PCL CONSTRUCTION SERVICES, INC | B= | C | 01/22/2009 | FIRE FINAL 1/22/09 RCE | MARY | MARY | | B= | C | 3793843 |
PCL CONSTRUCTION SERVICES, INC | B= | P | 01/21/2009 | NEED FIRE DEPARTMENT FINAL APPROVAL/ALL ELSE OK | BERTW | BERTW | | B= | P | 3793198 |
PCL CONSTRUCTION SERVICES, INC | BSP | P | 01/09/2009 | ABOVE GRID FIRECAULKING OK | BERTW | BERTW | | BSP | P | 3789582 |
PCL CONSTRUCTION SERVICES, INC | BFR | P | 12/15/2008 | WALLS OK/REMOVE OLD SHEETROCKING @ FIRE WALL ABOVE NEW CORRIDOOR DOOR FRAMING AND REROCK-SHEETROCK NEEDED BEHIND MED GAS STATION ,THIS IS PART OF THE RATED WALL SYSTEM -SEAL ALL PENETRATIONS AND FIRE CAULK WALLS TO UNDERSIDE OF DECK PENETRATIONS-NEED FIRE CAULKING INSPECTION | BERTW | BERTW | | BFR | P | 3781754 |
E LIGHT ELECTRIC SERVICES, INC | E= | C | 01/16/2009 | | BRET | BRET | | E= | C | 3791781 |
E LIGHT ELECTRIC SERVICES, INC | EP | C | 01/16/2009 | 200 AMP DISCONNECT AND TRANSFORMER OK | BRET | BRET | | EP | C | 3791779 |
E LIGHT ELECTRIC SERVICES, INC | ES | P | 01/15/2009 | THIS WAS A PARTIAL INSPECTION FOR ONE 200 AMP 4W SERVICE FOR THE FLUOROSCOPY LAB I INSPECTED THE SERVICE FROM THE MDP TO THE SHUNT TRIP. CORRECTIONS INCLUDE CHANGING THE BOND WIRE FROM #6 TO #4 INSIDE THE 200 KVA TRANSFORMER. AT MDP INSTALL CORRECT COVER PLATE WHERE NEW BUCKET SWITCH WAS INSTALLED. STILL NEED TO INSPECT EVERY THING DOWNSTREAM FROM SHUNT TRIP AND NEED TO SEE TRANSFORMER FOR SHUNT TRIP. NEED TO FIELD TEST EPO SWITCHES. | JOSEPH | JOSEPH | | ES | P | 3791248 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 01/09/2009 | DROP CEILING FLUOROSCOPY | MATTHEW | MATTHEW | | ER | P | 3789364 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 12/15/2008 | WALLS AND BATH HARDLID | BRET | BRET | | ER | P | 3781746 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 01/21/2009 | RECEIVED BALANCE REPORT | JON | JON | | H= | C | 3792905 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 01/15/2009 | NEED BALANCE REPORT | JON | JON | | H= | P | 3791477 |
HEATING & PLUMBING ENGINEERS, INC | H= | R | 01/14/2009 | NO CONTACT WITH CALL AHEAD NUMBER NEEDS RESCHEDULED. | JON | JON | | H= | R | 3790848 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 01/08/2009 | OK FOR WRAP. CALL BEFORE COVER TO SEE MEDIUM PRESSURE TIE IN AND HOT WATER PIPING TO COIL. | JON | JON | | HD | P | 3789034 |
HEATING & PLUMBING ENGINEERS, INC | P= | C | 01/13/2009 | 1-SK | LYNNIE | LYNNIE | | P= | C | 3790282 |
HEATING & PLUMBING ENGINEERS, INC | PB | C | 12/16/2008 | DO NOT KNOW WHAT THE WATER CONNECTED APPLIANCE IS ON PERMIT?--USE IT OR LOOSE IT | LYNNIE | LYNNIE | | PB | C | 3782297 |