PENROSE HOSPITAL FACILITIES | H06 | C | 02/16/2024 | WITNESSED 5 YEAR TEST W/ OTIS -- STILL NEED GENERATOR TESTING COMPLETED (Receipt #2034592) | BENH | BENH | | H06 | C | 7998055 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/25/2024 | 5 YEAR 1/19 -- ANNUAL 1/23 -- OTIS & SERVICE -- / 5 YEAR WITNESS TESTING SCHEDULED WITH OTIS FOR WEEK OF 2/12/24 - 2/16/24 (Receipt #2027928) | DUSTINS | DUSTINS | | H02 | C | 7977573 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/25/2023 | 5YR 01/2019 - ANNUAL 01/2023 - OTIS AND SERVICE -/ EMERGENCY LIGHT AND BELL ARE NON-FUNCTIONAL WITHOUT THE 110v CAB CIRCUIT -/ MISSING IN BETWEEN FLOOR RESTRICTION ON FLOORS 5 AND 6 -/ MISSING A DOOR RETAINER ON THE HOISTWAY FAST DOOR ON FLOOR 4 -/ PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL ITEM/S ARE ADDRESSED (Receipt #1972487) | MIKEM | MIKEM | | H01 | C | 7807388 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/27/2023 | HO2 -- ANNUAL 1/23 -- OTIS & SERVICE | BENH | BENH | | H02 | C | 7646850 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/20/2022 | 5YR 01/2019 -- ANNUAL 04/2022 -- OTIS AND SERVICE -- (NOTE: MONITOR GOVERNOR TAIL SHEAVE AND ROPE) (Receipt #1884768) | MIKEM | MIKEM | | H01 | C | 7453829 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/28/2022 | 5 YEAR 1/19, CAT1 3/21, OTIS H02 cat 1 4/22 | ERIC | ERIC | | H02 | C | 7254254 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/13/2021 | 5YR -- 1/19 -- CAT1 -- 3/21 -- OTIS AND SERVICE. 1ST FLOOR FAST HOISTWAY DOOR GIB IS WORN (Receipt #1789380) | ROBERTV | ROBERTV | | H01 | C | 7034181 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/11/2021 | H02 -- 5YR -- 1/19 -- CAT1 -- 3/20 -- OTIS AND SERVICE cat 1 3/21 | ROBERTV | ROBERTV | | H02 | C | 6831540 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/28/2020 | 5YR -- 1/19 -- ANNUAL 3/20 -- OTIS. (NO VISIBLE CODE ISSUES) (Receipt #1699713) | ROBERTV | ROBERTV | | H01 | C | 6653077 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/31/2020 | H02 -- 5YR -- 1/19 -- OTIS W/ TKE SERVICE. cat 1 3/20 | ROBERTV | ROBERTV | | H02 | C | 6470614 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/30/2019 | 5YR -- 1/19 -- OTIS W/ TKE SERVICE. (Receipt #1618268 from 07/30/2019) | ROBERTV | ROBERTV | | H01 | C | 6281882 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/08/2019 | WITNESSED 1/19 | ERIC | ERIC | | H02 | C | 6071961 |
PENROSE HOSPITAL FACILITIES | H06 | C | 01/07/2019 | WITNESSED 5YR SAFETY TEST W/ TKE--OTIS W/ TKE SERVICE (Receipt #1567603) | CALE | CALE | | H06 | C | 6070114 |
PENROSE HOSPITAL FACILITIES | HE16 | C | 10/11/2018 | DID PARTIAL WITNESS TESTING W/ TKE - NEED TO FINISH TESTS AS SHOWN IN IMAGES | ROBERTV | ROBERTV | | HE16 | C | 6017022 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/26/2018 | 5YR -- 10/13 -- ANNUAL 4/17 -- OTIS W/ TKE SERVICE. MISSING LOWER HOISTWAY DOOR RESTRICTOR FLAG ON 5TH FLOOR, 5 YR WITNESS TESTING DUE 10/2018 | ROBERTV | ROBERTV | | H01 | C | 5914743 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/08/2018 | 5 YEAR 8/13, ANNUAL 4/17 OTIS. TKE SERVICE AND LOCKBOX,HO2 | ERIC | ERIC | | H02 | C | 5731412 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/31/2017 | 5 YEAR 8/13, ANNUAL 4/17 OTIS. TKE SERVICE AND LOCKBOX. MISSING DOOR RESTRICTOR FLAG AT 5TH FLOOR (Receipt #1442952) | ERIC | ERIC | | H01 | C | 5580502 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/23/2017 | HO2--BELT MONITORS WILL BE ADDRESSED BY MIKE DUKES THIS MONTH | JOHNW | JOHNW | | H02 | C | 5396160 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/29/2016 | 5YR -- 8/13 -- ANNUAL 3/16 -- OTIS AND LOCKBOX. NEED TO CORRECT BELT MONITOR FAULT ISSUE (3RD NOTICE), MISSING DOOR RESTRICTOR FLAG ON 5TH FLOOR HOISTWAY DOOR, MISSING HOISTWAY FASCIA DOOR RESTRICTOR FLAGS ON MULTIPLE FLOORS (Receipt #1345811) | ROBERTV | ROBERTV | | H01 | C | 5258167 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/19/2016 | 5 YEAR 8/13 OTIS. STILL NEED TO CORRECT BELT MONITOR FAULT ISSUE FROM PREVIOUS INSPECTION AND NEED GEN2 SPECIFIC MAINTENANCE CONTROL PROGRAM | ERIC | ERIC | | H02 | C | 5117824 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/24/2015 | 5 YEAR 8/13 OTIS. NEED GENII SPECIFIC MCP, NEED ANNUAL TESTS AND TEST TAGS, ROPE MONITOR FLASHING 15 "STANDBY, LEARN RUN REQUIRED" (Receipt #1276860) | ERIC | ERIC | | H01 | C | 5001637 |
PENROSE HOSPITAL FACILITIES | H02 | C | 02/09/2015 | 5YR 8-13-OTIS | TOM | TOM | | H02 | C | 4908741 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/09/2014 | 5 YEAR 8/13 OTIS (Receipt #1206377) | ERIC | ERIC | | H01 | C | 4773990 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/14/2014 | H02 | ERIC | ERIC | | H02 | C | 4671386 |
PENROSE HOSPITAL FACILITIES | H06 | C | 08/20/2013 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1149709) | ERIC | ERIC | | H06 | C | 4590689 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/30/2013 | HO6 TO BE COMPLETED IN AUGUST 2013 (Receipt #1145064) | ERIC | ERIC | | H01 | C | 4573935 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/15/2013 | 5YR 3-08--OTIS | TOM | TOM | | H02 | C | 4464454 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/29/2012 | 5 YR 3-08--OTIS (Receipt #1065675) | TOM | TOM | | H01 | C | 4351751 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/19/2012 | 5YR 3-08--OTIS | TOM | TOM | | H02 | C | 4265042 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/13/2011 | 5 YR 3-08--OTIS (Receipt #989109) | TOM | TOM | | H01 | C | 4183958 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/26/2011 | 5YR 3-08--OTIS | TOM | TOM | | H02 | C | 4106391 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/12/2010 | 5 yr 6-08 otis (Receipt #923306) | TOM | TOM | | H01 | C | 4017505 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/29/2010 | 5 yr 3-08--otis | TOM | TOM | | H02 | C | 3938658 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/31/2009 | 5 YR 3-08 OTIS (Receipt #869817) | TOM | TOM | | H01 | C | 3866066 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/29/2009 | 5 YR 3-08--OTIS | TOM | TOM | | H02 | C | 3796690 |
PENROSE HOSPITAL FACILITIES | H06 | C | 01/01/2009 | WITNESSED | JOHNW | JOHNW | | H06 | C | 4222156 |