ALTURAS SPACE CENTER & NEWPORT, LLC | H01 | C | 01/23/2024 | ANNUAL 3/23 -- SCHINDLER W/ KONE SERVICE -- OIL IS LEAKING ON TO PIT FLOOR -- CAR TOP LIGHT IS OUT -- NON ELEVATOR RELATED ITEMS TO BE REMOVED FROM MACHINE ROOM -- MONTHLY FIREFIGHTERS LOGS & QUARTERLY EMERGENCY PHONE LOGS TO BE MAINTAINED -- NOTE: WENT OVER FIREFIGHTERS EMERGENCY OPERATION AND QUARTERLY EMERGENCY TEST WITH BUILDING ENGINEER AND WHERE TO LOG IT MONTHLY IN THE MACHINE ROOM (Receipt #2027235) cat 1 2/24 BH | BENH | BENH | | H01 | C | 7975310 |
ALTURAS SPACE CENTER & NEWPORT, LLC | H02 | C | 07/31/2023 | H02 --- CAT1 -- 3/2023 -- SCHINDLER W/ KONE SERVICE. CHECK PREVIOUS LISTED ITEMS AT H01 | ROBERTV | ROBERTV | | H02 | C | 7812249 |
ALTURAS SPACE CENTER & NEWPORT, LLC | H01 | C | 01/19/2023 | ANNUAL 01/2022 -- SCHINDLER WITH KONE SERVICE --/ MONTHLY FIRE SERVICE LOGS NOT BEING MAINTAINED --/ REMOVE ALL NON ELEVATOR RELATED ITEMS OUT OF THE MACHINE ROOM --/ CAR TOP LIGHTING IS OUT --/ PPRBD NOTE: CATEGORY 1 HYDRAULIC TESTING IS DUE THIS MONTH (Receipt #1927516) -- (pprbd note: cat1 - 03/2023, mechanics report states a packing has been purchased) | MIKEM | MIKEM | | H01 | C | 7638808 |
GPIF CO SPRINGS 8 LLC | H02 | C | 07/21/2022 | HO2 -- ANNUAL 01/2022 -- SCHINDLER WITH KONE SERVICE | MIKEM | MIKEM | | H02 | C | 7455412 |
GPIF CO SPRINGS 8 LLC | H01 | C | 01/12/2022 | ANNUAL 11/2020 -- SCHINDLER W/ KONE SERVICE -- ANNUAL CATEGORY 1 TEST PAST DUE (Receipt #1836050) (Cat1 -- 1/2022) | BENH | BENH | | H01 | C | 7237433 |
GPIF CO SPRINGS 8 LLC | H02 | C | 07/28/2021 | CAT 1 11/20 SCHINDLER, KONE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 7052887 |
GPIF CO SPRINGS 8 LLC | H01 | C | 01/06/2021 | WITNESSED 11/20 (Receipt #1740797) | ERIC | ERIC | | H01 | C | 6826821 |
GPIF CO SPRINGS 8 LLC | H06 | C | 11/24/2020 | WITNESSED CATEGORY 1 HYDRO TEST W/ KONE - (NO CODE ISSUES) | ROBERTV | ROBERTV | | H06 | C | 6788205 |
GPIF CO SPRINGS 8 LLC | H02 | C | 07/20/2020 | RP 8/19 SCHINDLER, KONE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 6643205 |
GPIF CO SPRINGS 8 LLC | H01 | C | 01/30/2020 | RP 8/19--SCHINDLER W/ KONE SERVICE (Receipt #1659284) | CALE | CALE | | H01 | C | 6469456 |
GPIF CO SPRINGS 8 LLC | H02 | C | 07/25/2019 | RP 8/18--SCHINDLER--HO2 | CALE | CALE | | H02 | C | 6276998 |
1055 NEWPORT | H01 | C | 01/31/2019 | RP -- 8/18 -- SCHINDLER (Receipt #1573160) | ROBERTV | ROBERTV | | H01 | C | 6093248 |
1055 NEWPORT | H02 | C | 07/17/2018 | SCHINDLER -- (SEE STEVE RICHARDSON FOR ACCESS)........ REQUIRED ANNUAL CATEGORY 1 TESTING FOR THIS ELEVATOR IS EXPIRED AND NEED PERFORMED WITHIN 30 DAYS. ALSO, CHECK VOLUME ON EMERGENCY PHONE | ROBERTV | ROBERTV | | H02 | C | 5905452 |
1055 NEWPORT | H01 | C | 01/16/2018 | RP -- 6/17 -- SCHINDLER. (SEE STEVE RICHARDSON FOR ACCESS) - INCREASE VOLUME ON EMERGENCY PHONE. (Receipt #1476312) | ROBERTV | ROBERTV | | H01 | C | 5737860 |
1055 NEWPORT | H02 | C | 07/14/2017 | H02 | ROBERTV | ROBERTV | | H02 | C | 5564014 |
