G. A. MAXWELL CONSTRUCT., INC. | B= | C | 06/26/2008 | FIRE FINAL SIGNED OFF ON CARD | BERTW | BERTW | | B= | C | 3698997 |
G. A. MAXWELL CONSTRUCT., INC. | B= | R | 04/03/2008 | 2nd and 3rd floors inspected, not ready, need smoke seals, doors closer have to work, missing exit signs where new corridor doors were installed, need to check on adding smoke detectors in doubled rooms 14" drop dowm pass threw. need fire final, complete other inspectios | ED | ED | | B= | R | 3659225 |
G. A. MAXWELL CONSTRUCT., INC. | BFR | P | 02/19/2008 | HANDICAP UNITS "C" FIRST FLOOR OK | BERTW | BERTW | | BFR | P | 3659219 |
G. A. MAXWELL CONSTRUCT., INC. | BSP | T | 02/08/2008 | PAID (REC#791486)ADDITIONAL PLAN REVIEW TIME: $50.000 From: MICHAEL Splice change for non-conforming hallway | MICHAELA | MICHAELA | | BSP | T | 3659211 |
G. A. MAXWELL CONSTRUCT., INC. | BSP | P | 02/07/2008 | PER CONVERSATION WITH ROGER LOVELL AND MICHAEL A @ PLAN CHECK DEPT THIS AM, CONTRACTOR WILL HAVE PLANS REVISED AND RESTAMPED WITH CHANGES SCANNED INTO SYSTEM FOR 1 HR CORRIDOR SITUATATION IN PREVIOUS FRAME INSPECTION NOTES | BERTW | BERTW | | BSP | P | 3659204 |
G. A. MAXWELL CONSTRUCT., INC. | BFR | P | 02/07/2008 | WALLS OK 3RD FLOOR ROOMS | BERTW | BERTW | | BFR | P | 3659199 |
G. A. MAXWELL CONSTRUCT., INC. | BFR | P | 02/01/2008 | FRAMING CHANGES OK ON 1ST AND 2ND LEVEL ROOMS/NEED APPROVED DETAIL FOR 1HR RATING @ INFILL AREA WHERE DOORS TO CORRIDOR HAVE BEEN REMOVED AND APPROVED DETAIL FOR 1HR CORRIDOR /TYPE OF CONSTRUCTION IN FEILD DOESNT MATCH PLANS | BERTW | BERTW | | BFR | P | 3659192 |
D & J QUALITY ELECTRIC INC | E= | C | 04/01/2008 | ALL CORRECTIONS HAVE BEEN MADE. | DEAN | DEAN | | E= | C | 3659166 |
D & J QUALITY ELECTRIC INC | E= | P | 03/27/2008 | CORRECTIONS FOR 1ST FLOOR, ROOMS 147, 152, 162, 174, 182, ALL NEED ALL CONDUCTORS OF SWITCH LEG UP TO ABANDUND LIGHT TO BE CUT SHORT WHERE IT ENTERS THE BOX. ALSO HAVE GFCI IN ROOM 178 NOT RESETTING. STILL NEED ROMEX SHEATH INTO BOX IN ROOM 254. VERIFY PANEL SCHEDULE AND ROOM #'S WITH GC. | DEAN | DEAN | | E= | P | 3659160 |
D & J QUALITY ELECTRIC INC | E= | P | 03/14/2008 | 2ND FLOOR ROOMS 245 THRU 283NEW CIRCUIT FOR DRY BAR MICRO, MINI FRIDGE AND COUNTER ALL OK EXCEPT ROOM 279 NEED NEW GFCI RECPET.-------------ALSO NEED TO RECHECK BLANKED OFF SWITCH IN ROOM 254, QUICK WIRE CONNECTOR POPPED OFF AND ROMEX SHEATH NOT INTO BOX------------ | DEAN | DEAN | | E= | P | 3659153 |
D & J QUALITY ELECTRIC INC | E= | P | 03/13/2008 | 3RD FLOOR ROOMS OK. 345 THRU 381. | DEAN | DEAN | | E= | P | 3659147 |
D & J QUALITY ELECTRIC INC | ES | C | 03/10/2008 | GROUNDING ELECTRODE FROM ALL 3 TRANSFORMERS TO WATER OK. | DEAN | DEAN | | ES | C | 3659141 |
D & J QUALITY ELECTRIC INC | ES | P | 03/07/2008 | STILL NEED GROUNDING ELECTRODE FROM TRANSFORMERS ON ALL 3 FLOORS TO WATER.-----------NEUTRALS AND GORUNDS HAVE BEEN SEPARATED IN THE EXISTING 480-VOLT PANELS------------- | DEAN | DEAN | | ES | P | 3659133 |
D & J QUALITY ELECTRIC INC | ES | R | 03/04/2008 | MISSING GROUNDING ELECTRODE CONDUCTORS FROM ALL 3 TRANSFORMERS (NEED TO GO TO WATER AT POINT OF ENTRANCE INTO BUILDING), NEUTRALS AND EQUIPMENT GROUNDS ARE TIED TOGETHER IN THE EXISTING 200-AMP 480-VOLT PANELS THAT THE NEW FEEDS ARE COMING FROM. NEED TO SEPARATE. | DEAN | DEAN | | ES | R | 3659125 |
D & J QUALITY ELECTRIC INC | ER | P | 02/13/2008 | 1ST FLOOR C UNITS OK | BRET | BRET | | ER | P | 3659118 |
D & J QUALITY ELECTRIC INC | ER | P | 02/07/2008 | 3RD FLOOR ROOMS OK I WILL NEED TO INSPECT ATTIC ON NEXT INSPECTION, | BRET | BRET | | ER | P | 3659111 |
D & J QUALITY ELECTRIC INC | ER | P | 02/01/2008 | 1ST AND 2ND FLOOR ROOMS ONLY . CORRIDOR AND C UNITS NOT READY. RELOCATE BEDROOM SWITCH TO OTHER SIDE OF WALL SO THAT IT IS ACCESSIBLE AT ENTRY TO ROOM. (SEE JEFF FOR LOCATIONS) | BRET | BRET | | ER | P | 3659102 |
D & J QUALITY ELECTRIC INC | ER | R | 01/31/2008 | (2nd floor) secure nm in walls where sheetrock has been removed, mc on grid in corridors. | BRET | BRET | | ER | R | 3659096 |
FRONTIER MECHANICAL SYSTEMS INC | P= | C | 04/04/2008 | | MARTY | MARTY | | P= | C | 3659187 |
FRONTIER MECHANICAL SYSTEMS INC | P= | P | 04/03/2008 | set stops on showers 120 max,hand helds leak. | MARTY | MARTY | | P= | P | 3659182 |
FRONTIER MECHANICAL SYSTEMS INC | PTO | C | 02/11/2008 | 175-181 | MARTY | MARTY | | PTO | C | 3659177 |
FRONTIER MECHANICAL SYSTEMS INC | PB | C | 02/05/2008 | VENTS TO 2ND FLOOR OK,ALREADY TESTED. | MARTY | MARTY | | PB | C | 3659171 |