ART C KLEIN CONSTRUCTION, INC. | B= | C | 08/08/2012 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | C | 4357420 |
ART C KLEIN CONSTRUCTION, INC. | B= | P | 04/26/2012 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: mmaloney@springsgov.com or 385-5080), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977), FOSTER ELECTRIC CORP Electrical Final Inspection is not Completed yet, FRONTIER MECHANICAL SYSTEMS IN Plumbing Final Inspection is not Completed yet, HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet. spray fireproofing inspection letter on file | BERTW | BERTW | | B= | P | 4302216 |
ART C KLEIN CONSTRUCTION, INC. | BSP | P | 03/23/2012 | soils letter on file for east addition | BERTW | BERTW | | BSP | P | 4286732 |
ART C KLEIN CONSTRUCTION, INC. | BFR | C | 03/21/2012 | | BERTW | BERTW | | BFR | C | 4285509 |
ART C KLEIN CONSTRUCTION, INC. | BFT | C | 03/21/2012 | | BERTW | BERTW | | BFT | C | 4285506 |
ART C KLEIN CONSTRUCTION, INC. | BFN | C | 03/21/2012 | | BERTW | BERTW | | BFN | C | 4285505 |
ART C KLEIN CONSTRUCTION, INC. | BSP | T | 03/19/2012 | PAID (REC#1033860) PLAN SPLICE FEE: $50 by: JAY for Construction: foundation revision/addition: OK | JAY | JAY | | BSP | T | 4284656 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 01/19/2012 | hat channel ok tug way lid | BERTW | BERTW | | BFR | P | 4261607 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 01/18/2012 | this completes framing pending all other rough inspections completed | BERTW | BERTW | | BFR | P | 4260878 |
ART C KLEIN CONSTRUCTION, INC. | BFR | R | 01/13/2012 | CANCELED BY CONTRACTOR | BERTW | BERTW | | BFR | R | 4259461 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 12/28/2011 | east baggage walls ok/hat channel ok west screening area | BERTW | BERTW | | BFR | P | 4253728 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 12/14/2011 | walls ok west baggage handling area | BERTW | BERTW | | BFR | P | 4249234 |
ART C KLEIN CONSTRUCTION, INC. | B= | P | 12/02/2011 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-7396), External Agency Inspection Z= by ZONING is not Completed yet (Contact: mmaloney@springsgov.com or 385-5080), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977), FOSTER ELECTRIC CORP Electrical Final Inspection is not Completed yet, FRONTIER MECHANICAL SYSTEMS IN Mechanical Final Inspection is not Completed yet, FRONTIER MECHANICAL SYSTEMS IN Plumbing Final Inspection is not Completed yet, HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet. training and OSR room ok/pending other roughs completed -- Schedule a new Building Final when above items are complete. | BERTW | BERTW | | B= | P | 4244039 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 11/18/2011 | OSR room walls ok | BERTW | BERTW | | BFR | P | 4238356 |
ART C KLEIN CONSTRUCTION, INC. | BFN | P | 11/09/2011 | east pilasters X4 ok | BERTW | BERTW | | BFN | P | 4233303 |
ART C KLEIN CONSTRUCTION, INC. | BFI | P | 11/07/2011 | east and west wings ok | BERTW | BERTW | | BFI | P | 4231975 |
ART C KLEIN CONSTRUCTION, INC. | BFN | P | 11/07/2011 | east wing pilasters ok | BERTW | BERTW | | BFN | P | 4231964 |
ART C KLEIN CONSTRUCTION, INC. | BFT | P | 10/28/2011 | east "V" line ok | BERTW | BERTW | | BFT | P | 4228404 |
ART C KLEIN CONSTRUCTION, INC. | BFN | P | 10/28/2011 | east walls to "V" line | BERTW | BERTW | | BFN | P | 4228399 |
ART C KLEIN CONSTRUCTION, INC. | BFT | P | 10/24/2011 | east phase up to V line ok,pending engineering for non-continous footings | BERTW | BERTW | | BFT | P | 4225920 |
ART C KLEIN CONSTRUCTION, INC. | BFN | P | 10/21/2011 | west walls complete | BERTW | BERTW | | BFN | P | 4225169 |
ART C KLEIN CONSTRUCTION, INC. | BFT | P | 10/18/2011 | west areas completed | BERTW | BERTW | | BFT | P | 4223125 |