1055 NEWPORT | H01 | C | 01/26/2017 | RP -- 6/16 -- SCHINDLER (Receipt #1397625) | ROBERTV | ROBERTV | | H01 | C | 5399042 |
1055 NEWPORT | H02 | C | 07/01/2016 | H02 | ROBERTV | ROBERTV | | H02 | C | 5235805 |
1055 NEWPORT | H01 | C | 01/22/2016 | RP -- 10/15 -- SCHINDLER (SEE STEVE RICHARDSON FOR ACCESS). EMERGENCY LIGHT IN ELEVATOR IS STILL NOT WORKING, THIS HAS BEEN NOTED A VIOLATION SINCE 9/2014 AND STILL HAS NOT BEEN ADDRESSED. (Receipt #1309569) | ROBERTV | ROBERTV | | H01 | C | 5121001 |
1055 NEWPORT | H06 | C | 10/09/2015 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS ARE STILL NOT WORKING 3RD NOTIFICATION | ERIC | ERIC | | H06 | C | 5053879 |
1055 NEWPORT | H02 | C | 07/16/2015 | RP -- 9/14 -- SCHINDLER. EMERGENCY LIGHT NOT WORKING. | ROBERTV | ROBERTV | | H02 | C | 4994222 |
1055 NEWPORT | H01 | C | 01/13/2015 | WITNESSED 9/14 (Receipt #1240795) | JOHNW | JOHNW | | H01 | C | 4884324 |
1055 NEWPORT | H06 | C | 09/15/2014 | RP -- 9/14 -- SCHINDLER. WITNESSED 5 YEAR HYDRO TEST. EMERGENCY LIGHT AND ALARM BARELY WORKING. | ROBERTV | ROBERTV | | H06 | C | 4815521 |
1055 NEWPORT | H02 | C | 07/21/2014 | RP--5--13--SCHINDLER--EMERGENCY LIGHT NOT WORKING --PRESSURE RELIEF TEST EXPIRED Need 5 year witnessed test | JOHNW | JOHNW | | H02 | C | 4780418 |
1055 NEWPORT | H01 | C | 01/30/2014 | RP--5--13--SCHINDLER (Receipt #1177280) | JOHNW | JOHNW | | H01 | C | 4680262 |
1055 NEWPORT | H02 | C | 07/09/2013 | RP--5---13--SCHINDLER | JOHNW | JOHNW | | H02 | C | 4558929 |
1055 NEWPORT | H01 | C | 01/24/2013 | RP--3--12--SCHINDLER (Receipt #1107417) | JOHNW | JOHNW | | H01 | C | 4459662 |
1055 NEWPORT | H02 | C | 07/17/2012 | RP--3--12--SCHINDLER | JOHNW | JOHNW | | H02 | C | 4342804 |
1055 NEWPORT | H01 | C | 01/12/2012 | RP--6--11--SCHINDLER--SEE STEVE AT 1050 FOR ACCESS (Receipt #1022369) | JOHNW | JOHNW | | H01 | C | 4258775 |
1055 NEWPORT | H02 | C | 07/15/2011 | RP--6--11--SCHINDLER | JOHNW | JOHNW | | H02 | C | 4178276 |
1055 NEWPORT | H01 | C | 01/21/2011 | RP--2--10--SCHINDLER (Receipt #955853) | JOHNW | JOHNW | | H01 | C | 4101816 |
1055 NEWPORT | H02 | C | 07/13/2010 | RP 2/10 SCHINDLER | ERIC | ERIC | | H02 | C | 4008868 |
1055 NEWPORT | H01 | C | 01/21/2010 | RP--1--09--SCHINDLER (Receipt #893506) | JOHNW | JOHNW | | H01 | C | 3934930 |
1055 NEWPORT | H02 | C | 08/26/2009 | RP--1--09--SCHINDLER--MOVED TO JANUARY | JOHNW | JOHNW | | H02 | C | 3876613 |
1055 NEWPORT | H01 | C | 02/23/2009 | RP--3--08--SHINDLER-- (Receipt #848319) | JOHNW | JOHNW | | H01 | C | 3807438 |
1055 NEWPORT | H02 | C | 08/13/2008 | RP 3-08 [ 202-520 ] --- SCHINDLER ELEVATOR --- GO TO 1050 AND ASK FOR MAINTENANCE TO ESCORT TO BLDG. 1055 TO UNLOCK MACHINE ROOM | LES | LES | | H02 | C | 3724818 |
1055 NEWPORT | H01 | C | 02/04/2008 | INITIAL INSPECTION--PERMIT ISSUED | TOM | TOM | | H01 | C | 3634526 |
1055 NEWPORT | H06 | C | 02/01/2008 | WITNESSED | JOHNW | JOHNW | | H06 | C | 4222186 |