GKKWORKS CONSTRUCTION SERVICES | B= | C | 11/24/2014 | All other required Final inspections are complete. (This is a computer generated result) | JOND | JOND | | B= | C | 4859132 |
GKKWORKS CONSTRUCTION SERVICES | B= | P | 11/13/2014 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977). | JOND | JOND | | B= | P | 4853234 |
GKKWORKS CONSTRUCTION SERVICES | BFN | P | 05/30/2014 | new contact is marvin carr 371-5710/ retaining wall B- repair modifications ok | BLAKE | BLAKE | | BFN | P | 4748788 |
GKKWORKS CONSTRUCTION SERVICES | BFT | C | 05/22/2014 | far west end of retaining wall ok | JOND | JOND | | BFT | C | 4743680 |
GKKWORKS CONSTRUCTION SERVICES | BFT | P | 05/15/2014 | retaining in back the southeast half ok | JOND | JOND | | BFT | P | 4739214 |
GKKWORKS CONSTRUCTION SERVICES | BSP | T | 04/18/2014 | PAID (REC#1192307) PLAN SPLICE FEE: $50 by: MICHAEL for Construction: Repair retaining wall - add details | MICHAELA | MICHAELA | | BSP | T | 4722645 |
GKKWORKS CONSTRUCTION SERVICES | BE | L | 01/14/2014 | Renewed at 1/14/2014 10:46:43 AM | MINDY | MINDY | | BE | L | 4671305 |
LUDVIK ELECTRIC CO. | BSP | T | 08/30/2013 | PAID (REC#1158387) PLAN SPLICE FEE: $100 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 4596117 |
RK MECHANICAL, LLC | BSP | T | 06/24/2013 | PAID (REC#1142148) PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: Revised mechanical pages | RUSSELL | RUSSELL | | BSP | T | 4548842 |
RK MECHANICAL, LLC | BSP | T | 06/20/2013 | PAID (REC#1142148) PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: new splice pages see clouds | TCRIPPEN | TCRIPPEN | | BSP | T | 4547431 |
GKKWORKS CONSTRUCTION SERVICES | BSP | T | 06/20/2013 | PAID (REC#1158386) PLAN SPLICE FEE: $50 by: MICHAEL for Construction: New doors and control room | MICHAELA | MICHAELA | | BSP | T | 4547297 |
GKKWORKS CONSTRUCTION SERVICES | BE | L | 06/19/2013 | Renewed at 6/19/2013 9:17:17 AM | NELIDA | NELIDA | | BE | L | 4545755 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 10/24/2012 | see sheet A115- storage room 285
| BLAKE | BLAKE | | BFR | P | 4407967 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 10/09/2012 | see plans for wall framing | JOND | JOND | | BFR | P | 4397922 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 10/02/2012 | partial ups room 168d see sheet a111 | BLAKE | BLAKE | | BFR | P | 4393290 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 09/19/2012 | partial- met with mike- see sheet A111- ODS storage rm 168B | BLAKE | BLAKE | | BFR | P | 4385306 |
