DANIEL-BARRY CONSTRUCTION INC | B= | C | 11/09/2012 | | BLAKE | BLAKE | | B= | C | 4419386 |
DANIEL-BARRY CONSTRUCTION INC | BSP | T | 10/24/2012 | PAID (REC#1090786) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY | SHELBY | SHELBY | | BSP | T | 4408023 |
DANIEL-BARRY CONSTRUCTION INC | B= | P | 10/10/2012 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: kmagargal@springsgov.com or 385-5060), E LIGHT ELECTRIC SERVICES, INC Electrical Final Inspection is not Completed yet. need elec final inspection completed -- Schedule a new Building Final when above items are complete. | BLAKE | BLAKE | | B= | P | 4398827 |
DANIEL-BARRY CONSTRUCTION INC | BE | L | 08/20/2012 | Renewed at 8/20/2012 1:45:32 PM | ROGER | ROGER | | BE | L | 4365286 |
DANIEL-BARRY CONSTRUCTION INC | BSP | P | 01/06/2012 | floor penetrations sealed ok @ new conduits | BERTW | BERTW | | BSP | P | 4256846 |
DANIEL-BARRY CONSTRUCTION INC | BBB | C | 01/06/2012 | | BERTW | BERTW | | BBB | C | 4256844 |
DANIEL-BARRY CONSTRUCTION INC | BSP | T | 12/07/2011 | PAID (REC#1016367) ADDITIONAL PLAN REVIEW TIME: $50 From: RUSSELL Changed electrical room height and added 4 clg r.a. grilles | RUSSELL | RUSSELL | | BSP | T | 4245923 |
DANIEL-BARRY CONSTRUCTION INC | BFN | C | 12/02/2011 | stamped open hole on file | BERTW | BERTW | | BFN | C | 4243909 |
DANIEL-BARRY CONSTRUCTION INC | BFT | C | 11/29/2011 | ok pending stamped open hole report | BERTW | BERTW | | BFT | C | 4241775 |
DANIEL-BARRY CONSTRUCTION INC | BSP | T | 11/28/2011 | PAID (REC#1014341) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: revised screenwall | SHELLEY | SHELLEY | | BSP | T | 4241081 |
DANIEL-BARRY CONSTRUCTION INC | BFR | P | 11/23/2011 | framing ok at electric room/pending other rough inspections | BERTW | BERTW | | BFR | P | 4240353 |
DANIEL-BARRY CONSTRUCTION INC | BSP | T | 11/15/2011 | PAID (REC#1012240) PLAN SPLICE FEE: $50 by: MICHAEL for Construction: Revise rated wall drawing | MICHAELA | MICHAELA | | BSP | T | 4235822 |
E LIGHT ELECTRIC SERVICES, INC | BSP | T | 11/03/2011 | PAID (REC#1010127) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY Remove D/C per Dean | SHELBY | SHELBY | | BSP | T | 4230716 |
E LIGHT ELECTRIC SERVICES, INC | E= | C | 11/08/2012 | | BRET | BRET | | E= | C | 4418736 |
E LIGHT ELECTRIC SERVICES, INC | E= | P | 11/02/2012 | sprinkler in footprint of transformer. | BRET | BRET | | E= | P | 4414463 |
E LIGHT ELECTRIC SERVICES, INC | EE | C | 08/14/2012 | | TERRI | TERRI | | EE | C | 4361219 |
E LIGHT ELECTRIC SERVICES, INC | E= | P | 02/22/2012 | need parameters set on 1000 amp breaker ( 800 amp conductors) , install labeling on 3 services location and service #, relocate sprinkler lines above electrical equipment, | BRET | BRET | | E= | P | 4274125 |
E LIGHT ELECTRIC SERVICES, INC | EP | C | 02/22/2012 | 3rd floor electrical equipment ok | BRET | BRET | | EP | C | 4274120 |
E LIGHT ELECTRIC SERVICES, INC | EP | R | 02/17/2012 | NOTE---NEED TO MOVE 2 SPRINKLER LINES OVER TOP OF SWITCHGEAR AND PANELBOARD----- NEED TO CHECK ALL TRANS. AND PANELS---- | TIMA | TIMA | | EP | R | 4272733 |
E LIGHT ELECTRIC SERVICES, INC | ES | C | 02/17/2012 | Commercial Service: 1600 AMP 4/W NEW SERVICE FOR POLICE OPS 911 | TIMA | TIMA | | ES | C | 4272729 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 02/17/2012 | ELECTRIC ROOM CEILING OK | TIMA | TIMA | | ER | P | 4272726 |
E LIGHT ELECTRIC SERVICES, INC | ES | R | 02/16/2012 | NEED TO BOND NEUTRAL IN TRANSFER SWITCH/SERVICE DISCONNECT,UNBOND NEUTRAL IN SWITCHGEAR IN BUILDING,NEED 2ND GROUND ROD AT TRANSFER SWITCH,NEED GROUND ROD FOR CT METER AND ADDRESS TAG,NEED GFI TEST RESULTS FOR SERVICE DISCONNECT | TIMA | TIMA | | ES | R | 4272191 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 01/31/2012 | pole base ok | BRET | BRET | | ER | P | 4266136 |
E LIGHT ELECTRIC SERVICES, INC | ER | P | 01/10/2012 | conduit run from basement to 3rd floor electric room new walls ok | BRET | BRET | | ER | P | 4258060 |
E LIGHT ELECTRIC SERVICES, INC | EUG | C | 12/14/2011 | ug complete need to bond all grc 90s that are not at least 18" below grade nec 250.80 | BRET | BRET | | EUG | C | 4249043 |
E LIGHT ELECTRIC SERVICES, INC | EUG | P | 12/02/2011 | eug from transfer to building ok to cover | BRET | BRET | | EUG | P | 4244190 |
E LIGHT ELECTRIC SERVICES, INC | EUG | P | 11/22/2011 | 10 ' from building 10' from transfer switch o to cover. | BRET | BRET | | EUG | P | 4240276 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 02/24/2012 | INSPECTED ALL ON DUCT INSPECTION NO BALANCE REQUIRED, COOLING ONLY NO FRESH AIR NEEDED PER PLANS. | JON | JON | | H= | C | 4275162 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | C | 01/12/2012 | Duct complete, roof complete, drains and refer piping complete. Cooling unit has internal float switch for secondary | JON | JON | | HD | C | 4259113 |
RIAL HEATING AND AIR CONDITIONING, INC. | HRP | C | 12/02/2011 | LINE SET AND TEST ONLY NO EQUIPMENT YET | JON | JON | | HRP | C | 4243993 |