ROBINSON CONSTRUCTION, LLC. | B= | C | 11/24/2009 | Health Department final complete - see below | BOB | BOB | | B= | C | 3916306 |
ROBINSON CONSTRUCTION, LLC. | B= | P | 11/24/2009 | Additional Inspections Required: External Agency Inspection HD= by HEALTHDEPT is not Completed yet. | MIKE | MIKE | | B= | P | 3916285 |
ROBINSON CONSTRUCTION, LLC. | B= | P | 11/19/2009 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: ngadson@springsgov.com or 385-5982), External Agency Inspection HD= by HEALTHDEPT is not Completed yet. Restrooms are existing nonconforming, Deadbolt has been removed from rear exit door | MIKE | MIKE | | B= | P | 3913856 |
ROBINSON CONSTRUCTION, LLC. | BFR | C | 11/19/2009 | | MIKE | MIKE | | BFR | C | 3913853 |
ROBINSON CONSTRUCTION, LLC. | BFR | P | 10/27/2009 | Received revised structural framing plan for the RTU support from Darrell Yee (30364), Need heat rough inspection | MIKE | MIKE | | BFR | P | 3903726 |
ROBINSON CONSTRUCTION, LLC. | BSP | R | 10/19/2009 | Steel reinforcement for RTU - Location & configuration do not match approved engineer design | MIKE | MIKE | | BSP | R | 3900004 |
ROBINSON CONSTRUCTION, LLC. | BFR | P | 10/15/2009 | WALLS OK; NEED HEATING ROUGH; NEED INSPECTION OF JOIST REINFORCEMENT | DANF | DANF | | BFR | P | 3898984 |
MEYER ELECTRIC | E= | C | 11/10/2009 | | MIKEC | MIKEC | | E= | C | 3909639 |
MEYER ELECTRIC | E= | R | 11/09/2009 | GFI REV.POLARITY | MIKEC | MIKEC | | E= | R | 3909082 |
MEYER ELECTRIC | ER | C | 10/14/2009 | WALL | MIKEC | MIKEC | | ER | C | 3898140 |
COLORADO GAS SYSTEMS | H= | C | 11/12/2009 | GAS FINAL. | LYNNS | LYNNS | | H= | C | 3910447 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 11/12/2009 | RECEIVED BALANCE REPORT. | LYNNS | LYNNS | | H= | C | 3910253 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 11/10/2009 | INTERLOCK ON HOOD OK. NEED BALANCE REPORT. | LYNNS | LYNNS | | H= | P | 3909765 |
COLORADO GAS SYSTEMS | H= | P | 11/04/2009 | SEE HI NOTES | JON | JON | | H= | P | 3907260 |
COLORADO GAS SYSTEMS | HC | C | 11/04/2009 | OK FOR 2# METER. 2825 | JON | JON | | HC | C | 3907256 |
COLORADO GAS SYSTEMS | HI | C | 11/04/2009 | APPLIANCE CONNECTIONS, TAG AND REGULATOR FOR FINAL. | JON | JON | | HI | C | 3907252 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 11/02/2009 | GREASE WRAP OK. NEED TO SEE INTERLOCK AND BALANCE REPORT. | LYNNS | LYNNS | | H= | P | 3905971 |
COLORADO GAS SYSTEMS | HI | P | 11/02/2009 | 60# TEST ON ELEVATED PRESSURE LINE FROM METER. NEED TO SEE INSIDE GAS YET. | LYNNS | LYNNS | | HI | P | 3905969 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | C | 10/28/2009 | GREASE DUCT OK TO FIRE WRAP. | LYNNS | LYNNS | | HD | C | 3904592 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 10/27/2009 | WITH A LIGHT TEST, MIKE E. FROM RIAL AND I FOUND SEVERAL HOLES IN THE WELDS. HE WILL REPAAIR THEM AND CALL FOR ANOTHER INSPECTION. | LYNNS | LYNNS | | HD | P | 3903842 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 10/26/2009 | NEED TO LIGHT TEST WELDS. HAVE A 3/8" SHELF ON NORTH SIDE OF FIRST JOINT, REPAIR. | LYNNS | LYNNS | | HD | P | 3903043 |
HOGAN MECHANICAL, INC. | P= | C | 11/19/2009 | CABINET DOORS REMOVED FOR FLOOR/SINK ACCESS | LEE | LEE | | P= | C | 3913750 |
HOGAN MECHANICAL, INC. | P= | P | 11/05/2009 | LACKS OWNER SUPPLIED EQUIPMENT (WATER AND DRAINS) FRONT FLOOR SINK LACKS READY ACCESS | LEE | LEE | | P= | P | 3908022 |
HOGAN MECHANICAL, INC. | PTO | C | 10/16/2009 | | LEE | LEE | | PTO | C | 3899141 |
HOGAN MECHANICAL, INC. | PB | C | 10/07/2009 | | LYNNIE | LYNNIE | | PB | C | 3895407 |