GKKWORKS CONSTRUCTION SERVICES | BFD | P | 09/10/2012 | met with mike rogers- 2 sections of drain inspected- see plans sheet | BLAKE | BLAKE | | BFD | P | 4378358 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 08/09/2012 | P3 wall framing at plum wall 2nd floor grid 10.9 ; line b through f.5 approved plans sheet A115 | DANF | DANF | | BFR | P | 4358423 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 07/27/2012 | see pages A111 and A115---wall between mech rm 151 and storage rm 152, also wall between NEC 1A and mech rm 288 | BLAKE | BLAKE | | BFR | P | 4350010 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 07/16/2012 | channel installed on wall at 6 line grid lines A-E | DANF | DANF | | BFR | P | 4342095 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 07/13/2012 | met with mike rogers 651-8041/ see approved plans sheet A115/ room NEC 1A, column line G between A and E- ok to insulate, recall once channel installed | BLAKE | BLAKE | | BFR | P | 4341339 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 07/03/2012 | 4 door frame framing noted on approved plans sheet A111 | DANF | DANF | | BFR | P | 4335493 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 06/21/2012 | walls as noted on approved plans sheet A111; battery rooms B1 #157 and B2, #158; still need the door installed and framing at riser pipe see plans | DANF | DANF | | BFR | P | 4330035 |
LUDVIK ELECTRIC CO. | E= | C | 09/10/2014 | FIRE ALARM INSPECTION: | MIKEC | MIKEC | | E= | C | 4812975 |
LUDVIK ELECTRIC CO. | EE | L | 09/10/2014 | Renewed at 9/10/2014 7:56:34 AM | MATTHEW | MATTHEW | | EE | L | 4812974 |
LUDVIK ELECTRIC CO. | E= | C | 10/30/2013 | PHASE A | MIKEC | MIKEC | | E= | C | 4632873 |
LUDVIK ELECTRIC CO. | ER | P | 05/23/2013 | GENERATOR BLDG | MIKEC | MIKEC | | ER | P | 4529937 |
LUDVIK ELECTRIC CO. | E= | P | 05/09/2013 | STORAGE "B"-174, STORAGE "A"- 173, UPS RM "A"-171, UPS "B"- 171 | MIKEC | MIKEC | | E= | P | 4520872 |
LUDVIK ELECTRIC CO. | ER | P | 04/30/2013 | partial finals includes fire alarm see plans | MIKEC | MIKEC | | ER | P | 4514416 |
LUDVIK ELECTRIC CO. | ER | P | 04/22/2013 | MECH. ROOMS | MIKEC | MIKEC | | ER | P | 4510241 |
LUDVIK ELECTRIC CO. | ER | P | 04/12/2013 | SEE PLANS | MIKEC | MIKEC | | ER | P | 4504988 |
LUDVIK ELECTRIC CO. | EP | P | 04/01/2013 | uss1 end sections of gear | BRET | BRET | | EP | P | 4497805 |
LUDVIK ELECTRIC CO. | ER | P | 03/25/2013 | regulators and medium voltage gear | BRET | BRET | | ER | P | 4493208 |
LUDVIK ELECTRIC CO. | ER | P | 03/19/2013 | progress inspection see plans | MIKEC | MIKEC | | ER | P | 4489627 |
LUDVIK ELECTRIC CO. | ER | P | 03/19/2013 | FIRE ALARM INSPECTION: progress inspection see plans | MIKEC | MIKEC | | ER | P | 4489623 |
LUDVIK ELECTRIC CO. | ES | C | 03/11/2013 | Commercial Service: 400 AMP 35K V OK TO ENERGIZE-----NOTE CONTRACTOR WOULD LIKE TO COORDINATE THE POWERING UP OF THE SERVICE ALSO ENGINEER HAS 400 AMP FUSES REQUIRED CONTRACTOR IS INSTALLING 300 AMP FOR NOW FOR TESTING PURPOSES SO A SHUT DOWN WILL BE REQUIRED TO INSTALLED 400 AMP FUSES AT A LATER DATE---- | TIMA | TIMA | | ES | C | 4484439 |
