FOSTER ELECTRIC CORPORATION | BSP | T | 07/01/2010 | PAID (REC#917954): ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY Load changes resuling from water heater changes | SHELBY | SHELBY | | BSP | T | 4003800 |
COLARELLI CONSTRUCTION, INC. | B= | C | 06/23/2010 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | C | 3999590 |
COLARELLI CONSTRUCTION, INC. | B= | P | 06/22/2010 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-7396), FOSTER ELECTRIC CORP Electrical Final Inspection is not Completed yet, UNIVERSAL MECHANICAL & CONSTR Mechanical Final Inspection is not Completed yet. | BERTW | BERTW | | B= | P | 3998845 |
COLARELLI CONSTRUCTION, INC. | BFR | C | 06/22/2010 | | BERTW | BERTW | | BFR | C | 3998842 |
COLARELLI CONSTRUCTION, INC. | BSP | T | 06/04/2010 | PAID (REC # 912991)PLAN SPLICE FEE: $50 by: SHELLEY for Construction: ADDED SQ FOOTAGE TO SCOPE | SHELLEY | SHELLEY | | BSP | T | 3990425 |
FOSTER ELECTRIC CORPORATION | BSP | T | 06/04/2010 | PAID (REC # 912991)ADDITIONAL PLAN REVIEW TIME: $50 From: MATTHEW splice 3 new pages for exercise room | MATTHEW | MATTHEW | | BSP | T | 3990379 |
UNIVERSAL MECHANICAL & CONSTR | BSP | P | 06/01/2010 | PAID ( REC # 912991)PLAN SPLICE FEE: $50 by: DALEH for Mechanical: splice for extending exercise room | DALEH | DALEH | | BSP | P | 3988580 |
COLARELLI CONSTRUCTION, INC. | BFR | P | 05/19/2010 | WALLS OK/PENDING ALL OTHER ROUGH INSPECTIONS COMPLETED | BERTW | BERTW | | BFR | P | 3983256 |
FOSTER ELECTRIC CORPORATION | E= | C | 09/21/2010 | plans revised with 2nd water heater | BRET | BRET | | E= | C | 4042917 |
FOSTER ELECTRIC CORPORATION | E= | R | 09/17/2010 | could not find revised plans. contractor not on site. | BRET | BRET | | E= | R | 4041442 |
FOSTER ELECTRIC CORPORATION | E= | P | 06/22/2010 | ground bushings and labelling complete plans changes of load will be made per contractor by 7-2-2010 | BRET | BRET | | E= | P | 3998905 |
FOSTER ELECTRIC CORPORATION | E= | P | 06/21/2010 | see ep | MATTHEW | MATTHEW | | E= | P | 3998056 |
FOSTER ELECTRIC CORPORATION | EP | P | 06/21/2010 | need bond bushings on 480v feeder, revise plans showing correct load at water heaters; 45kva | MATTHEW | MATTHEW | | EP | P | 3998055 |
FOSTER ELECTRIC CORPORATION | E= | R | 06/18/2010 | see service notes | BRET | BRET | | E= | R | 3997896 |
FOSTER ELECTRIC CORPORATION | ES | R | 06/18/2010 | called 243-7858 person did not know anything about job. Is this number correct? | BRET | BRET | | ES | R | 3997894 |
FOSTER ELECTRIC CORPORATION | ES | R | 06/18/2010 | called 243-7858 person did not know anything about job. Is this number correct? | BRET | BRET | | ES | R | 3997893 |
FOSTER ELECTRIC CORPORATION | ER | C | 06/11/2010 | ceilings ok | BRET | BRET | | ER | C | 3994201 |
FOSTER ELECTRIC CORPORATION | ER | P | 05/18/2010 | walls | BRET | BRET | | ER | P | 3982459 |
UNIVERSAL MECHANICAL & CONSTR | H= | C | 06/23/2010 | RECEIVED BALANCE REPORT | JON | JON | | H= | C | 3999589 |
UNIVERSAL MECHANICAL & CONSTR | H= | P | 06/21/2010 | THE INTERLOCK FOR THE EXHAUST FAN IS COMPLETE. PARTIAL PENDING THE AIR BALANCE REPORT. | JEFFB | JEFFB | | H= | P | 3998437 |
UNIVERSAL MECHANICAL & CONSTR | HD | C | 06/09/2010 | OK FOR TILE. NEED TO VERIFY INTERLOCK AND BALANCE REPORT FOR FINAL. | JON | JON | | HD | C | 3992644 |
UNIVERSAL MECHANICAL & CONSTR | HD | P | 05/20/2010 | OK FOR DUCT WRAP. INTERLOCK, RETURN PATH AND BALANCE REPORT FINAL. | JON | JON | | HD | P | 3984362 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 06/21/2010 | | LYNNIE | LYNNIE | | P= | C | 3998070 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 06/18/2010 | ALL MIXING VALVES ARE SET TO HIGH--MAX 120*--NOW SET ON 140+--LAVS TO BE SET AT 85*/110* TOO | LYNNIE | LYNNIE | | P= | P | 3997440 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 05/21/2010 | | LYNNIE | LYNNIE | | PTO | C | 3984632 |
LANDMARK PLUMBING AND HEATING, INC. | PB | C | 05/10/2010 | VERIFY EXISTING EJECTOR PIT SIZING BY PTO | LYNNIE | LYNNIE | | PB | C | 3978600 |