ART C KLEIN CONSTRUCTION, INC. | BFN | P | 10/18/2011 | 17-19/K thru L ok west areas | BERTW | BERTW | | BFN | P | 4223123 |
ART C KLEIN CONSTRUCTION, INC. | BFT | P | 10/14/2011 | 17-19 line/K thru L piasters ok | BERTW | BERTW | | BFT | P | 4221839 |
ART C KLEIN CONSTRUCTION, INC. | BFN | P | 10/13/2011 | 15.3 line F-H pilasters ok | BERTW | BERTW | | BFN | P | 4221070 |
ART C KLEIN CONSTRUCTION, INC. | BFT | P | 10/13/2011 | 17-19 line/K thru L pads ok | BERTW | BERTW | | BFT | P | 4221065 |
ART C KLEIN CONSTRUCTION, INC. | BSP | T | 10/13/2011 | PAID (REC#1005594) PLAN SPLICE FEE: $50 by: JAY for Construction: Foundation adjustments - Delta 2 | JAY | JAY | | BSP | T | 4220848 |
ART C KLEIN CONSTRUCTION, INC. | BFT | P | 10/11/2011 | 16 line E thru H pilasters ok/15.3 line E thru H pads ok | BERTW | BERTW | | BFT | P | 4220172 |
ART C KLEIN CONSTRUCTION, INC. | BFT | P | 10/07/2011 | pending revised design for elevation changes/line E thru H,15-16 pads and footing ok/open hole report for this section on file | BERTW | BERTW | | BFT | P | 4218611 |
FOSTER ELECTRIC CORPORATION | E= | C | 08/08/2012 | TYPE TC CABLE IS INSTALLED FOR DOOR OPENERS COMPLIES WITH NEC. | TIMA | TIMA | | E= | C | 4357419 |
FOSTER ELECTRIC CORPORATION | EP | C | 07/30/2012 | PANEL BHS-4E AND BHS-1E AND TRANSFORMERS OK | TIMA | TIMA | | EP | C | 4350881 |
FOSTER ELECTRIC CORPORATION | E= | P | 07/30/2012 | NO CORDS FOR PERMANENT WIRING TO GARAGE DOOR OPENERS------REST OK----- | TIMA | TIMA | | E= | P | 4350879 |
FOSTER ELECTRIC CORPORATION | ER | P | 01/30/2012 | EAST CBRA CEILINGS OK--------AHU-5 25 AMP MAX OVERCURRENT PROTECTION CHECK ON FINAL----- | TIMA | TIMA | | ER | P | 4265379 |
FOSTER ELECTRIC CORPORATION | ER | P | 01/23/2012 | EAST PASSENGER SCREENING HARD LID OK | TIMA | TIMA | | ER | P | 4262534 |
FOSTER ELECTRIC CORPORATION | ER | P | 01/18/2012 | WEST CBRA CEILINGS OK | TIMA | TIMA | | ER | P | 4260702 |
FOSTER ELECTRIC CORPORATION | ER | P | 12/28/2011 | EAST BAGGAGE WALLS OK | TIMA | TIMA | | ER | P | 4253772 |
FOSTER ELECTRIC CORPORATION | ER | P | 12/19/2011 | PASSENGER SCREENING BRIDGE WEST HARD LIDS OK | TIMA | TIMA | | ER | P | 4250728 |
FOSTER ELECTRIC CORPORATION | ER | P | 12/14/2011 | WEST BAGGAGE AREA WALLS OK | TIMA | TIMA | | ER | P | 4248965 |
FOSTER ELECTRIC CORPORATION | E= | P | 12/02/2011 | OSR AND TRAINING ROOM OK | TIMA | TIMA | | E= | P | 4243995 |
FOSTER ELECTRIC CORPORATION | ER | P | 12/01/2011 | CEILINGS OSR ROOMS OK | TIMA | TIMA | | ER | P | 4243470 |
FOSTER ELECTRIC CORPORATION | ER | P | 11/18/2011 | OSR AND SERVER ROOMS WALLS OK | TIMA | TIMA | | ER | P | 4238136 |
HVAC SOLUTIONS, INC. | H= | C | 08/06/2012 | Siemens verified co operation and received balance report. | JON | JON | | H= | C | 4356277 |
HVAC SOLUTIONS, INC. | H= | P | 07/31/2012 | Pending verification that co sensor interlock was tested, power was off to east terminal side purge fans. | JON | JON | | H= | P | 4352538 |
HVAC SOLUTIONS, INC. | H= | P | 07/11/2012 | Received balance report, still need on site visit. Duct inspection has not been completed. Will review balance report on site with approved plans when called for inspection. | JON | JON | | H= | P | 4339634 |
HVAC SOLUTIONS, INC. | HD | P | 02/23/2012 | OK FOR DUCT WRAP ON PASSENGER SCREENING EAST AND WEST. | JON | JON | | HD | P | 4274976 |
FRONTIER MECHANICAL SYSTEMS INC | H= | C | 02/09/2012 | Piping gas and drains only. | JON | JON | | H= | C | 4269799 |
HVAC SOLUTIONS, INC. | HD | P | 01/25/2012 | Rough duct complete at east baggage for three air handlers. Will need interlocks for exhaust and make air dampers verified before final with balance reports on all. | JON | JON | | HD | P | 4264046 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 01/25/2012 | East hot and chilled water piping and condensate for 3 air handlers at baggage ok for insulation | JON | JON | | HWP | P | 4264039 |
