CRADDOCK DEVELOPMENT COMPANY, INC. | B= | C | 02/24/2011 | all items completed | BERTW | BERTW | | B= | C | 4115201 |
CRADDOCK DEVELOPMENT COMPANY, INC. | B= | P | 02/23/2011 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | P | 4114349 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BSP | P | 01/07/2011 | reopen permit only, no inspection done | BLAKE | BLAKE | | BSP | P | 4095516 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFR | C | 05/01/2009 | | BERTW | BERTW | | BFR | C | 3829966 |
CRADDOCK DEVELOPMENT COMPANY, INC. | B= | P | 05/01/2009 | FIRE DEPARTMENT APPROVAL SIGNED ON PERMIT CARD FOR STOCKING ONLY-NEED FIRE DEPARTMENT FINAL APPROVAL/FIRE CAULKING NOT COMPLETED @ RED IRON PENETRATIONS THROUGH FIRE WALL/NEED FRONT AND OVERHEAD DOOR CUTOUT AND SUPPORT FRAMING ENGINEERING/NEED MECHANICAL FINAL INSPECTION/ADDRESS ON BUILDING | BERTW | BERTW | | B= | P | 3829963 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BSP | T | 04/22/2009 | PAID (REC#856310): ADDITIONAL PLAN REVIEW TIME: $50 From: DALEH splice for adding gas piping plan relocated meter | DALEH | DALEH | | BSP | T | 3826442 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BSP | P | 04/15/2009 | DRYWALL MUD NEEDS TO FIRE CAULKED @ RED IRON PENETRATIONS IN RATED WALLS | BERTW | BERTW | | BSP | P | 3823984 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BSP | P | 04/03/2009 | COLUMN WRAPS OK-3 LAYERS OK | BERTW | BERTW | | BSP | P | 3819908 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFR | P | 03/30/2009 | COLUMNS 3 LAYERS OF SHEETROCK OK | BERTW | BERTW | | BFR | P | 3817611 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFR | P | 03/25/2009 | 1ST LAYER OF DRYWALL OK/COLUMN WRAPS IN PROGRESS | BERTW | BERTW | | BFR | P | 3816800 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFR | P | 03/23/2009 | WENT OVER STUD GAUGES/COLUMNS NOT READY/REVIEWED 2 HOUR FIRE WALL AND ALL NEW DOOR CUT-OUTS | BERTW | BERTW | | BFR | P | 3815745 |
CRADDOCK DEVELOPMENT COMPANY, INC. | BFR | R | 03/19/2009 | EXPOSE 1ST LAYER OF DRYWALL-COVERED UP WITHOUT INSPECTION/COLUMNS NEED FRAMING AND 3 LAYERS OF SHEETROCK PER LISTING AND 25 GAUGE STUDS/INFILL NOT FRAMED/TRUNK LINE OPENING NEEDS INFILL AND SHEETROCK/WALL FRAMING OK TO COVER WITH ONE LAYER OF SHEETROCK/FIRE CAULKING INSPECTION NEEDED/STILL NEED DOOR CUT-OUTS INSPECTED-MEZZANINE AREA NEEDS INSPECTED | BERTW | BERTW | | BFR | R | 3814634 |
HIGHER POWER ELECTRIC | E= | C | 04/29/2009 | | MIKEC | MIKEC | | E= | C | 3828764 |
HIGHER POWER ELECTRIC | ER | P | 03/18/2009 | wall ok ceiling ok leave tile out at j-box to check straping on final | TIMA | TIMA | | ER | P | 3814247 |
LANDMARK PLUMBING AND HEATING, INC. | H= | C | 05/01/2009 | GAS FINAL. | JON | JON | | H= | C | 3830032 |
TRADEWINDS HEATING & AIR-COND. | H= | C | 05/01/2009 | RECEIVED BALANCE REPORT | JON | JON | | H= | C | 3829783 |
LANDMARK PLUMBING AND HEATING, INC. | H= | R | 04/30/2009 | NOT READY FOR FINAL... TALKED TO MIKE ON SITE. | JON | JON | | H= | R | 3829430 |
TRADEWINDS HEATING & AIR-COND. | H= | P | 04/29/2009 | NEED BALANCE REPORT | JON | JON | | H= | P | 3828813 |
LANDMARK PLUMBING AND HEATING, INC. | HC | C | 04/23/2009 | 10 LB TEST OK TO MOVE METER | JON | JON | | HC | C | 3827267 |
LANDMARK PLUMBING AND HEATING, INC. | HI | P | 04/22/2009 | RELEASED METER 10 LB TEST. FOR FINAL NEED APPROVED PLANS, ROOF INSPECTION, METER TAG. | JON | JON | | HI | P | 3826736 |