SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | C | 08/31/2012 | | BLAKE | BLAKE | | B= | C | 4373491 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | P | 05/29/2012 | weld certs and RMG observation reports for mezzanine structural connections on file ok | BERTW | BERTW | | BSP | P | 4317632 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | P | 04/24/2012 | RBD will need a letter of structural observation for this mezzanine framing inspection to include bolting,welding and general overall conformance to approved plans | BERTW | BERTW | | BSP | P | 4301251 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | P | 02/22/2012 | new location mezzanine support footings ok/letter on file for structural slab in lieu of footings in electric equipment room/pending stamped open hole report | BERTW | BERTW | | BSP | P | 4274477 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | R | 02/21/2012 | canceled by dispatch over E-mail | BERTW | BERTW | | BSP | R | 4273450 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | R | 02/14/2012 | CANCELED BY DISPATCHER E-MAIL | BERTW | BERTW | | BSP | R | 4271318 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | T | 02/06/2012 | PAID (REC#1026514) PLAN SPLICE FEE: $50 by: MICHAEL for Construction: Add mezannine structure to shell | MICHAELA | MICHAELA | | BSP | T | 4268180 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 11/17/2011 | tco extended until 6/1/12 -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 4237433 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BE | L | 02/16/2011 | Renewed at 2/16/2011 3:13:03 PM | MINDY | MINDY | | BE | L | 4112123 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 07/15/2010 | per pepper tco ok until jan 1 2011 -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 4010162 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 05/20/2010 | Temp CO: last TCO until new agreement ( Expires: 6/19/2010 12:00:00 AM) | JIMP | JIMP | | B= | P | 3984016 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 04/27/2010 | still need fire sprinkler installed in north unit | BERTW | BERTW | | B= | P | 3973025 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BIN | C | 04/27/2010 | INSULATION WILL BE INSTALLED @ INTERIOR FINSH PER NOTES | BERTW | BERTW | | BIN | C | 3973023 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | C | 04/27/2010 | ENGINEERING ON FILE FOR RAFTER REPAIRS AND ENGINEERING OBSERVATION REPORT ON FILE | BERTW | BERTW | | BFR | C | 3973021 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 03/23/2010 | tco ok 30 more days -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 3957177 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 02/22/2010 | tco ok 30 more days -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 3946589 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 02/10/2010 | FIRE DAMAGE REPAIR TO ROOF SYSTEM IN PROGRESS-CONTRACTOR WILL HAVE RMG ENGINEERING WHO DID THE DESIGN DO THE INSPECTION AND PROVIDE ENGINEERING OBSERVATION LETTER AND DESIGN FOR NEXT INSPECTION | BERTW | BERTW | | BFR | P | 3942687 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 01/21/2010 | tco ok 30 more days -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 3935041 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 12/21/2009 | tco ok 30 more days -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 3925150 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 11/20/2009 | tco ok 30 more days -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 3914670 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 10/21/2009 | tco ok 30 more days | BLAKE | BLAKE | | B= | P | 3901207 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BIN | P | 09/24/2009 | ROOF OK UNIT #120 OK | BERTW | BERTW | | BIN | P | 3889547 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 09/22/2009 | health dept final complete - see below | BOB | BOB | | B= | P | 3888461 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 09/21/2009 | Additional Inspections Required: External Agency Inspection HD= by HEALTHDEPT is not Completed yet. tco ok 30 more days -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 3887400 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BIN | P | 09/09/2009 | SUITE #100 and #130 ROOF OK | BERTW | BERTW | | BIN | P | 3882777 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 08/21/2009 | tco ok 30 more days | BLAKE | BLAKE | | B= | P | 3874660 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 07/21/2009 | extend tco 30 more days | BLAKE | BLAKE | | B= | P | 3860821 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 06/19/2009 | extend tco 30 more days | BLAKE | BLAKE | | B= | P | 3848287 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | P | 05/27/2009 | tco ok for shell per Jim pepper pending completion of sprk system and insulation, sprk and insulation will be completed as tenant spaces are completed | BLAKE | BLAKE | | B= | P | 3838961 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | B= | R | 05/01/2009 | NEED COMPLETED INSULATION-FRAMING INSPECTION/POST ADDRESS ON BUILDING/FIRE DEPARTMENT APPROVAL REQUIRED/COMPLETE FIRE SPRINKLERS/ 5-5-09 ADDRESS IS NOW ON BUILDING | BERTW | BERTW | | B= | R | 3830291 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 05/01/2009 | NEED RAFTERS THAT ARE FIRE DAMAGED REPAIRED/RMG ENGINEERING LETTER ON FILE FOR AREAS TO BE REPAIRED | BERTW | BERTW | | BFR | P | 3830286 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BIN | R | 05/01/2009 | NEED INSULATION IN RAFTERS | BERTW | BERTW | | BIN | R | 3830283 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 04/24/2009 | ENGINEERING ON FILE FOR ROOF TOP UNIT FRAMING/FIRE DAMAGE REPAIR NOTES FROM RMG ON FILE | BERTW | BERTW | | BFR | P | 3827772 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | T | 04/23/2009 | PAID (REC#855467) ADDITIONAL PLAN REVIEW TIME: $50 From: MICHAEL Splice change to insulation intall schedule - will install with tenant finish | MICHAELA | MICHAELA | | BSP | T | 3826836 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 04/20/2009 | STILL NEED TO ADDRESS FIRE DAMAGE REPAIRS/ | BERTW | BERTW | | BFR | P | 3825824 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 04/07/2009 | DETAIL FOR ROOF SCREEN WALL ATTACHMENT ON FILE/ATTACHMENTS OK | BERTW | BERTW | | BFR | P | 3821221 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 04/06/2009 | NO SUPER ON SITE | BERTW | BERTW | | BFR | P | 3820701 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 04/02/2009 | NEED DETAIL FOR SCREEN WALL ATTACHMENT/WENT OVER ROOF INSULATION REQUIREMENTS/NEED APPROVED IECC COMPLIANCE CERT | BERTW | BERTW | | BFR | P | 3819695 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | T | 03/31/2009 | PAID (REC#852275) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY slice two pages to add heater | SHELBY | SHELBY | | BSP | T | 3818591 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | T | 03/31/2009 | PAID (REC#852277) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELLEY changed entry and added electrical room, clarified removal of stair | SHELLEY | SHELLEY | | BSP | T | 3818130 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | T | 03/31/2009 | PAID (REC#852278) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN new splice page changed water entry room | TCRIPPEN | TCRIPPEN | | BSP | T | 3818119 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | T | 03/31/2009 | PAID (REC#852280) ADDITIONAL PLAN REVIEW TIME: $50 From: DALEH splice for