PENROSE HOSPITAL FACILITIES | HE16 | C | 05/06/2024 | ELEVATOR WAS SHUT DOWN BY OTIS AT TIME OF WITNESS TEST INSPECTION. GOVERNOR OVERSPEED SWITCH WAS BROKEN AND REPAIRS ARE NEEDED TO BE MADE PRIOR TO TESTING. PLEASE CONTACT PPRBD WHEN READY FOR WITNESS TEST TO BE PERFORMED AND PRIOR TO RETURNING ELEVATOR TO PUBLIC USE. | DUSTINS | DUSTINS | | HE16 | C | 8075423 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/25/2024 | 5 YEAR 1/19 -- ANNUAL 1/23 -- OTIS & SERVICE -- / 5 YEAR WITNESS TESTING SCHEDULED WITH OTIS FOR WEEK OF 2/12/24 - 2/16/24 (Receipt #2027927) | DUSTINS | DUSTINS | | H02 | C | 7977571 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/25/2023 | 5YR 01/2019 - ANNUAL 01/2023 - OTIS AND SERVICE -/ MAIN DRIVE SHEAVE IS INDICATING METAL ON METAL GRINDING AND NEEDS TO BE DIAGNOSED BEFORE MECHANICAL FAILURE (SECOND NOTICE) -/ HOLD PERMIT TO OPERATE UNTIL THE DIAGNOSIS HAS BEEN PROVIDED TO PPRBD (Receipt #1972495) (Elevator has been shutdown by Otis due to bearing problems needing addressed RV) | MIKEM | MIKEM | | H01 | C | 7807424 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/27/2023 | HO2 -- ANNUAL 1/23 -- OTIS & SERVICE | BENH | BENH | | H02 | C | 7646848 |
PENROSE HOSPITAL FACILITIES | HE16 | C | 09/21/2022 | RE-INSPECTION RESULTED IN THE ELEVATOR BEING DOWN FOR REPAIRS ON THE MAIN DRIVE -- BRIAN FROM OTIS STATES THAT THEY WILL BE REPLACING THE MAIN DRIVE MOTOR/SHEAVE IN THE NEAR FUTURE -- FOLLOW UP SCHEDULED FOR 30 DAYS | MIKEM | MIKEM | | HE16 | C | 7524422 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/20/2022 | 5YR 01/2019 -- ANNUAL 04/2022 -- OTIS AND SERVICE --/ OVERHEAD SHEAVE BEARING IS GOING BAD (NOISY) AND SHALL BE REMEDIED (Receipt #1884774) | MIKEM | MIKEM | | H01 | C | 7453863 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/28/2022 | 5 YEAR 1/19, CAT1 3/21, OTIS H02 cat 1 4/22 | ERIC | ERIC | | H02 | C | 7254250 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/13/2021 | 5YR -- 1/19 -- CAT1 -- 3/21 -- OTIS AND SERVICE. 5TH FLOOR FAST HOISTWAY DOOR GIB NEEDS ATTENTION - (ITEMS FROM PREVIOUS INSPECTION HAVE BEEN ADDRESSED) (Receipt #1789377) | ROBERTV | ROBERTV | | H01 | C | 7034174 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/12/2021 | H02 -- 5YR -- 1/19 -- CAT1 3/20 -- OTIS AND SERVICE. OTIS WILL HAVE ITEMS PREVIOUSLY NOTED ADDRESSED BY 3/1/2021, FOLLOW UP SCHEDULED FOR THAT TIME (Items have been addressed per Otis RV) CAT 1 3/21 | ROBERTV | ROBERTV | | H02 | C | 6833841 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/28/2020 | 5YR -- 1/19 -- ANNUAL 3/20 -- OTIS. BELT MONITOR IS FLASHING ABNORMALLY FOR BELT #3. DRIVE MACHINE OR SHEAVES ARE MAKING METEL ON METAL NOISE WHILE RUNNING CONTRACT SPEED - (NEEDS DIAGNOSED). NEED TO MONITOR ROUGED SUSPENSION BELTS........ FOLLOW UP SCHEDULED WITHIN 60 DAYS (Receipt #1699711) | ROBERTV | ROBERTV | | H01 | C | 6653064 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/31/2020 | H02 -- 5YR -- 1/19 -- OTIS W/ TKE SERVICE. cat 1 3/20 | ROBERTV | ROBERTV | | H02 | C | 6470613 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/30/2019 | 5YR -- 1/19 -- OTIS W/ TKE SERVICE. (Receipt #1618267 from 07/30/2019) | ROBERTV | ROBERTV | | H01 | C | 6281879 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/08/2019 | WITNESSED 1/19 | ERIC | ERIC | | H02 | C | 6071942 |
PENROSE HOSPITAL FACILITIES | H06 | C | 01/08/2019 | WITNESSED 5 YEAR SAFETY TEST. COMPENSATION CHAIN COVERING IS FALLING APART AND NEEDS TO BE REPAIRED/REPLACED AND BELT MONITOR IS NOT FUNCTIONING AS REQUIRED (Receipt #1568042) | ERIC | ERIC | | H06 | C | 6071935 |