LUDVIK ELECTRIC CO. | ES | R | 03/06/2013 | NEED ENGINEER LETTER FOR CHANGE TO 300 AMP FUSES FROM 400 AMP AS PER DRAWINGS,NEED TO CHECK ABOUT VAULT GROUNDING,NEED ADDRESS TAG | TIMA | TIMA | | ES | R | 4482555 |
LUDVIK ELECTRIC CO. | EUG | P | 02/14/2013 | PROGRESS INSPECTION AND QUESTIONS ABOUT SERVICE INSPECTION | TIMA | TIMA | | EUG | P | 4472130 |
LUDVIK ELECTRIC CO. | EUG | P | 01/29/2013 | SEE PLANS | MIKEC | MIKEC | | EUG | P | 4463530 |
LUDVIK ELECTRIC CO. | ER | P | 01/04/2013 | progress inspection | MIKEC | MIKEC | | ER | P | 4449281 |
LUDVIK ELECTRIC CO. | EUG | P | 12/21/2012 | see plans | MIKEC | MIKEC | | EUG | P | 4444993 |
LUDVIK ELECTRIC CO. | ER | P | 12/05/2012 | see plans | MIKEC | MIKEC | | ER | P | 4434189 |
LUDVIK ELECTRIC CO. | ER | P | 11/14/2012 | FIRE ALARM INSPECTION: partial final room 157 | MIKEC | MIKEC | | ER | P | 4422127 |
LUDVIK ELECTRIC CO. | ER | P | 11/14/2012 | partial final battery room 157 two strings | MIKEC | MIKEC | | ER | P | 4422126 |
LUDVIK ELECTRIC CO. | ER | P | 11/06/2012 | partial final battery room | MIKEC | MIKEC | | ER | P | 4417077 |
LUDVIK ELECTRIC CO. | EUG | P | 10/31/2012 | e119 see plans | BRET | BRET | | EUG | P | 4413472 |
LUDVIK ELECTRIC CO. | ER | P | 10/18/2012 | see plans | MIKEC | MIKEC | | ER | P | 4404551 |
LUDVIK ELECTRIC CO. | ER | P | 10/02/2012 | walls see plans | MIKEC | MIKEC | | ER | P | 4393686 |
LUDVIK ELECTRIC CO. | ER | P | 09/24/2012 | battery rooms see plans | MIKEC | MIKEC | | ER | P | 4388013 |
LUDVIK ELECTRIC CO. | EUG | P | 09/11/2012 | see plans | MIKEC | MIKEC | | EUG | P | 4379204 |
LUDVIK ELECTRIC CO. | EUG | P | 08/28/2012 | generator conduits | MIKEC | MIKEC | | EUG | P | 4370920 |
LUDVIK ELECTRIC CO. | EUG | P | 08/14/2012 | see plans | MIKEC | MIKEC | | EUG | P | 4361792 |
LUDVIK ELECTRIC CO. | ER | P | 08/09/2012 | wall see plans | MIKEC | MIKEC | | ER | P | 4358936 |
LUDVIK ELECTRIC CO. | EUG | P | 07/31/2012 | no access to permit | MIKEC | MIKEC | | EUG | P | 4352555 |
LUDVIK ELECTRIC CO. | ER | P | 07/27/2012 | see plans | MIKEC | MIKEC | | ER | P | 4350449 |
LUDVIK ELECTRIC CO. | EUG | P | 07/25/2012 | see plans | MIKEC | MIKEC | | EUG | P | 4348753 |
LUDVIK ELECTRIC CO. | ER | P | 07/25/2012 | wall | MIKEC | MIKEC | | ER | P | 4348752 |
LUDVIK ELECTRIC CO. | EUG | P | 07/18/2012 | see plans | MIKEC | MIKEC | | EUG | P | 4344094 |
LUDVIK ELECTRIC CO. | ER | P | 07/03/2012 | SEE HIGHLIGHTED PLANS | MIKEC | MIKEC | | ER | P | 4335911 |
LUDVIK ELECTRIC CO. | ES | P | 04/30/2012 | Commercial Service: pre release | MIKEC | MIKEC | | ES | P | 4304102 |