relocated gas meter | DALEH | DALEH | | BSP | T | 3818114 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 03/23/2009 | RTU:S FRAMING OK/FIRE DAMAGE NEEDS REPAIRS PER JOB SUPER-REVISE PLANS TO SHOW ELECTRIC ROOM FRAMING AND FIRE SPRINKLER RISER ROOM NEEDS TO BE ON PLANS/SCREEN WALLS ON ROOF TOP NEED REVISED ATTACHMENT DETAIL/STILL NEED CONFIRMATION OF FIRE SPRINKLER SYSTEM NOT REQUIRED @ CORE SHELL FINAL INSPECTION-SPOKE WITH MONICA FROM CONTRACTOR COMPANY ABOUT THIS | BERTW | BERTW | | BFR | P | 3815965 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 03/19/2009 | NEED TO INSPECT ROOF RSFTERS AND RTU HEADOUTS/NEED ENGINEERING FOR PREVIOUS LISTED ITEMS | BERTW | BERTW | | BFR | P | 3815007 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 03/18/2009 | PROVIDE ENGINEERING FOR FIRE DAMAGED RAFTERS AND COLUMNS/SOME COLUMNS NOT UNDER BEAM SPLICES AND STRAPPING OF BEAMS TO COLUMNS NEED ENGINEERING DETAILS | BERTW | BERTW | | BFR | P | 3814458 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFN | C | 03/17/2009 | ALL PAPERWORK IS ON FILE FROM PREVIOUS NOTES | BERTW | BERTW | | BFN | C | 3813980 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFT | C | 03/09/2009 | NEED COMPLETED FOUNDATION INSPECTION/OPEN HOLE AND ENGINEERING DETAILS | BERTW | BERTW | | BFT | C | 3810770 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 03/05/2009 | ALL EXCEPT SCREEN WALL FRAMING, STEEL FOR SCREEN WALL OK ABOVE CARMICHAELS | RICK | RICK | | BFR | P | 3809064 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFT | P | 02/23/2009 | NEED STAMPED OPEN HOLE REPORT AND DETAIL FOR PILASTERS AND GROUT @ SUPPORTING COLUMNS | BERTW | BERTW | | BFT | P | 3805226 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFR | P | 02/20/2009 | WENT OVER FRAMING ITEMS WITH DAVE THE FRAMING CONTRACTOR/FRAME INSPECTIONS WIIL START NEXT WEEK | BERTW | BERTW | | BFR | P | 3804629 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFN | P | 02/20/2009 | WENT OVER ENGINEERING ITEMS NEEDED TO COMPLETE THIS INSPECTION/MATT THE JOB SITE SUPER WILL CALL THIS NEXT WEEK | BERTW | BERTW | | BFN | P | 3804627 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFT | P | 02/17/2009 | NEED ENGINEERING DETAIL FOR LAST FOOTING @ NORTHWEST COLUMN WHERE GROUT IS THICKER THEN SPECIFIED DUE TO CUTTING OFF MORE THEN 12" OFF BOTTOM OF ROTTED COLUMN | BERTW | BERTW | | BFT | P | 3803025 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFT | P | 01/27/2009 | ALL PADS OK/NEED OPEN HOLE AND DETAILS FOR GROUT UNDER POSTS | BERTW | BERTW | | BFT | P | 3795554 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFT | P | 01/21/2009 | WENT OVER PAD SIZING WITH CONCRETE COMPANY SUPER | BERTW | BERTW | | BFT | P | 3793394 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFN | P | 01/20/2009 | PADS OK 6 LINE THRU 10 / CONTRACTOR IS CUTTING BOTTOMS SECTIONS OFF OF ROTTED COLUMNS PER PLANS | BERTW | BERTW | | BFN | P | 3792721 |
HARMON - BONDED PLUMBING & HEATING, INC. | BSP | T | 01/15/2009 | PAID (REC#846003) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN rerouted drain lines | TCRIPPEN | TCRIPPEN | | BSP | T | 3791489 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | T | 01/13/2009 | PAID (REC#842493) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN moved drain to outside , no plumbing permit added this to building permit | TCRIPPEN | TCRIPPEN | | BSP | T | 3790320 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | T | 01/09/2009 | PAID (REC#842495) ADDITIONAL PLAN REVIEW TIME: $50 From: JOHNJ CHANGED OCCUPANCY FROM "B" TO "M" : NEW OCCUPANCY IS {M} | JOHNJ | JOHNJ | | BSP | T | 3789751 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | T | 01/08/2009 | PAID (REC#841733) ADDITIONAL PLAN REVIEW TIME: $50 From: MICHAEL Splice additional pads | MICHAELA | MICHAELA | | BSP | T | 3788915 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BSP | P | 01/07/2009 | NEED PLANS WITH APPROVED PAD SIZING | BERTW | BERTW | | BSP | P | 3788723 |
