HUME CONSTRUCTORS INC | B= | C | 09/24/2008 | | RICK | RICK | | B= | C | 3745918 |
HUME CONSTRUCTORS INC | B= | P | 07/26/2008 | Temp CO: need cabinets in pharmacy | KIM | KIM | | B= | P | 3698554 |
HUME CONSTRUCTORS INC | B= | P | 06/25/2008 | NEED SIGN @ UNISEX BATHROOM / ALL OTHER O.K. | JEREMY | JEREMY | | B= | P | 3698479 |
FOUR BAR MECHANICAL | BSP | T | 06/24/2008 | PAID (REC#813085) ADDITIONAL PLAN REVIEW TIME: $50 From: DALEH splice for change to plan delta 4 owner added new 14" round duct fro future | DALEH | DALEH | | BSP | T | 3697694 |
HUME CONSTRUCTORS INC | BFR | P | 03/06/2008 | WALLS OK | RICK | RICK | | BFR | P | 3645307 |
HUME CONSTRUCTORS INC | BSP | T | 02/25/2008 | PAID (REC#793886)ADDITIONAL PLAN REVIEW TIME: $50.000 From: DALEH splice for new demo mechanical and mechanical sheet | DALEH | DALEH | | BSP | T | 3645299 |
FOUR BAR MECHANICAL | BSP | T | 02/25/2008 | PAID (REC#793885)ADDITIONAL PLAN REVIEW TIME: $50.000 From: TCRIPPEN venting see clouded areas | TCRIPPEN | TCRIPPEN | | BSP | T | 3645361 |
HUME CONSTRUCTORS INC | BFR | P | 02/19/2008 | walls ok pending detail to north pharmancy wall not going to deck | DANF | DANF | | BFR | P | 3645289 |
HUME CONSTRUCTORS INC | BSP | T | 02/07/2008 | PAID (REC#792161)ADDITIONAL PLAN REVIEW TIME: $50.000 From: RICH REVISED LAYOUTS FOR STORAGE AND PHARMACY AREA | RICH | RICH | | BSP | T | 3645263 |
HUME CONSTRUCTORS INC | BSP | T | 02/07/2008 | PAID (REC#792166)ADDITIONAL PLAN REVIEW TIME: $50.000 From: RUSSELL splice for new mechanical sheet | RUSSELL | RUSSELL | | BSP | T | 3645273 |
HUME CONSTRUCTORS INC | BSP | T | 02/07/2008 | PAID (REC#792167)ADDITIONAL PLAN REVIEW TIME: $50.000 From: GARYL | GARYL | GARYL | | BSP | T | 3645281 |
MANITOU ELECTRIC, LLC | E= | C | 09/19/2008 | | JERRY | JERRY | | E= | C | 3743103 |
MANITOU ELECTRIC, LLC | E= | R | 09/16/2008 | ACCESS TO TERMINATED CABLE,ID PANEL SCHEDULES CORRECTLY | JERRY | JERRY | | E= | R | 3741558 |
MANITOU ELECTRIC, LLC | E= | P | 06/06/2008 | ALL OF PHARMACY AND PANEL SCHEDULE
| JERRY | JERRY | | E= | P | 3688144 |
MANITOU ELECTRIC, LLC | ER | P | 03/31/2008 | GRID CEILING FOR THE 2 LARGE ROOMS ON THE WEST SIDE | JERRY | JERRY | | ER | P | 3645353 |
MANITOU ELECTRIC, LLC | ER | P | 03/28/2008 | GRID CEILING OF EXTERIOR OFFICES WEST AND NORTH SIDES | JERRY | JERRY | | ER | P | 3645346 |
MANITOU ELECTRIC, LLC | ER | P | 03/28/2008 | GRID CEILING OF EXTERIOR OFFICES WEST AND NORTH SIDES | JERRY | JERRY | | ER | P | 3645339 |
MANITOU ELECTRIC, LLC | ER | P | 02/29/2008 | WALLS COMPLETE | JERRY | JERRY | | ER | P | 3645330 |
MANITOU ELECTRIC, LLC | ER | P | 02/25/2008 | UNDERGROUND IN OFFICE | JERRY | JERRY | | ER | P | 3645322 |
MANITOU ELECTRIC, LLC | ER | P | 02/19/2008 | WALLS COLUMN AA TO CC | MATTHEW | MATTHEW | | ER | P | 3645314 |
REFRIGERATION ENGINEERS,INC | H= | C | 06/25/2008 | RECEIVED BALANCE REPORT. PLANS ARE CORRECTED. MECHANICAL ROOM COMPLETE. | JON | JON | | H= | C | 3697891 |
