PENROSE HOSPITAL FACILITIES | H06 | C | 02/16/2024 | WITNESSED 5 YEAR TEST W/ OTIS -- MACHINE ROOM CLEANLINESS TO BE ADDRESSED -- PHASE 1 FIREFIGHTERS OPERATION IS NOT WORKING PROPERLY IT RECALLS TO THE FLOOR ABOVE THE KEYSWITCH FLOOR AND NOT ALL THE WAY TO THE BOTTOM FLOOR WHERE THE KEY SWITCH IS LOCATED -- NEED GENERATOR TESTING COMPLETED (Receipt #2034583) | BENH | BENH | | H06 | C | 7998040 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/25/2024 | 5 YEAR 1/19 -- ANNUAL 1/23 -- OTIS & SERVICE -- / 5 YEAR WITNESS TESTING SCHEDULED WITH OTIS FOR WEEK OF 2/12/24 - 2/16/24 (Receipt #2027929) | DUSTINS | DUSTINS | | H02 | C | 7977574 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/25/2023 | 5YR 01/2019 - ANNUAL 01/2023 - OTIS AND SERVICE -/ COUNTERWEIGHT ROLLERS ARE IN NEED OF ADJUSTMENTS -/ PPRBD NOTE: ELEVATOR FAULTED OUT AFTER INSPECTION (Receipt #1972471) | MIKEM | MIKEM | | H01 | C | 7807337 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/27/2023 | HO2 -- ANNUAL 1/23 -- OTIS & SERVICE -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7646854 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/20/2022 | 5YR 01/2019 -- ANNUAL 04/2022 -- OTIS AND SERVICE --/ COUNTERWEIGHT GUIDE ROLLERS ARE NOISY WHILE RIDING THE ELEVATOR AND SHALL BE DIAGNOSED (Receipt #1884742) | MIKEM | MIKEM | | H01 | C | 7453762 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/28/2022 | 5 YEAR 1/19, CAT1 3/21, OTIS H02 cat 1 4/22 | ERIC | ERIC | | H02 | C | 7254255 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/13/2021 | 5YR -- 1/19 -- CAT1 -- 3/21 -- OTIS AND SERVICE. 6TH FLOOR FAST HOISTWAY DOOR IS BENT, HAS MISSING SAFETY RETAINER AND SIGHT GUARD NEEDS SECURED. 2ND FLOOR FAST HOISTWAY DOOR IS MISSING SAFETY RETAINER. (Receipt #1789383) | ROBERTV | ROBERTV | | H01 | C | 7034193 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/11/2021 | H02 -- 5YR -- 1/19 -- CAT1 -- 3/20 -- OTIS AND SERVICE cat 1 3/21 | ROBERTV | ROBERTV | | H02 | C | 6831547 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/28/2020 | 5YR -- 1/19 -- ANNUAL 3/20 -- OTIS. (NO VISIBLE CODE ISSUES) (Receipt #1699717) | ROBERTV | ROBERTV | | H01 | C | 6653085 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/31/2020 | H02 -- 5YR -- 1/19 -- OTIS W/ TKE SERVICE. cat 1 3/20 | ROBERTV | ROBERTV | | H02 | C | 6470617 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/30/2019 | 5YR -- 1/19 -- OTIS W/ TKE SERVICE. OUT OF SERVICE AT TIME OF INSPECTION (Receipt #1618270 from 07/30/2019) | ROBERTV | ROBERTV | | H01 | C | 6281884 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/08/2019 | WITNESSED 1/19 | ERIC | ERIC | | H02 | C | 6071956 |
PENROSE HOSPITAL FACILITIES | H06 | C | 01/07/2019 | WITNESSED 5YR SAFETY TEST W/ TKE--OTIS W/ TKE SERVICE (Receipt #1567604) | CALE | CALE | | H06 | C | 6070139 |