SERVICETEK CONSTRUCTION & MAINTENANCE CONTRACTORS, INC. | BFT | P | 12/30/2008 | SOILS 3000PSF/PADS FROM 1 LINE THRU 5 LINE OK | BERTW | BERTW | | BFT | P | 3786474 |
BIBLE ELECTRIC, INC. | E= | C | 05/29/2009 | gfci receptacle installed for low volt lighting for wall sign | BRET | BRET | | E= | C | 3840001 |
BIBLE ELECTRIC, INC. | E= | P | 04/29/2009 | PENDING SIGN PERMIT OR HOOK-UP | BRET | BRET | | E= | P | 3829081 |
BIBLE ELECTRIC, INC. | E= | P | 04/28/2009 | ROOF OK | BRET | BRET | | E= | P | 3828450 |
BIBLE ELECTRIC, INC. | ER | C | 04/28/2009 | | BRET | BRET | | ER | C | 3828448 |
BIBLE ELECTRIC, INC. | ES | C | 04/09/2009 | COMMERCIAL SERVICE: 1600 AMP 120/208V METERED IN TRANSFORMER BIBLE ELEC | MIKEC | MIKEC | | ES | C | 3822208 |
BIBLE ELECTRIC, INC. | EUG | P | 03/09/2009 | FUTURE SIGN SOUTH EAST CORNER EUG OK | BRET | BRET | | EUG | P | 3810509 |
BIBLE ELECTRIC, INC. | EUG | P | 02/25/2009 | SOUTH POLE BASE AND SIGN UG. COULD NOT FIND ELECTRICIAN ON SITE | BRET | BRET | | EUG | P | 3806059 |
BIBLE ELECTRIC, INC. | EUG | P | 02/17/2009 | SOUTH PARKING LIGHT 2 BASES, NORTH EUG AT BUILDING FOR LIGHTING AND SIGNS. | BRET | BRET | | EUG | P | 3802898 |
BIBLE ELECTRIC, INC. | EUG | P | 02/12/2009 | LIGHT POLE BASES | MIKEC | MIKEC | | EUG | P | 3801935 |
BIBLE ELECTRIC, INC. | EUG | P | 02/09/2009 | site lighting southwest. call for pole base inspection before concrete. | BRET | BRET | | EUG | P | 3800364 |
BIBLE ELECTRIC, INC. | EUG | P | 01/26/2009 | NORTH PARKING 5 POLE LOCATIONS ( BASES ON READY) AND PARTIAL TRENCH TO SIGN | BRET | BRET | | EUG | P | 3794733 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | C | 04/27/2009 | THE GAS LINE IS COMPLETE. | JEFFB | JEFFB | | H= | C | 3828134 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 04/27/2009 | NO AIR BALANCE REPORT REQUIRED FOR SHELL UNIT. | JEFFB | JEFFB | | H= | C | 3828119 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | C | 04/27/2009 | | JEFFB | JEFFB | | HD | C | 3828117 |
HARMON - BONDED PLUMBING & HEATING, INC. | HC | C | 04/14/2009 | OK FOR METER. Suite 140 | JEFFB | JEFFB | | HC | C | 3823448 |
HARMON - BONDED PLUMBING & HEATING, INC. | HI | C | 04/14/2009 | THE GAS LINE IS TAGGED. | JEFFB | JEFFB | | HI | C | 3823447 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | P | 04/02/2009 | ENTRY FOR INSPECTOR TRAINING ONLY. | JON | JON | | H= | P | 3819487 |
HARMON - BONDED PLUMBING & HEATING, INC. | HC | R | 04/02/2009 | REJECTED BECAUSE TAGGING OF THE GAS LINE IS STILL NOT COMPLETE. NOTES: TRAINING WITH JON B. ALSO. | JEFFB | JEFFB | | HC | R | 3819359 |
HARMON - BONDED PLUMBING & HEATING, INC. | HC | R | 03/25/2009 | OK FOR METER. | JEFFB | JEFFB | | HC | R | 3816963 |
HARMON - BONDED PLUMBING & HEATING, INC. | HI | P | 03/25/2009 | 10 LB TEST IS OK. 1 1/4" MAIN TO THE ROOF FOR COMMON RTU. GAS LINE TAGGING IS REQUIRED. | JEFFB | JEFFB | | HI | P | 3816960 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | R | 03/24/2009 | NO ONE ON SITE FROM HARMON. I DON'T KNOW WHAT TO INSPECT. | JEFFB | JEFFB | | H= | R | 3816474 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | C | 03/20/2009 | | MARTY | MARTY | | P= | C | 3815291 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | C | 03/20/2009 | | MARTY | MARTY | | PTO | C | 3815290 |
HARMON - BONDED PLUMBING & HEATING, INC. | PB | C | 02/17/2009 | base for tneant finishes,and grease waste. | MARTY | MARTY | | PB | C | 3802850 |
HARMON - BONDED PLUMBING & HEATING, INC. | PB | P | 01/16/2009 | need to see w/service and floor sink moved. | MARTY | MARTY | | PB | P | 3791978 |