RK MECHANICAL, LLC | H= | C | 10/01/2014 | MECHANICAL FINAL COMPLETE. FINAL TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4826900 |
RK MECHANICAL, LLC | H= | P | 09/30/2014 | ENGINEER'S LETTER REGARDING DAMPERS IN UPS ROOM 168D RECEIVED AND SCANNED. FOR FINAL PROVIDE TEST AND BALANCE REPORT FOR TRANSPORT A AND B ROOMS. | NANCY | NANCY | | H= | P | 4825220 |
RK MECHANICAL, LLC | H= | P | 06/30/2014 | TEST AND BALANCE REPORT RECEIVED 5/30/14. STILL NEED READINGS FOR TRANSPORT A AND B ROOMS. NOTE: THIS INSPECTION NOTE ACCIDENTLY PUT ON PERMIT I48398. MOVED ENTRY TO THIS PERMIT 6/30/14. | NANCY | NANCY | | H= | P | 4768321 |
RK MECHANICAL, LLC | H= | P | 02/11/2014 | MECHANICAL FINAL OK PENDING ANSWERS REGARDING UPS ROOM CEILING RADIATION DAMPERS, RECEIPT OF TEST AND BALANCE REPORT. RETAINING ANGLES ON EF19 ALL OK. | NANCY | NANCY | | H= | P | 4685204 |
RK MECHANICAL, LLC | H= | P | 01/23/2014 | OK TO INSTALL RETAINING ANGLES ON EF19 FIRE/SMOKE DAMPERS IN BLOCK WALL. QUESTION REGARDING TYPE OF FIRE SUPPRESSION SYSTEM BEING USED IN UPS ROOM. CEILING RADIATION DAMPER IN UPS ROOM CEILING WILL ONLY CLOSE IF THERE IS ENOUGH HEAT TO MELT FUSIBLE LINK, WILL NOT CLOSE UPON ACTIVATION OF SUPPRESSION SYSTEM. LABEL ALL FIRE DAMPER ACCESS DOORS. LABEL ALL EQUIPMENT. PROVIDE TEST AND BALANCE REPORT. NOTE: CRAH131A INSTALLED AND COMPLETE. PIPING PART OF JOB ALL COMPLETE. TRANSPORT A AND B COMPLETE. | NANCY | NANCY | | H= | P | 4676843 |
RK MECHANICAL, LLC | HD | C | 01/23/2014 | | NANCY | NANCY | | HD | C | 4676840 |
RK MECHANICAL, LLC | H= | P | 09/30/2013 | RELIEF HOODS ON ROOF ALL OK. | NANCY | NANCY | | H= | P | 4613267 |
RK MECHANICAL, LLC | HD | P | 09/30/2013 | ROOM 168: PROVIDE INSTALLATION INSTRUCTIONS FOR CEILING RADIATION DAMPERS. UPS ROOM: STILL NEED TO COMPLETE EF19 AND FIRE/SMOKE DAMPERS. CRAH31A: STILL NEEDS TO BE INSTALLED. TRANSPORT A AND B: STILL NEEDS INSPECTION. | NANCY | NANCY | | HD | P | 4613260 |
RK MECHANICAL, LLC | HD | P | 09/27/2013 | CANCELED FOR TODAY. RESCHEDULED FOR MONDAY. | NANCY | NANCY | | HD | P | 4611891 |
RK MECHANICAL, LLC | HD | P | 08/27/2013 | HALLWAY 270: OK FOR ANGLES ON ALL FIRE/SMOKE DAMPERS. | NANCY | NANCY | | HD | P | 4593319 |
RK MECHANICAL, LLC | H= | P | 08/13/2013 | GENERATOR BUILDING COMPLETE. | NANCY | NANCY | | H= | P | 4583688 |
RK MECHANICAL, LLC | HD | P | 07/31/2013 | FAN COIL UNIT 13: OK TO WRAP SUPPLY/RETURN DUCTS ABOVE CEILING ROOM 168B (OPS CONTROL). STILL NEED ONE FITTING AT UNIT AND DRAIN PAN. NEED REVISED/APPROVED PRINTS SHOWING FCU13 ADDEDTO ORIGINAL JOB. | NANCY | NANCY | | HD | P | 4575204 |