PENROSE HOSPITAL FACILITIES | HE16 | C | 10/11/2018 | DID PARTIAL WITNESS TESTING W/ TKE - NEED TO FINISH TESTS AS SHOWN IN IMAGES | ROBERTV | ROBERTV | | HE16 | C | 6016984 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/26/2018 | 5YR -- 10/13 -- ANNUAL 4/17 -- OTIS W/ TKE SERVICE. TRAVELING CABLE SHEATHING IS CRACKED VIEWING FROM LOWEST LANDING. 2ND FLOOR FAST HOISTWAY DOOR MISSING ONE SAFETY RETAINER AT LANDING SILL. 5 YR WITNESS TESTING DUE 10/2018 (Receipt #1521007) | ROBERTV | ROBERTV | | H01 | C | 5914644 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/17/2018 | 5YR 8--13--OTIS ANNUAL IS 7--17--TKE SERVICE AND LOCKBOX--MONITOR IS STILL NOT WORKING TO BE REPLACED WITH IN THE NEXT MONTH | JOHNW | JOHNW | | H02 | C | 5739336 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/31/2017 | 5 YEAR 8/13, ANNUAL 7/17 OTIS. TKE SERVICE AND LOCKBOX. NEED TO COMPLETE BELT MONITOR INSTALLATION (Receipt #1442953) | ERIC | ERIC | | H01 | C | 5580505 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/23/2017 | HO2 --BELT MONITORS WILL BE ADDRESSED BY MIKE DUKES THIS MONTH | JOHNW | JOHNW | | H02 | C | 5396165 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/29/2016 | 5YR -- 8/13 -- ANNUAL 3/16 -- OTIS AND LOCKBOX. NEED TO CORRECT BELT MONITOR FAULT ISSUE (3RD NOTICE), MISSING HOISTWAY FASCIA DOOR RESTRICTOR FLAGS. (Receipt #1345806 from 08/01/2016) | ROBERTV | ROBERTV | | H01 | C | 5258164 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/19/2016 | 5 YEAR 8/13 OTIS. STILL NEED TO CORRECT BELT MONITOR FAULT ISSUE FROM PREVIOUS INSPECTION AND NEED GEN2 SPECIFIC MAINTENANCE CONTROL PROGRAM | ERIC | ERIC | | H02 | C | 5117823 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/24/2015 | 5 YEAR 8/13 OTIS. NEED GENII SPECIFIC MCP, NEED ANNUAL TESTS AND TEST TAGS, ROPE MONITOR FLASHING 15 "STANDBY, LEARN RUN REQUIRED" (Receipt #1276856) | ERIC | ERIC | | H01 | C | 5001624 |
PENROSE HOSPITAL FACILITIES | H02 | C | 02/09/2015 | 5YR 8-13 OTIS | TOM | TOM | | H02 | C | 4908740 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/09/2014 | 5 YEAR 8/13 OTIS (Receipt #1206376) | ERIC | ERIC | | H01 | C | 4773989 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/14/2014 | H02 | ERIC | ERIC | | H02 | C | 4671385 |
PENROSE HOSPITAL FACILITIES | H06 | C | 08/20/2013 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1149710) | ERIC | ERIC | | H06 | C | 4590690 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/30/2013 | HO6 TO BE COMPLETED IN AUGUST 2013 (Receipt #1145063) | ERIC | ERIC | | H01 | C | 4573934 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/15/2013 | 5YR 3-08--OTIS | TOM | TOM | | H02 | C | 4464455 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/29/2012 | 5 YR 3-08--OTIS (Receipt #1065674) | TOM | TOM | | H01 | C | 4351750 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/19/2012 | 5YR 3-08--OTIS | TOM | TOM | | H02 | C | 4265039 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/12/2011 | 5 YR 3-08--OTIS (Receipt #989107) | TOM | TOM | | H01 | C | 4183956 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/26/2011 | 5YR3-08--OTIS | TOM | TOM | | H02 | C | 4106388 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/12/2010 | 5 yr 6-08 otis (Receipt #923305) | TOM | TOM | | H01 | C | 4017504 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/29/2010 | 5 yr 3-08--otis | TOM | TOM | | H02 | C | 3938657 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/31/2009 | 5 YR 3-08 OTIS (Receipt #869816) | TOM | TOM | | H01 | C | 3866065 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/29/2009 | 5 YR 3-08--OTIS | TOM | TOM | | H02 | C | 3796689 |
PENROSE HOSPITAL FACILITIES | H06 | C | 01/01/2009 | WITNESSED | JOHNW | JOHNW | | H06 | C | 4222157 |