PENROSE HOSPITAL FACILITIES | H06 | T | 03/20/2024 | PAID (REC#2045155) AFTER-HOURS INSPECTION: $200 From: ERIC After hours generator testing $200.00 | ERIC | ERIC | | H06 | T | 8027926 |
PENROSE HOSPITAL FACILITIES | H06 | C | 02/16/2024 | WITNESSED 5 YEAR TEST W/ OTIS -- GENERATOR TESTING IS REQUIRED TO COMPLETE THE 5 YEAR TEST (Receipt #2034477) | BENH | BENH | | H06 | C | 7997759 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/25/2024 | 5 YEAR 1/19 -- ANNUAL 1/23 -- OTIS & SERVICE -- / 5 YEAR WITNESS TESTING SCHEDULED WITH OTIS FOR WEEK OF 2/12/24 - 2/16/24 (Receipt #2027924) | DUSTINS | DUSTINS | | H02 | C | 7977564 |
PENROSE HOSPITAL FACILITIES | H03 | C | 11/06/2023 | 5 YEAR 1/19 -- ANNUAL 1/23 -- OTIS & SERVICE -- / PERFORMED RE-INSPECTION TO ONLY VERIFY BELT AND BELT MONITOR REPLACEMENT, ALL REPAIRS MADE NEED TO BE LOGGED WITHIN THE MAINTENANCE CONTROL PROGRAM (Receipt #2005620) mcp repair log updated, 11/9/23 DS | DUSTINS | DUSTINS | | H03 | C | 7910486 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/25/2023 | 5YR 01/2019 - ANNUAL 01/2023 - OTIS AND SERVICE -/ PROVIDE I.T.S. BELT MONITORING TESTING PROCEDURES OR REPLACE SUSPENSION DETECTION MEANS WITH OEM PULSE UNIT -/ PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL ITEM/S ARE ADDRESSED - (pprbd note: per otis, the belt monitor and belts will be replaced by the end of October 2023 mm) (Receipt #1972530) | MIKEM | MIKEM | | H01 | C | 7807516 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/27/2023 | HO2 -- ANNUAL 1/23 -- OTIS & SERVICE | BENH | BENH | | H02 | C | 7646843 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/21/2022 | 5YR 01/2019 -- ANNUAL 04/2022 -- OTIS AND SERVICE -- NO VISIBLE CODE ISSUES (Receipt #1885112) | MIKEM | MIKEM | | H01 | C | 7455208 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/28/2022 | 5 YEAR 1/19, CAT1 3/21, OTIS H02 cat 1 4/22 | ERIC | ERIC | | H02 | C | 7254246 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/13/2021 | 5YR -- 1/19 -- CAT1 -- 3/21 -- OTIS AND SERVICE. (NO VISIBLE CODE ISSUES) (Receipt #1789370) | ROBERTV | ROBERTV | | H01 | C | 7034139 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/11/2021 | H02 -- 5YR -- 1/19 -- CAT1 -- 3/20 -- OTIS AND SERVICE cat 1 3/21 | ROBERTV | ROBERTV | | H02 | C | 6831513 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/28/2020 | 5YR -- 1/19 -- ANNUAL 3/20 -- OTIS. (NO VISIBLE CODE ISSUES) (Receipt #1699703) | ROBERTV | ROBERTV | | H01 | C | 6653018 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/31/2020 | H02 -- 5YR -- 3/19 -- OTIS W/ TKE SERVICE. cat 1 3/20 | ROBERTV | ROBERTV | | H02 | C | 6470605 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/30/2019 | 5YR -- 3/19 -- OTIS W/ TKE SERVICE. (Receipt #1618258 from 07/30/2019) | ROBERTV | ROBERTV | | H01 | C | 6281863 |
PENROSE HOSPITAL FACILITIES | H06 | C | 03/15/2019 | WITNESSED 5 YEAR SAFETY TEST. NO ISSUES. NEW DRIVE MOTOR INSTALLED (Receipt #1582601) | ERIC | ERIC | | H06 | C | 6133953 |
