ABERDEEN CONSTRUCTION, INC. | B= | C | 06/13/2008 | | DALE | DALE | | B= | C | 3691608 |
ABERDEEN CONSTRUCTION, INC. | B= | P | 06/11/2008 | complete all other inspection / need vert. grab bars / seal penatrations at 1 hr wall | DALE | DALE | | B= | P | 3690671 |
ABERDEEN CONSTRUCTION, INC. | BFR | P | 04/30/2008 | walls ok pending other inspections | DALE | DALE | | BFR | P | 3668974 |
ABERDEEN CONSTRUCTION, INC. | BFR | P | 04/22/2008 | walls ok except at front and demo pending other inspections | DALE | DALE | | BFR | P | 3662702 |
BEGEMAN ELECTRIC CO | E= | C | 05/22/2008 | | THOMAS | THOMAS | | E= | C | 3679972 |
BEGEMAN ELECTRIC CO | E= | R | 05/21/2008 | see rough | THOMAS | THOMAS | | E= | R | 3679337 |
BEGEMAN ELECTRIC CO | ER | R | 05/21/2008 | correct panel schedules---label panels with color codes & voltages---panel blanks missing | THOMAS | THOMAS | | ER | R | 3679330 |
BEGEMAN ELECTRIC CO | ER | P | 05/15/2008 | grid cielings complete--BEST ACCESS IS SERVICE ENTRANCE E 15 JUST WEST OF DEPT. MOTOR VEHICHLES--NORTH SIDE OF MALL | THOMAS | THOMAS | | ER | P | 3676842 |
BEGEMAN ELECTRIC CO | ER | P | 04/28/2008 | WALLS AND HARDLIDS | MIKEC | MIKEC | | ER | P | 3666780 |
BEGEMAN ELECTRIC CO | ER | P | 04/21/2008 | front arfea walls minus the north west wall and the bathroom walls ok'd | TERRY | TERRY | | ER | P | 3662684 |
ATEK HTG. & AIR CONDITIONING | H= | C | 06/12/2008 | RECEIVED BALANCE REPORT. | LYNNS | LYNNS | | H= | C | 3690793 |
ATEK HTG. & AIR CONDITIONING | H= | P | 06/09/2008 | PENDING BALANCE REPORT. | LYNNS | LYNNS | | H= | P | 3688993 |
ATEK HTG. & AIR CONDITIONING | HD | C | 05/20/2008 | ROUGH DUCT. NEED TO SEE BATH FAN DOUBLE WALLED TO TERMINATION AND RTU. OK TO DROP TILE IN FRONT. | LYNNS | LYNNS | | HD | C | 3678753 |
ATEK HTG. & AIR CONDITIONING | HD | P | 05/15/2008 | ISOLATE POSITIVE PRESSURE BATH EXHAUST DUCT FROM RETURN AIR PLENUM AS PER PRINTS. LATERALS WRAPPED PRIOR TO INSPECTION. EITHER MEET WITH INSPECTOR AT NEXT INSPECTION TO RANDOMLY EXPOSE LATERAL JOINTS OR REMOVE INSULATION ON ALL LATERAL JOINTS PRIOR TO NEXT INSPECTION. NOTE: ROOFTOP UNIT NOT LOOKED AT YET. | NANCY | NANCY | | HD | P | 3676602 |
POPES PLUMBING HEATING & AC INC. | P= | C | 05/28/2008 | | LEE | LEE | | P= | C | 3682292 |
POPES PLUMBING HEATING & AC INC. | P= | P | 05/27/2008 | THANKS TO ONE AND ALL INSPECTORS FOR NOT PUTTING THE SUITE NUMBER ON PERMIT---1) ADD 2-DF TO PERMIT 2) WATER HEATER WILL NOT ALLOW 105* HOT WATER TO ALL REQ'D FIXTURES | LYNNIE | LYNNIE | | P= | P | 3681732 |
POPES PLUMBING HEATING & AC INC. | PTO | C | 04/25/2008 | TRAP PRIMER ACCESS, HAMMER ARRESTORS AND EXPANSION DEVICE BY FINAL | LEE | LEE | | PTO | C | 3662689 |
POPES PLUMBING HEATING & AC INC. | PTO | L | 04/24/2008 | FIELD CANCELLED | LEE | LEE | | PTO | L | 3662692 |
POPES PLUMBING HEATING & AC INC. | PTO | R | 04/23/2008 | NOT READY, NO TESTS, STILL INSTALLING WATER PIPE, REINSP-ALL | LEE | LEE | | PTO | R | 3662697 |