PENROSE HOSPITAL FACILITIES | HE16 | C | 10/11/2018 | DID PARTIAL WITNESS TESTING W/ TKE - NEED TO FINISH TESTS AS SHOWN IN IMAGES | ROBERTV | ROBERTV | | HE16 | C | 6017026 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/26/2018 | 5YR -- 10/13 -- ANNUAL 4/17 -- OTIS W/ TKE SERVICE. 5 YR WITNESS TESTING DUE 10/2018 | ROBERTV | ROBERTV | | H01 | C | 5914766 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/08/2018 | 5 YEAR 8/13, ANNUAL 4/17 OTIS. TKE SERVICE AND LOCKBOX,HO2 | ERIC | ERIC | | H02 | C | 5731414 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/31/2017 | 5 YEAR 8/13, ANNUAL 4/17 OTIS. TKE SERVICE AND LOCKBOX (Receipt #1442950) | ERIC | ERIC | | H01 | C | 5580497 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/23/2017 | HO2 --BELT MONITORS WILL BE ADDRESSED BY MIKE DUKES THIS MONTH | JOHNW | JOHNW | | H02 | C | 5396168 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/29/2016 | 5YR -- 8/13 -- ANNUAL 3/16 -- OTIS AND LOCKBOX. NEED TO CORRECT BELT MONITOR FAULT ISSUE (3RD NOTICE) (Receipt #1345824 from 08/01/2016) | ROBERTV | ROBERTV | | H01 | C | 5258188 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/19/2016 | 5 YEAR 8/13 OTIS. STILL NEED TO CORRECT BELT MONITOR FAULT ISSUE FROM PREVIOUS INSPECTION AND NEED GEN2 SPECIFIC MAINTENANCE CONTROL PROGRAM | ERIC | ERIC | | H02 | C | 5117825 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/24/2015 | 5 YEAR 8/13 OTIS. NEED GENII SPECIFIC MCP, NEED ANNUAL TESTS AND TEST TAGS, ROPE MONITOR FLASHING 10 "REPLACE BOARD, USE EXISTING EEPROM" (Receipt #1276862) | ERIC | ERIC | | H01 | C | 5001642 |
PENROSE HOSPITAL FACILITIES | H02 | C | 02/09/2015 | 5YR 8-13 OTIS | TOM | TOM | | H02 | C | 4908742 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/09/2014 | 5 YEAR 8/13 OTIS (Receipt #1206379) | ERIC | ERIC | | H01 | C | 4773992 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/14/2014 | H02 | ERIC | ERIC | | H02 | C | 4671390 |
PENROSE HOSPITAL FACILITIES | H06 | C | 08/20/2013 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1149705) | ERIC | ERIC | | H06 | C | 4590674 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/30/2013 | HO6 TO BE COMPLETED IN AUGUST 2013 (Receipt #1145065) | ERIC | ERIC | | H01 | C | 4573936 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/15/2013 | 5YR 3-08--OTIS--HALL CALL STATION LOOSE IN WALL AT FIRE LANDING | TOM | TOM | | H02 | C | 4464453 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/29/2012 | 5 YR 3-08--OTIS (Receipt #1065676) | TOM | TOM | | H01 | C | 4351752 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/19/2012 | 5YR 3-08--OTIS | TOM | TOM | | H02 | C | 4265043 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/13/2011 | 5 YR 3-08--OTIS (Receipt #989110) | TOM | TOM | | H01 | C | 4183959 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/26/2011 | 5YR3-08--OTIS | TOM | TOM | | H02 | C | 4106394 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/12/2010 | 5 yr 6-08 otis (Receipt #923307) | TOM | TOM | | H01 | C | 4017507 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/29/2010 | 5 yr 3-08--otis | TOM | TOM | | H02 | C | 3938660 |
PENROSE HOSPITAL FACILITIES | H01 | C | 07/31/2009 | 5 YR 3-08 OTIS (Receipt #869818) | TOM | TOM | | H01 | C | 3866067 |
PENROSE HOSPITAL FACILITIES | H02 | C | 01/29/2009 | 5 YR 3-08--OTIS | TOM | TOM | | H02 | C | 3796693 |
PENROSE HOSPITAL FACILITIES | H06 | C | 01/01/2009 | WITNESSED | JOHNW | JOHNW | | H06 | C | 4222155 |