RK MECHANICAL, LLC | H= | P | 07/17/2013 | SEE RECORD OF TEST DATED 7-17-13. FINAL INSPECTION OF CHILLED WATER PIPING, PIPING TO EQUIPMENT, CONDENSATE DRAINS ETC. COMPLETE PIPING TO CRAH 31A WHEN UNIT IS SET IN PLACE IN SWITCH GEAR ROOM. COMPLETE ALL LABELING PER VERIZON'S FINAL DECISION. | NANCY | NANCY | | H= | P | 4565080 |
RK MECHANICAL, LLC | HD | P | 06/13/2013 | 3-FSD'S IN UPS ROOM B #172 OK FOR ANGLES, BREAKAWAYS OK-- 3 FSD'S IN UPS ROOM #171 OK FOR ANGLES, STILL NEED TO CHECK BREAKAWAYS.--CORRIDOR #150 FCU'S 4 AND 5 OK, CHECK ANGLES AND CONDENSATE TERMINATIONS AT FINAL. EF-19 FAN AND DUCT OK THRU CORRIDOR #153 | ROBERTV | ROBERTV | | HD | P | 4542909 |
RK MECHANICAL, LLC | HWP | C | 05/07/2013 | SEE RECORD OF TEST FOR 5/7/13. 55 LB ( BUILDING WORKING PRESSURE) TEST OK ON CHILLED WATER SUPPLY/RETURN, COMPLETE MAIN LOOP ON BUILDING SIDE. OK TO COMPLETE INSULATION. FOR FINAL NEED TO SEE LATERALS, CONDENSATE ETC. | NANCY | NANCY | | HWP | C | 4518666 |
RK MECHANICAL, LLC | HWP | P | 05/01/2013 | SEE RECORD OF TEST FOR 5/1/13. 100 LB TEST OK ON PRIMARY SYSTEM, PUMP ROOM 151 AND UNDERGROUND TO AIR COOLED CHILLER PAD. OK TO INSULATE. | NANCY | NANCY | | HWP | P | 4515212 |
RK MECHANICAL, LLC | HWP | P | 04/30/2013 | NOT READY FOR TEST. ALREADY RESCHEDULED FOR TOMORROW. | NANCY | NANCY | | HWP | P | 4514298 |
RK MECHANICAL, LLC | HD | P | 03/18/2013 | MECHANICAL ROOM 288: OK TO WRAP FINAL OUTSIDE AIR DUCT TO CRAH UNIT | NANCY | NANCY | | HD | P | 4488756 |
RK MECHANICAL, LLC | HD | P | 03/11/2013 | ROOM 250: RELIEF DUCTS ALL OK. HALLWAY 149: FIRE/SMOKE DAMPERS AND ANGLES ALL OK. SUPPLY AND OUTSIDE AIR DUCTS OK. BY FINAL LABEL ACCESS DOORS. MECH ROOM 143: OUTSIDE AIR OK, OK TO WRAP. ALL OTHER DUCTS OK EXCEPT STILL NEED TO SEE TIE IN OF SUPPLY AIR TO AHU4. UPS ROOM: PROVIDE INSTALLATION INSTRUCTIONS FOR CEILING RADIATION DAMPERS. PROVIDE ANSWERS TO RFI'S REGARDING THIS ROOM. MECH ROOM 168D (NEXT TO UPS ROOM): TWO FAN COILS, SUPPLY AND RETURN DUCTS OK, OK TO WRAP DUCTS. | NANCY | NANCY | | HD | P | 4484547 |
RK MECHANICAL, LLC | HWP | P | 01/31/2013 | SEE RECORD OF TEST FOR 1/31/13. ROOM 288, CHILLED WATER SUPPLY/RETURN TO CRAH UNITS 5 A AND B, 6 A AND B AND 7 B: FIVE 80 LB TESTS OK. OK TO INSULATE ALL. | NANCY | NANCY | | HWP | P | 4464592 |
RK MECHANICAL, LLC | HWP | P | 01/30/2013 | SEE RECORD OF TEST FOR 1/30/13. ROOM 288, CHILLED WATER SUPPLY/RETURN TO CRAH UNITS. 19 TOTAL TESTS. FOURTEEN 80 LB TESTS OK. RETEST UNITS 5 A AND B, 6 A AND B AND 7 B. | NANCY | NANCY | | HWP | P | 4463759 |
RK MECHANICAL, LLC | HD | P | 01/28/2013 | HALLWAY 270: FRAMING FOR 4 FIRE/SMOKE DAMPERS OK, OK TO COVER AND INSTALL DAMPERS, STILL NEED TO SEE CLEARANCES BEFORE ANGLES ARE INSTALLED. MECHANICAL ROOM 269: SUPPLY, RETURN, RELIEF DUCT FIRE/SMOKE DAMPERS THROUGH FLOOR OK, OK TO INSTALL 16 GAUGE ANGLES. SUPPLY,RELIEF, RETURN AIR DUCTS OK, OK TO WRAP MEDIUM AND LOW PRESSURE DUCTS FOR VAV 36. | NANCY | NANCY | | HD | P | 4461885 |
