PCL CONSTRUCTION SERVICES, INC | B= | P | 05/01/2008 | Temp CO: PENDING MECH. FIRE HAS SIGNED OFF WITH A TCO. | JAN | JAN | | B= | P | 3644717 |
PCL CONSTRUCTION SERVICES, INC | B= | C | 04/29/2008 | Complete per notes below | JAN | JAN | | B= | C | 3667996 |
PCL CONSTRUCTION SERVICES, INC | BSP | T | 04/22/2008 | PAID (REC#802435)ADDITIONAL PLAN REVIEW TIME: $50.000 From: DALEH splice for change to exhaust fan cfm | DALEH | DALEH | | BSP | T | 3644709 |
PCL CONSTRUCTION SERVICES, INC | B= | P | 04/01/2008 | pending mech. fire has signed off with a tco. | ED | ED | | B= | P | 3644785 |
PCL CONSTRUCTION SERVICES, INC | BSP | P | 03/20/2008 | demising wall smoke sealing ok | BERTW | BERTW | | BSP | P | 3644779 |
PCL CONSTRUCTION SERVICES, INC | BSP | R | 03/19/2008 | LEFT MESSAGE @1;47PM WAITED TILL 2:20PM FOR ESCORT/PLEASE RECALL INSPECTION | BERTW | BERTW | | BSP | R | 3644771 |
PCL CONSTRUCTION SERVICES, INC | BSP | T | 03/13/2008 | PAID (REC#796448)ADDITIONAL PLAN REVIEW TIME: $50.000 From: GARYL ADDED RECEPTACLE ON BACK UP SYSTEM | GARYL | GARYL | | BSP | T | 3644763 |
PCL CONSTRUCTION SERVICES, INC | BSP | P | 03/07/2008 | ABOVE GRID FIRECAULKING BATHROOMS OK | BERTW | BERTW | | BSP | P | 3644755 |
PCL CONSTRUCTION SERVICES, INC | BSP | P | 02/08/2008 | FIRE CAULKING @ FLOOR THRU PENETRATIONS OK | BERTW | BERTW | | BSP | P | 3644747 |
PCL CONSTRUCTION SERVICES, INC | BFR | P | 02/06/2008 | SEE SHEET A-3 FOR WALLS INSPECTED/NEED FLOOR PENETRATIONS FIRECAULKED | BERTW | BERTW | | BFR | P | 3644739 |
PCL CONSTRUCTION SERVICES, INC | BFR | P | 01/25/2008 | WALLS OK SHEET A-3 CORRIDOR ONLY | BERTW | BERTW | | BFR | P | 3644732 |
PCL CONSTRUCTION SERVICES, INC | BSP | T | 01/22/2008 | PAID (REC#789264)ADDITIONAL PLAN REVIEW TIME: $50.000 From: JOHNJ changed ent door to glass in un rated wall, smoke wall only | JOHNJ | JOHNJ | | BSP | T | 3644725 |
IES COMMERCIAL, INC. | E= | C | 03/28/2008 | | TIMA | TIMA | | E= | C | 3645001 |
IES COMMERCIAL, INC. | E= | R | 03/27/2008 | CANCELLED BY CONTRACTOR | TIMA | TIMA | | E= | R | 3644993 |
IES COMMERCIAL, INC. | E= | P | 03/26/2008 | EAST TO WEST PERIMITER OFFICES & PROCEDURE ROOMS & STORAGE ROOM OK | TIMA | TIMA | | E= | P | 3644985 |
IES COMMERCIAL, INC. | ER | C | 03/25/2008 | CEILINGS COMPLETE | TIMA | TIMA | | ER | C | 3644977 |
IES COMMERCIAL, INC. | ER | P | 03/19/2008 | CEILINGS MARKED ON SHEET E-3 OK | TIMA | TIMA | | ER | P | 3644969 |
IES COMMERCIAL, INC. | ER | P | 03/18/2008 | CEILINGS MARKED ON SHEET E-3 OK NEED 2 BARREL LUGS ON LIGHTING PANEL | TIMA | TIMA | | ER | P | 3644961 |
IES COMMERCIAL, INC. | ER | P | 03/14/2008 | CEILINGS MARKED ON SHEET E-3 OK | TIMA | TIMA | | ER | P | 3644953 |
IES COMMERCIAL, INC. | ER | P | 03/07/2008 | DOCTORS SLEEP ROOM BATHROOM HARD LIDS & REMAINING WALL OK | TIMA | TIMA | | ER | P | 3644944 |
IES COMMERCIAL, INC. | ER | P | 02/26/2008 | WALLS MARKED ON PLANS OK | MATTHEW | MATTHEW | | ER | P | 3644937 |
IES COMMERCIAL, INC. | ER | P | 02/19/2008 | SOFFITS MARKED ON PLANS | MATTHEW | MATTHEW | | ER | P | 3644929 |
IES COMMERCIAL, INC. | ER | P | 02/15/2008 | SOFFIT MARKED ON PLANS OK | MATTHEW | MATTHEW | | ER | P | 3644920 |