REFRIGERATION ENGINEERS,INC | HD | P | 05/20/2008 | FOR FINAL STILL NEED PLAN REVISION FOR ADDED 14'' SUPPLY AIR LINE TO STORAGE ROOM. NEED PROPER DUCT SUPPORT IN MECH ROOM. NEED BRACES ON CANVAS CONNECTORS REMOVED. NEED LISTING INFORMATION FOR CABLE DUCT HANGERS AND HANGERS TO BE TO INSTRUCTIONS FOR INSTALLATION AND SPACING BY NEXT INSPECTION. NEED BALANCE REPORT. NEED HOT WATER, CHILLED WATER AND CONDENSATE COMPLETED. | JON | JON | | HD | P | 3678562 |
REFRIGERATION ENGINEERS,INC | H= | P | 04/17/2008 | NEED BALANCE REPORT AND MECH ROOM EQIUPMENT SET AND DUCT COMPLETED. | JON | JON | | H= | P | 3645256 |
REFRIGERATION ENGINEERS,INC | HD | P | 04/17/2008 | STILL NEED PLAN REVISED. WRAP ON 14''OK... RETAINING ANGLES COMPLETE. STILL NEED MECH ROOM WORK COMPLETED. | JON | JON | | HD | P | 3645248 |
REFRIGERATION ENGINEERS,INC | HD | P | 04/16/2008 | OK FOR WRAP ON NEW 14'' FROM MECH ROOM TO STORAGE ROOM. READY FOR RETAINING ANGLES ON FIRE SMOKE DAMPERS X2. STILL NEED PLANS REVISED. | JON | JON | | HD | P | 3645240 |
REFRIGERATION ENGINEERS,INC | HWP | C | 04/16/2008 | ALL PIPING UNDER SYSTEM PRESSURE AND TIED IN TO NEW EQUIPMENT | ERIC | ERIC | | HWP | C | 3645233 |
REFRIGERATION ENGINEERS,INC | HD | P | 04/11/2008 | FIRE SMOKE DAMPER FRAME AT WEST SIDE FOR 2 DAMPERS OK, NEED SHEET ROCK REINSTALLED AROUND THESE DAMPERS BEFORE RETAINING ANGLES AND CALLED FOR INSPECTION. SMOKE DAMPERS X2 OK AT EAST SIDE. NEED PLANS REVISED FOR NEW DUCT CHANGES OUT OF MECH ROOM AND CALLED FOR INSPECTION WHEN READY. NO MECH ROOM EQUIPMENT INSTALLED AS OF TODAY. | JON | JON | | HD | P | 3645225 |
REFRIGERATION ENGINEERS,INC | HD | P | 04/09/2008 | OK FOR CEILING AT EAST SIDE. STILL NEED MECH ROOM COMPLETED AND ISSUES WITH SMOKE DAMPERS RESOLVED. DOES HAVE AT LEAST 1- FIRE SMOKE DAMPER INSTALLED WHICH IS CONCEALED AND DOES NOT APPEAR TO MEET INSTRUCTIONS. WENT OVER ALL THIS WITH BRIAN AND JOB SUPERINTENDENT.. PLANS ONLY CALL FOR SMOKE DAMPERS. | JON | JON | | HD | P | 3645217 |
REFRIGERATION ENGINEERS,INC | HD | P | 03/14/2008 | VAV DUCT TIE-INS AT EAST SIDE. OK TO INSULATE | ERIC | ERIC | | HD | P | 3645209 |
REFRIGERATION ENGINEERS,INC | HD | P | 03/04/2008 | NEED SMOKE DAMPER INSTRUCTIONS, 2 DAMPERS ON WEST SIDE ARE CONCEALED ALREADY. OTHER SMOKE DAMPERS NOT READY YET. OK FOR MEDIUM PRESSURE AND LOW PRESSURE DUCT WRAP ON EAST SIDE, STILL LACKING NEW VAV BOXES EAST SIDE. OK FOR WRAP ON WEST SIDE, NEED TO SEE FLEX, DIFFUSERS AND DUCT WRAP WEST SIDE BEFORE COVER. | JON | JON | | HD | P | 3645201 |
FOUR BAR MECHANICAL | P= | C | 09/11/2008 | Pharmacy sink changed to future, will require additional permit and inspection to set sink. | KYE | KYE | | P= | C | 3738957 |
FOUR BAR MECHANICAL | P= | P | 06/09/2008 | all ok minus s/west sink that is pumped. | MARTY | MARTY | | P= | P | 3688528 |
FOUR BAR MECHANICAL | P= | P | 05/12/2008 | CAULK WALLHUND LAV AND TOILETS. FINISH SINK IN NW. CORNER. NEED LETTER FROM ENGINEER LISTING SINK AS FUTURE. | MICK | MICK | | P= | P | 3674164 |
FOUR BAR MECHANICAL | PTO | C | 03/06/2008 | SEE VENT TIED IN ON EAST FUTURE SINK WILL SEE FRIDAY. | MARTY | MARTY | | PTO | C | 3645382 |
FOUR BAR MECHANICAL | PTO | P | 02/20/2008 | LIFT STATION WEST SIDE PLUS WATERS TO LIFT STATION. | MARTY | MARTY | | PTO | P | 3645377 |
FOUR BAR MECHANICAL | PB | C | 02/07/2008 | | MARTY | MARTY | | PB | C | 3645369 |