COLARELLI CONSTRUCTION, INC. | B= | C | 06/18/2012 | All other required Final inspections are complete. (This is a computer generated result) | BERTW | BERTW | | B= | C | 4327699 |
COLARELLI CONSTRUCTION, INC. | B= | P | 06/07/2012 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: mmaloney@springsgov.com or 385-5080). | BERTW | BERTW | | B= | P | 4322719 |
COLARELLI CONSTRUCTION, INC. | BFR | C | 06/07/2012 | | BERTW | BERTW | | BFR | C | 4322716 |
RYBA ELECTRIC, INC. | BSP | T | 04/13/2012 | PAID (REC#1039084) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY modify feeder for panels L4A and G | SHELBY | SHELBY | | BSP | T | 4296613 |
COLARELLI CONSTRUCTION, INC. | BFR | P | 03/27/2012 | phase #2 walls ok/need 2 vestibules inspected/pending other roughs completed | BERTW | BERTW | | BFR | P | 4288087 |
COLARELLI CONSTRUCTION, INC. | BFR | P | 01/30/2012 | walls ok phase #1/pending other roughs completed | BERTW | BERTW | | BFR | P | 4265400 |
RYBA ELECTRIC, INC. | E= | C | 05/04/2012 | | BRET | BRET | | E= | C | 4306727 |
RYBA ELECTRIC, INC. | ER | C | 04/25/2012 | | BRET | BRET | | ER | C | 4301539 |
RYBA ELECTRIC, INC. | ER | C | 04/25/2012 | | BRET | BRET | | ER | C | 4301507 |
RYBA ELECTRIC, INC. | EP | P | 04/17/2012 | l4a,h4a transformer, install 125 amp breaker in h4 , handles ties | BRET | BRET | | EP | P | 4297812 |
RYBA ELECTRIC, INC. | ER | P | 04/10/2012 | phase one ceiling ok | BRET | BRET | | ER | P | 4294322 |
RYBA ELECTRIC, INC. | ER | P | 03/28/2012 | 2nd phase walls ok | BRET | BRET | | ER | P | 4288912 |
RYBA ELECTRIC, INC. | ER | P | 03/13/2012 | 402 thur 408 ceiling | BRET | BRET | | ER | P | 4281956 |
RYBA ELECTRIC, INC. | ER | P | 02/09/2012 | bathroom hard lid | BRET | BRET | | ER | P | 4269673 |
RYBA ELECTRIC, INC. | ER | P | 01/26/2012 | walls marked on plans | BRET | BRET | | ER | P | 4264389 |
HVAC SOLUTIONS, INC. | H= | C | 05/09/2012 | DID NOT SEE PERMIT CARD ON SITE. MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 4308157 |
HVAC SOLUTIONS, INC. | H16 | C | 05/09/2012 | TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H16 | C | 4308099 |
HVAC SOLUTIONS, INC. | H= | P | 04/27/2012 | DRAWING FROM ENGINEER SHOWING EXISTING FIRE DAMPER AND EXHAUST DUCT RECEIVED AND SCANNED. | NANCY | NANCY | | H= | P | 4302716 |
HVAC SOLUTIONS, INC. | H= | P | 04/23/2012 | PHASE TWO INSPECTION. WOMENS BATHROOM: NEED REVISED/APPROVED PRINTS SHOWING ACTUAL EXHAUST DUCT INSTALLED WITH EXISTING FIRE DAMPER. DELETE FIRE/SMOKE FROM PRINTS. IT/ELECTRICAL ROOM: INSTALL CONDENSATE DRAINS AND T-STAT. FIRE DAMPERS: LABEL GRID TO SHOW DAMPER LOCATIONS. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4300583 |
HVAC SOLUTIONS, INC. | HD | P | 03/28/2012 | ok for 2 damper openings, still need fire smoke damper framing in women's bath room inspected when ready. Ok for wrap on all round pipe. | JON | JON | | HD | P | 4288924 |
HVAC SOLUTIONS, INC. | HD | P | 03/13/2012 | NEED PLANS ON SITE, NEED TO LABEL CEILING AT FIRE DAMPER, NEED BALANCE REPORT | JON | JON | | HD | P | 4282536 |
HVAC SOLUTIONS, INC. | HD | P | 02/01/2012 | ok for wrap and fire damper framing ok | JON | JON | | HD | P | 4266774 |
HVAC SOLUTIONS, INC. | HD | P | 01/30/2012 | 4th floor ok to wrap low pressure on boxes 10 through 19. Need fire damper instructions before damper inspections are called | JON | JON | | HD | P | 4265486 |
LANDMARK PLUMBING AND HEATING, INC. | P= | C | 05/02/2012 | | LYNNIE | LYNNIE | | P= | C | 4304931 |
LANDMARK PLUMBING AND HEATING, INC. | P= | P | 05/01/2012 | BREAK SINK LACKS AN AAV | LYNNIE | LYNNIE | | P= | P | 4304357 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | C | 05/01/2012 | | LYNNIE | LYNNIE | | PTO | C | 4304354 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 04/06/2012 | PHASE TWO--IN WALL | LYNNIE | LYNNIE | | PTO | P | 4293029 |
LANDMARK PLUMBING AND HEATING, INC. | PTO | P | 02/07/2012 | PHASE 1 OKAY---- ADD THE DF BY FINAL | LYNNIE | LYNNIE | | PTO | P | 4268408 |