IES COMMERCIAL, INC. | ER | P | 02/14/2008 | WALLS AND SOFFITS MARKED ON PLANS | MATTHEW | MATTHEW | | ER | P | 3644913 |
IES COMMERCIAL, INC. | ER | P | 02/08/2008 | WALLS MARKED ON PLANS OK | MATTHEW | MATTHEW | | ER | P | 3644904 |
RIVIERA ELECTRIC | ER | P | 02/01/2008 | WALLS MARKED ON E-2 OK | TIMA | TIMA | | ER | P | 3644810 |
RIVIERA ELECTRIC | ER | P | 01/25/2008 | WALLS MARKED ON PLANS OK | MATTHEW | MATTHEW | | ER | P | 3644801 |
SIMPSON COMPANY | H= | C | 04/29/2008 | NEW SPLICE FOR 6TH FLOOR. | JON | JON | | H= | C | 3667684 |
SIMPSON COMPANY | H= | P | 04/24/2008 | DID NOT GO ON INSPECTION, HAD PHONE CONVERSATION WITH KENT CAMPBELL WITH SIMPSON. THERE WAS NO CALL AHEAD OR NO NEW INFORMATION PROVIDED FOR THIS INSPECTION. KENT IS NOT SURE ABOUT THIS JOB AND IS RESEARCHING AND WILL CALL INSPECTION WHEN READY. | JON | JON | | H= | P | 3644859 |
SIMPSON COMPANY | H= | P | 03/31/2008 | APPEARS EXHAUST SYSTEM ON BALANCE REPORT IS OFF BY 30%, NOTE ON PLANS DID INDICATE THAT EXHAUST FAN MAY HAVE TO BE CHANGED OR FAN SPEED INCREASED. JANITORS CLOSET DAMPER AT EXHAUST GRILL WAS CLOSED. REST OK. | JON | JON | | H= | P | 3644897 |
SIMPSON COMPANY | HD | P | 03/13/2008 | TRANSFERS, FLEX, DIFFUSERS FOR ENTIRE PROJECT COMPLETE. NEED TO COMPLETE EXHAUST DUCT IN UNFINISHED AREA AND TIE IN BATH DUCTS TO REGISTERS IN ALL BATHROOMS. STILL NEED PERMKT FOR HOT WATER PIPING FOR RADIANT PANELS AND VERIFY THAT SOFT COPPER TUBING AT RADIANT PANELS DO NOT REQUIRE INSULATION. APPROVED PLANS NOT ON JOB SITE, THEY ARE BACK IN REVIEW FOR ELECTRICAL CHANGES AT TIME OF INSPECTION. | ERIC | ERIC | | HD | P | 3644891 |
SIMPSON COMPANY | HD | P | 02/15/2008 | THIS INSPECTION WAS AN HWP, TEST AND VISUAL OK AND READY FOR INSULATION.. NEED HEAT PERMIT OBTAINED BY MARQUEZ AS TO ALLOW A HEAT INSPECTION UNDER THE RIGHT LICENSE NUMBER. | JON | JON | | HD | P | 3644883 |
SIMPSON COMPANY | HD | P | 02/13/2008 | SEE BLUE HIGH LIGHTS DATED TODAY FOR EXHAUST AND TRANSFER DUCTS. | JON | JON | | HD | P | 3644875 |
SIMPSON COMPANY | HD | P | 01/31/2008 | SEE ORANGE HIGH LIGHTS ON CONTRACTOR SET OF PLANS DATED TODAY. FOREMAN'S NAME IS JIM ON SITE AND HE WILL ENSURE A CALL AHEAD NUMBER IS PROVIDED FOR FUTURE INSPECTIONS. MEDIUM AND LOW PRESSURE OK FOR WRAP,,,RETURN DUCT AND SUPPLY DUCT FROM SHAFT CONNECTIONS AT FIRE SMOKE DAMPERS COMPLETE, ENSURE ACCESS DOORS BEFORE FINAL. STILL NEED TO SEE EXHAUST DUCT , TRANSFERS, FLEX AND DIFFUSERS. | JON | JON | | HD | P | 3644867 |
MARQUEZ CONSTRUCTORS, INC. | P= | C | 03/28/2008 | REMOVED SPRAYS | JEFF | JEFF | | P= | C | 3644851 |
MARQUEZ CONSTRUCTORS, INC. | P= | P | 03/27/2008 | UNPROTECTED HOSE SPRAYS X 2, REST OK | JEFF | JEFF | | P= | P | 3644843 |
MARQUEZ CONSTRUCTORS, INC. | PTO | C | 02/15/2008 | | JEFF | JEFF | | PTO | C | 3644835 |
MARQUEZ CONSTRUCTORS, INC. | PTO | P | 02/06/2008 | LACKS DOMESTIC WATER AT MAIN CORRIDOR AND SHOWER VALVES, REST OK | JEFF | JEFF | | PTO | P | 3644827 |
MARQUEZ CONSTRUCTORS, INC. | PTO | P | 02/04/2008 | LOST TEST DWV AT RR 633/634, TRAP RISER AT MOP SINK AT SAME EXCEEDS 24", DOMESTIC WATER OVERHEAD OK, NEED HALL AND BATHROOM/SINK WEST SIDE COMPLETED | JEFF | JEFF | | PTO | P | 3644818 |