RK MECHANICAL, LLC | HWP | P | 01/22/2013 | 100 LB TEST OK ON UNDERGROUND CHILLED WATER SUPPLY AND RETURN FROM TURN UP AT OUTSIDE OF BUILDING TO AIR COOLED CHILLER PAD. OK TO COVER. | NANCY | NANCY | | HWP | P | 4457672 |
RK MECHANICAL, LLC | HD | P | 01/02/2013 | MECHANICAL ROOM 288: OUTSIDE AIR/MIXING BOX AND DUCTS TO TOP OF ALL CRAH UNITS OK, OK TO WRAP. | NANCY | NANCY | | HD | P | 4447544 |
RK MECHANICAL, LLC | HD | P | 11/29/2012 | HALLWAY 149: SPACING AROUND FIRE/SMOKE DAMPERS OK, OK FOR ANGLES, INSTALL WIDE ANGLES WHERE NEEDED. FIRE/SMOKE DAMPERS FROM ROOM 168 TO UPS ROOM, SPACING AROUND DAMPERS OK. INSTALL WIDE ANGLES WHERE NEEDED. CUT OUT UNISTRUT WHERE NEEDED. ROOM 168: SUPPLY AIR OK. | NANCY | NANCY | | HD | P | 4430885 |
RK MECHANICAL, LLC | HD | P | 10/19/2012 | CANCELED BY CONTRACTOR. | NANCY | NANCY | | HD | P | 4405131 |
RK MECHANICAL, LLC | HD | P | 10/18/2012 | QUESTION REGARDING PROTECTION OF UPS ROOM CEILING. DAMPERS NOT LISTED FOR CEILING INSTALLATION, ONLY WALL AND FLOOR. NEED ANSWER TO RFI REGARDING WHERE PROTECTION OF UPS ROOM IS TO BE, EITHER AT WALL OR CEILING AND IF SECOND UPS WALL NEEDS TO BE BUILT TO DECK. NOTE: SEE FIRE/SMOKE DAMPERS 111 AND 112. | NANCY | NANCY | | HD | P | 4404544 |
RK MECHANICAL, LLC | HWP | P | 10/17/2012 | SEE RECORD OF TEST FOR 10/17/12. TWO 100 LB TESTS OK ON SECONDARY CHILLED WATER SUPPLY AND RETURN IN HALLWAYS 150 AND 153 AND ROOM 152. OK TO INSULATE. | NANCY | NANCY | | HWP | P | 4403351 |
RK MECHANICAL, LLC | HD | P | 09/28/2012 | MECHANICAL ROOM 288: OK TO WRAP OUTSIDE AIR DUCTS TO CRAH UNITS. | NANCY | NANCY | | HD | P | 4391601 |
RK MECHANICAL, LLC | HD | P | 09/27/2012 | CONTRACTOR WANTED INSPECTION TOMORROW. ALREADY RESCHEDULED. | NANCY | NANCY | | HD | P | 4390365 |
RK MECHANICAL, LLC | HWP | P | 08/31/2012 | WRONG INSPECTION CALLED IN, WANTED PLUMBING INSPECTION. | NANCY | NANCY | | HWP | P | 4373926 |
RK MECHANICAL, LLC | HD | P | 08/13/2012 | HALLWAY 149 OFF OF MECHANICAL ROOM 143: FRAMING FOR THREE FIRE/SMOKE DAMPERS OK. OK TO INSTALL DAMPERS, NEED TO SEE CLEARANCES. | NANCY | NANCY | | HD | P | 4360635 |
RK MECHANICAL, LLC | HD | P | 08/01/2012 | MECHANICAL ROOM 288: PARTIAL DUCTS INSTALLED AT CEILING, OK TO WRAP. | NANCY | NANCY | | HD | P | 4353089 |
RK MECHANICAL, LLC | HD | P | 07/27/2012 | BATTERY ROOMS 157, 158: CLEARANCE OK ON SIX DAMPERS, OK FOR ANGLES. BATTERY ROOM 157 INTO HALLWAY 153: REMOVE ANGLES FROM ONE SIDE TO VERIFY CLEARANCES. | NANCY | NANCY | | HD | P | 4350153 |
RK MECHANICAL, LLC | HD | P | 07/20/2012 | UPS ROOMS A AND B: TWO FIRE/SMOKE DAMPER FRAMES OK. OK TO INSTALL DAMPERS, NEED TO SEE CLEARANCES BEFORE ANGLES ARE INSTALLED. | NANCY | NANCY | | HD | P | 4345502 |
