ROBINSON CONSTRUCTION, LLC. | B= | C | 10/21/2011 | already completed by pepper | BLAKE | BLAKE | | B= | C | 4224933 |
ROBINSON CONSTRUCTION, LLC. | B= | C | 10/19/2011 | all signed off | JIMP | JIMP | | B= | C | 4224171 |
ROBINSON CONSTRUCTION, LLC. | BE | C | 04/25/2011 | Renewed at 4/25/2011 1:33:54 PM (only expired one day) | JAN | JAN | | BE | C | 4140256 |
ROBINSON CONSTRUCTION, LLC. | B= | P | 10/25/2010 | Problem not corrected, Still need completed shell building final -- Schedule a new Building Final when above items are complete. | MIKE | MIKE | | B= | P | 4060869 |
ROBINSON CONSTRUCTION, LLC. | BFR | C | 10/22/2010 | | MIKE | MIKE | | BFR | C | 4060121 |
ROBINSON CONSTRUCTION, LLC. | B= | P | 10/22/2010 | Need completed shell final | MIKE | MIKE | | B= | P | 4060080 |
ROBINSON CONSTRUCTION, LLC. | B= | P | 10/21/2010 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-7396). Need fire final, Need completed shell final | MIKE | MIKE | | B= | P | 4059790 |
ROBINSON CONSTRUCTION, LLC. | B= | R | 10/20/2010 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-7396). Need fire final, Need completed frame inspection(fire barrier walls are on shell permit), Need completed shell final | MIKE | MIKE | | B= | R | 4058719 |
ROBINSON CONSTRUCTION, LLC. | B= | R | 10/18/2010 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-7396), ENVIRONMENTAL HTG & AIR COND Mechanical Final Inspection is not Completed yet. 1) COMPLETE FRAMING INSPECTION, FIRE BARRIER WALL INSPECTION 2) NEED OPEN/CLOSED KEYED LOCK ON ENTRY DOOR 3) NEED SIGN ABOVE ENTRY DOOR PERMANTLY ATTACHED 4) COMPLETE MECHANICAL AND FIRE FINALS | DANF | DANF | | B= | R | 4057439 |
MEYER ELECTRIC | BSP | T | 09/30/2010 | PAID (REC#936229) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY Revise one line | SHELBY | SHELBY | | BSP | T | 4049317 |
ROBINSON CONSTRUCTION, LLC. | BIN | C | 09/10/2010 | R-13 in walls ok | MIKE | MIKE | | BIN | C | 4038007 |
ROBINSON CONSTRUCTION, LLC. | BFR | P | 09/10/2010 | Reviewed fire barrier requirements | MIKE | MIKE | | BFR | P | 4038006 |
ROBINSON CONSTRUCTION, LLC. | BFR | R | 09/08/2010 | Need all rough inspections, Missing bath fan | MIKE | MIKE | | BFR | R | 4036436 |
MEYER ELECTRIC | E= | C | 10/08/2010 | rtu was inspected previous inspection | GARYL | GARYL | | E= | C | 4053058 |
MEYER ELECTRIC | ES | C | 10/01/2010 | Commercial Service: 200 amp 4w 3ph 120/208 commercial service by meyer electric; | JOSEPH | JOSEPH | | ES | C | 4049900 |
MEYER ELECTRIC | ER | P | 09/29/2010 | ceilings only, water htr is hard wired with a disconnect on it, 1-mcc in panel #12 | GARYL | GARYL | | ER | P | 4047938 |
MEYER ELECTRIC | ES | R | 09/28/2010 | revise plans to show 200 amp feeder and fuses, handle tie and group multi conductor circuits | MATTHEW | MATTHEW | | ES | R | 4047200 |
MEYER ELECTRIC | ER | R | 09/28/2010 | secure fixtures to grid, wire to structure on oppisite corners, water heater cord connected above drop ceiling, strap mc at water heater, contractor needs to verify water heater size (nameplate turned to wall) | MATTHEW | MATTHEW | | ER | R | 4047192 |
MEYER ELECTRIC | ER | P | 09/08/2010 | WALLS ONLY | GARYL | GARYL | | ER | P | 4036199 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | C | 10/19/2010 | RECEIVED BALANCE REPORT. | LYNNS | LYNNS | | H= | C | 4057994 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 10/18/2010 | HVAC FINAQL PENDING BALANCE REPORT. | LYNNS | LYNNS | | H= | P | 4057684 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | C | 10/01/2010 | BATH FAN AND ROOF WORK OK. | LYNNS | LYNNS | | HD | C | 4049987 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | H= | P | 10/01/2010 | NEED TO INSULATE PVC IN CEILING BY WATER HEATER, NEED BALANCE REPORT. | LYNNS | LYNNS | | H= | P | 4049984 |
ENVIRONMENTAL HEATING & AIR CONDITIONING INC. | HD | P | 09/09/2010 | ROUGH DUCT OK. NEED TO SEE BATH FAN VENT COMPLETED AND ROOF WORK. | LYNNS | LYNNS | | HD | P | 4037455 |
HOGAN MECHANICAL, INC. | P= | C | 10/12/2010 | FLOOR MOP SINK REQ A DOOR PER A1-1 | LYNNIE | LYNNIE | | P= | C | 4054882 |
HOGAN MECHANICAL, INC. | PTO | C | 09/10/2010 | | LYNNIE | LYNNIE | | PTO | C | 4038073 |
HOGAN MECHANICAL, INC. | PB | C | 08/31/2010 | | LYNNIE | LYNNIE | | PB | C | 4032806 |