDS SAFETY RETAINERS AT BOTTOM. NEED EMERGENCY PHONE TESTING LOGS ONSITE (Receipt #1730962) | ROBERTV | ROBERTV | | H01 | C | 6781711 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2020 | 5YR 11/17--ANNUAL 01/20--OTIS W/ TKE SERVICE--HO2 | CALE | CALE | | H02 | C | 6585379 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2019 | 5YR 11/17--ANNUAL 12/18--OTIS W/ TKE SERVICE (Receipt #1644024) (Cat. 1 Performed 01/2020) | CALE | CALE | | H01 | C | 6397201 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2019 | H02 -- 5YR 11/17 -- ANNUAL 12/18 | ROBERTV | ROBERTV | | H02 | C | 6214117 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2018 | 5YR -- 11/17 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING DUE (Receipt #1565965)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 6038531 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2018 | 5 YEAR 11/17 OTIS, TKE SERVICE,HO2 | ERIC | ERIC | | H02 | C | 5851117 |
MEMORIAL HOSPITAL | HE16 | C | 12/28/2017 | BELT MONITOR REPAIRED | ERIC | ERIC | | HE16 | C | 5723782 |
MEMORIAL HOSPITAL | H06 | C | 11/13/2017 | WITNESSED 5 YEAR SAFETY TEST. SUSPENSION BELT MONITOR TEST FAILED, BELT MONITOR MUST BE REPAIRED OR REPLACED WITHIN 30 DAYS (Receipt #1465281) | ERIC | ERIC | | H06 | C | 5682548 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2017 | ANNUAL INSPECTION AND 5 YEAR SAFETY TEST COMPLETED AT SAME TIME, ONE HOUR OF CREDIT WILL BE GIVEN FOR 5 YEAR TESTING (Receipt #1465279) | ERIC | ERIC | | H01 | C | 5682539 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2017 | H02 - 5 YR CATEGORY 5 TESTING DUE 9/2017 | ROBERTV | ROBERTV | | H02 | C | 5503093 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2016 | 5YR--9--12--OTIS --TKE LOCKBOX (Receipt #1385786) | JOHNW | JOHNW | | H01 | C | 5355933 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2016 | 5 YEAR 9/12 OTIS. TKE SERVICE HO2 | ERIC | ERIC | | H02 | C | 5207949 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2015 | 5YR 9-12 OTIS CHECK BELT MONITOR (Receipt #1301575) | TOM | TOM | | H01 | C | 5088745 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2015 | HO2 | JOHNW | JOHNW | | H02 | C | 4958514 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2014 | 5YR 9-12 OTIS-TKE SERVICE--LIGHT BULB GUARDING IN CAR (Receipt #1234598) | TOM | TOM | | H01 | C | 4861798 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2014 | HO2--5YR--9--12--OTIS | JOHNW | JOHNW | | H02 | C | 4746696 |
MEMORIAL HOSPITAL | H01 | C | 11/19/2013 | 5YR 9-12-OTIS--"DOOR CLOSE" SYMBOL IS MISSING FROM CONTROL OPERATING PANEL IN CAR (Receipt #1168753) | TOM | TOM | | H01 | C | 4649576 |
MEMORIAL HOSPITAL | H02 | C | 05/31/2013 | 5YR 9-12-OTIS | TOM | TOM | | H02 | C | 4534882 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2012 | 5YR 9-12-OTIS--BELT MONITOR STILL SHOWING BELT 4 NEEDS REPLACING (Receipt #1097951) | TOM | TOM | | H01 | C | 4432154 |
MEMORIAL HOSPITAL | H06 | C | 09/07/2012 | WITNESSED 5 YEAR SAFETY TEST. BELT MONITOR INDICATES THAT SUSPENSION BELT #4 MUST BE REPLACED (Receipt #1077213) | ERIC | ERIC | | H06 | C | 4377862 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2012 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 4317867 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2011 | 5 YR 11-07--OTIS (Receipt #1015016) | TOM | TOM | | H01 | C | 4242769 |
MEMORIAL HOSPITAL | H02 | C | 05/10/2011 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 4154574 |
MEMORIAL HOSPITAL | H01 | C | 11/10/2010 | 5YR 11-07-OTIS (Receipt #948404) | TOM | TOM | | H01 | C | 4078467 |
MEMORIAL HOSPITAL | H02 | C | 05/20/2010 | 5 yr 11-07--otis | TOM | TOM | | H02 | C | 3988090 |
MEMORIAL HOSPITAL | H01 | C | 11/25/2009 | 5 YR 11-07--OTIS (Receipt #887192) | TOM | TOM | | H01 | C | 3916399 |
MEMORIAL HOSPITAL | H02 | C | 05/19/2009 | 5 YR 11-07--OTIS | TOM | TOM | | H02 | C | 3835989 |
MEMORIAL HOSPITAL | H01 | C | 11/22/2008 | 5yr 11-07 (Receipt #836768) | TOM | TOM | | H01 | C | 3773885 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2008 | 6 month | JOHNW | JOHNW | | H02 | C | 3685072 |
MEMORIAL HOSPITAL | H01 | C | 11/27/2007 | INITIAL INSPECTION | TOM | TOM | | H01 | C | 3617988 |