RK MECHANICAL, LLC | HD | P | 07/19/2012 | PROPERLY FRAME TWO FIRE/SMOKE DAMPERS. | NANCY | NANCY | | HD | P | 4344676 |
RK MECHANICAL, LLC | HD | P | 07/18/2012 | CANCELED BY CONTRACTOR. ALREADY RESCHEDULED FOR TOMORROW. | NANCY | NANCY | | HD | P | 4343923 |
RK MECHANICAL, LLC | HWP | P | 07/12/2012 | SEE RECORD OF TEST FOR 7/12/12. 100 LB TEST OK ON HOT WATER SUPPLY/RETURN, 6 INCH, 4 INCH AND 2 INCH PIPING THROUGH HALLWAYS 150 AND 153, ROOMS 151, 159 AND 160. OK TO INSULATE ALL PIPING UNDER TEST. | NANCY | NANCY | | HWP | P | 4340559 |
RK MECHANICAL, LLC | HD | P | 06/22/2012 | BATTERY ROOM 157 INTO HALLWAY 153: TWO FIRE/SMOKE DAMPER FRAMING OK. OK TO INSTALL DAMPERS. | NANCY | NANCY | | HD | P | 4330797 |
RK MECHANICAL, LLC | HD | P | 06/20/2012 | BATTERY ROOMS 157, 158: FRAMING FOR SIX FIRE DAMPERS OK. OK TO INSTALL DAMPERS, STILL NEED TO SEE CLEARANCES BEFORE ANGLES ARE INSTALLED. QUESTION REGARDING EXHAUST DUCT PENETRATING WALL TYPE P2 BETWEEN BATTERY ROOMS 157 AND 158. | NANCY | NANCY | | HD | P | 4329472 |
RK MECHANICAL, LLC | HD | P | 06/19/2012 | ROOMS 157, 158: CLOSE UP HOLES IN FIRE DAMPER FRAMING. STUD FRAMING OK. | NANCY | NANCY | | HD | P | 4328723 |
RK MECHANICAL, LLC | P= | C | 09/13/2013 | phase 1 complete. phase 2 is under permit I19967. | DICK | DICK | | P= | C | 4604224 |
RK MECHANICAL, LLC | PTO | P | 05/08/2013 | 4" NON-POTABLE IN EXISTING BUILDING TO VALVE OK -- NON-POTABLE IN GENERATOR BUILDING OK -- NEED STICKERS / LABELS FOR FINAL | LEE | LEE | | PTO | P | 4520270 |
RK MECHANICAL, LLC | PB | P | 03/26/2013 | NEW F.D IN HALLWAY O.K, SEE PLANS | JOEL | JOEL | | PB | P | 4493773 |
RK MECHANICAL, LLC | PTO | P | 02/04/2013 | 2-f.d in hallway 150 | JOEL | JOEL | | PTO | P | 4465791 |
RK MECHANICAL, LLC | PB | P | 01/22/2013 | EMERGENCY F.D IN HALL WAY O.K | JOEL | JOEL | | PB | P | 4457627 |
RK MECHANICAL, LLC | PB | P | 10/05/2012 | INSPECTED UNDERGROUND 4" COPPER TO GENERATOR BUILDING | LEE | LEE | | PB | P | 4396452 |
RK MECHANICAL, LLC | P= | P | 09/05/2012 | WATER ENTRY O.K | JOEL | JOEL | | P= | P | 4375679 |
RK MECHANICAL, LLC | PTO | P | 08/14/2012 | CONSULTATION | LEE | LEE | | PTO | P | 4361839 |
RK MECHANICAL, LLC | PTO | P | 07/18/2012 | NON POTABLE H20 O.K | JOEL | JOEL | | PTO | P | 4343691 |
RK MECHANICAL, LLC | PTO | P | 07/13/2012 | 151,152,157,158,288,153 DWV O.K | JOEL | JOEL | | PTO | P | 4341154 |
RK MECHANICAL, LLC | PWO | C | 07/09/2012 | water entry. | MARTY | MARTY | | PWO | C | 4337807 |
RK MECHANICAL, LLC | PTO | P | 05/11/2012 | 4'' and 1- 1/4'' domestic h2o o.k see plans | JOEL | JOEL | | PTO | P | 4309639 |
RK MECHANICAL, LLC | PB | P | 04/30/2012 | revise plans to show new work, test o.k for storm and dwv west side | JOEL | JOEL | | PB | P | 4303538 |