PENROSE HOSPITAL FACILITIES | H05 | C | 07/26/2018 | ELEVATOR IS OUT OF SERVICE PENDING MAJOR REPAIRS -- H05 FOR NOW | ROBERTV | ROBERTV | | H05 | C | 5914580 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/17/2018 | THIS ELEVATOR IS OUT OF SERVICE --WILL PUT IN HO5 STATUS AT THE NEXT HO1 | JOHNW | JOHNW | | H02 | C | 5739321 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/31/2017 | 5 YEAR 8/13, ANNUAL 3/16 OTIS. TKE SERVICE AND LOCKBOX. NEED ANNUAL CAT 1 TEST (Receipt #1442959) | ERIC | ERIC | | H01 | C | 5580517 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/23/2017 | HO2 --MONITOR ISSUE WILL BE ADDRESSED MY MIKE DUKES THIS MONTH | JOHNW | JOHNW | | H02 | C | 5395941 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/29/2016 | 5YR -- 8/13 -- ANNUAL 3/16 -- OTIS AND LOCKBOX. NEED TO CORRECT BELT MONITOR FAULT ISSUE (3RD NOTICE), EMERGENCY PHONE NOT WORKING, MACHINE BRAKE WIRING ELECTRICAL BOX NEEDS SECURED. (Receipt #1345785) | ROBERTV | ROBERTV | | H01 | C | 5258158 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/19/2016 | 5 YEAR 8/13 OTIS. STILL NEED TO CORRECT BELT MONITOR FAULT ISSUE FROM PREVIOUS INSPECTION AND NEED GEN2 SPECIFIC MAINTENANCE CONTROL PROGRAM | ERIC | ERIC | | H02 | C | 5117815 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/24/2015 | 5 YEAR 8/13 OTIS. NEED GENII SPECIFIC MCP, NEED ANNUAL TESTS AND TEST TAGS, ROPE MONITOR FLASHING 15 "STANDBY, LEARN RUN REQUIRED" (Receipt #1276851) | ERIC | ERIC | | H01 | C | 5001614 |
PENROSE HOSPITAL FACILITIES | H02 | C | 02/06/2015 | 5YR 8-13 OTIS | TOM | TOM | | H02 | C | 4908737 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/09/2014 | 5 YEAR 8/13 OTIS (Receipt #1206372) | ERIC | ERIC | | H01 | C | 4773986 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/14/2014 | H02 | ERIC | ERIC | | H02 | C | 4671382 |
PENROSE HOSPITAL FACILITIES | H06 | C | 08/21/2013 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1150155) | ERIC | ERIC | | H06 | C | 4592103 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/30/2013 | HO6 TO BE COMPLETED IN AUGUST 2013 (Receipt #1145060) | ERIC | ERIC | | H01 | C | 4573931 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/18/2013 | 5YR 3-08--OTIS | TOM | TOM | | H02 | C | 4464461 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/29/2012 | 5 YR 3-08-OTIS PHONE DOES NOT DISCONNECT AFTER CALL (Receipt #1065669) | TOM | TOM | | H01 | C | 4351745 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/17/2012 | 5 YR 3-08--PHONE IN CAR DOES NOT DISCONNECT | TOM | TOM | | H02 | C | 4265027 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/12/2011 | 5 YR 3-08--OTIS (Receipt #989100) | TOM | TOM | | H01 | C | 4183938 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/26/2011 | 5YR 3-08--OTIS | TOM | TOM | | H02 | C | 4106382 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/12/2010 | 5 yr 3-08 otis (Receipt #923302) | TOM | TOM | | H01 | C | 4017501 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/29/2010 | 5 yr 3-08--otis | TOM | TOM | | H02 | C | 3938665 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/31/2009 | 5 YR 3-08 OTIS (Receipt #869823) | TOM | TOM | | H01 | C | 3866072 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/29/2009 | 5 YR 3-08--OTIS | TOM | TOM | | H02 | C | 3796699 |
PENROSE HOSPITAL FACILITIES | H06 | C | 01/01/2009 | WITNESSED | JOHNW | JOHNW | | H06 | C | 4222160 |