HVAC SOLUTIONS, INC. | HD | P | 01/18/2012 | EAST SIDE BAGGAGE 1ST FLOOR OK TO WRAP THREE AIR HANDLERS | JON | JON | | HD | P | 4261164 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 01/12/2012 | INSULATION COMPLETE AT CBRA AREA WEST. | JON | JON | | HWP | P | 4259120 |
HVAC SOLUTIONS, INC. | HD | P | 01/12/2012 | DUCT COMPLETE CBRA AND BOTH WEST BAGGAGE ROOMS. WILL NEED BALANCE REPORTS FOR ALL AT FINAL. | JON | JON | | HD | P | 4259119 |
HVAC SOLUTIONS, INC. | HD | P | 01/05/2012 | WEST THREE AIR HANDLERS OK FOR WRAP.. ALL CO EXHAUST TO BE INSPECTED WHEN READY. CALL EAST SIDE DUCT INSPECTION WHEN READY. ALL INTERLOCKS AND BALANCE REPORT BY FINAL | JON | JON | | HD | P | 4256335 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 01/05/2012 | PIPING COMPLETE TO WEST AIR HANDLERS AND OK TO INSULATE. | JON | JON | | HWP | P | 4256334 |
HVAC SOLUTIONS, INC. | HD | P | 12/14/2011 | OK FOR WRAP, RECALL BEFORE TILE. | JON | JON | | HD | P | 4248837 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 11/30/2011 | OSR PIPING COMPLETE | JON | JON | | HWP | P | 4242979 |
FRONTIER MECHANICAL SYSTEMS INC | H= | P | 11/30/2011 | OSR COMPLETE | JON | JON | | H= | P | 4242978 |
HVAC SOLUTIONS, INC. | H= | P | 11/30/2011 | OSR COMPLETE | JON | JON | | H= | P | 4242975 |
HVAC SOLUTIONS, INC. | HD | P | 11/28/2011 | OSR room ok for duct wrap. Need hwp when ready in OSR | JON | JON | | HD | P | 4241436 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 11/14/2011 | TWO NEW RE-HEAT COILS AND ONE RELOCATE COMPLETE. | JON | JON | | HWP | P | 4235494 |
FRONTIER MECHANICAL SYSTEMS INC | H= | P | 10/10/2011 | INSPECT GAS TIE IN ON HWP INSPECTION WHEN IN SECURE AREA. | JON | JON | | H= | P | 4219338 |
FRONTIER MECHANICAL SYSTEMS INC | HC | C | 10/06/2011 | OK TO MOVE METER, 10 LB TEST | JON | JON | | HC | C | 4217848 |
FRONTIER MECHANICAL SYSTEMS INC | HI | C | 10/06/2011 | 10 LB TEST COMPLETE. FOR METER MOVE.. FOR FINAL SEE TIE IN TO EXISTING. | JON | JON | | HI | C | 4217842 |
FRONTIER MECHANICAL SYSTEMS INC | P= | C | 06/13/2012 | | JOEL | JOEL | | P= | C | 4325431 |
FRONTIER MECHANICAL SYSTEMS INC | PRD | C | 03/08/2012 | | JOEL | JOEL | | PRD | C | 4280585 |
FRONTIER MECHANICAL SYSTEMS INC | PTO | C | 02/09/2012 | | JOEL | JOEL | | PTO | C | 4269435 |
FRONTIER MECHANICAL SYSTEMS INC | PTO | P | 01/25/2012 | east terminal h2o o.k, 2- funnel drains in east terminal need aav | JOEL | JOEL | | PTO | P | 4263706 |
FRONTIER MECHANICAL SYSTEMS INC | PRD | P | 01/25/2012 | east terminal tie in o.k | JOEL | JOEL | | PRD | P | 4263700 |
FRONTIER MECHANICAL SYSTEMS INC | PRD | P | 01/11/2012 | EAST TERMINIAL | LYNNIE | LYNNIE | | PRD | P | 4258390 |
FRONTIER MECHANICAL SYSTEMS INC | PRD | P | 01/06/2012 | west terminal roof drains. | MARTY | MARTY | | PRD | P | 4256851 |
FRONTIER MECHANICAL SYSTEMS INC | PTO | P | 01/06/2012 | west treminal,grease and sand oil. | MARTY | MARTY | | PTO | P | 4256847 |
FRONTIER MECHANICAL SYSTEMS INC | PRD | P | 12/21/2011 | roof and overflow drains west terminal,also vents for sand oil. | MARTY | MARTY | | PRD | P | 4252071 |
FRONTIER MECHANICAL SYSTEMS INC | PRD | P | 10/13/2011 | east terminal underground r.d o.k | JOEL | JOEL | | PRD | P | 4221068 |
FRONTIER MECHANICAL SYSTEMS INC | PRD | P | 09/15/2011 | underground west terminal. | MARTY | MARTY | | PRD | P | 4207845 |
FRONTIER MECHANICAL SYSTEMS INC | PB | P | 09/08/2011 | grease and sanitary,will need to see storm drains. | MARTY | MARTY | | PB | P | 4204662 |
FRONTIER MECHANICAL SYSTEMS INC | PB | P | 09/02/2011 | sand oil ok. | MARTY | MARTY | | PB | P | 4202574 |
FRONTIER MECHANICAL SYSTEMS INC | PB | P | 08/26/2011 | grid line j-g. | MARTY | MARTY | | PB | P | 4199329 |