WELLS & WEST GENERAL CONTRACTORS, INC. | B= | C | 04/15/2008 | ITEMS COMPLETED | ED | ED | | B= | C | 3650030 |
WELLS & WEST GENERAL CONTRACTORS, INC. | B= | P | 03/14/2008 | COMPLETE INSTALLATION OF MAX OCCUPANCY SIGNS / FINAL OK WITH OTHER FINAL INSPECTIONS. | BOBB | BOBB | | B= | P | 3650022 |
COLORADO ELECTRICAL INSTALLATION | BSP | T | 03/03/2008 | PAID (REC#794625)ADDITIONAL PLAN REVIEW TIME: $50.000 From: SHELBY | SHELBY | SHELBY | | BSP | T | 3649898 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BSP | R | 02/28/2008 | WRONG PERMIT NUMBER FOR DEMO. CORRECT # IS; G48486 | BOBB | BOBB | | BSP | R | 3650014 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 02/28/2008 | OK ABOVE CEILING WITH ELECTRIC INSPECTION. | BOBB | BOBB | | BFR | P | 3650006 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 02/22/2008 | Ok interior wall partition at south west area of remodel. | BOBB | BOBB | | BFR | P | 3649999 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BIN | C | 01/29/2008 | | BOBB | BOBB | | BIN | C | 3649992 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 01/28/2008 | Wall framing ok with other rough inspections. | BOBB | BOBB | | BFR | P | 3649985 |
COLORADO ELECTRICAL INSTALLATION | E= | C | 04/14/2008 | | MATTHEW | MATTHEW | | E= | C | 3649945 |
COLORADO ELECTRICAL INSTALLATION | E= | R | 04/11/2008 | NEED TO SUPPORT FLEX FEEDING OFFICE FURNITURE J-BOXES TO CODE | TIMA | TIMA | | E= | R | 3649938 |
COLORADO ELECTRICAL INSTALLATION | E= | P | 03/11/2008 | ALL OK EXCEPT NEED OFFICE FURNITURE WIRED,NEED GROMET BUSHING ON RTU-1,CORRECT PANEL SCEDULE ON CU-1 IN PANEL R14A | TIMA | TIMA | | E= | P | 3649930 |
COLORADO ELECTRICAL INSTALLATION | ER | C | 02/29/2008 | CEILINGS OK | TIMA | TIMA | | ER | C | 3649922 |
COLORADO ELECTRICAL INSTALLATION | ER | P | 02/21/2008 | WALL ADDED FOR ROOM 101A OK | MATTHEW | MATTHEW | | ER | P | 3649915 |
COLORADO ELECTRICAL INSTALLATION | ER | P | 01/25/2008 | WALLS OK | MATTHEW | MATTHEW | | ER | P | 3649906 |
PROFESSIONAL PIPING, LLC | H= | C | 04/15/2008 | GAS FINAL. | JON | JON | | H= | C | 3649977 |
MECHONE, INC. | H= | C | 03/14/2008 | RECEIVED BALANCE REPORT. | LYNNS | LYNNS | | H= | C | 3649890 |
PROFESSIONAL PIPING, LLC | HC | C | 02/29/2008 | INCREASING LOAD 565K | JON | JON | | HC | C | 3649969 |
PROFESSIONAL PIPING, LLC | HI | C | 02/29/2008 | GAS COMPLETE TO PLANS 10 LB TEST. | JON | JON | | HI | C | 3649961 |
PROFESSIONAL PIPING, LLC | HI | P | 02/28/2008 | SEND 565K LOAD INCREASE TO CSPU AT COMPLETION OF GAS INSPECTION. STILL NEED TEST ON ENTIRE 2'' LINE FROM METER TO BOTH SHUT-OFF VALVES ON ROOF. SUPPORT NEW HEADER AND PIPING AT METER LOCATION. | JON | JON | | HI | P | 3649954 |
MECHONE, INC. | H= | P | 02/28/2008 | SEE DUCT INSPECTION NOTES,, OK FOR TILE. | JON | JON | | H= | P | 3649882 |
MECHONE, INC. | HD | C | 02/28/2008 | DUCT COMPLETE. FOR FINAL NEED SMOKE SHUT DOWN PER PLANS AT RTU-1 AND COMPLETE BALANCE REPORT. | JON | JON | | HD | C | 3649874 |
MECHONE, INC. | HD | P | 02/19/2008 | NEED GAS PERMIT AND INSPECTION. NEED FLEX AND DIFFUSERS. FURNACE VENT OK. TWP PACKAGE UNITS AND DUCT ON PADS OK. | JON | JON | | HD | P | 3649867 |
MECHONE, INC. | HD | P | 01/28/2008 | ROUGH DUCT FOR ONE FURNACE SYSTEM AND 2 RTU SYSTEMS. READY FOR FLEX AND DIFFUSERS.. NEED EQUIPMENT SET AND VENT INSPECTION WHEN READY. | JON | JON | | HD | P | 3649860 |