MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | B= | C | 02/14/2013 | All other required Final inspections are complete. (This is a computer generated result) | JOHNP | JOHNP | | B= | C | 4471778 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | B= | P | 08/31/2012 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: kmagargal@springsgov.com or 385-5060), CONTRACT MECHANICAL SVC INC Plumbing Final Inspection is not Completed yet. Plumbing final | JOHNP | JOHNP | | B= | P | 4374057 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | C | 08/31/2012 | | JOHNP | JOHNP | | BFR | C | 4374025 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BLA | C | 08/16/2012 | Soffits | JOHNP | JOHNP | | BLA | C | 4363403 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BIN | C | 07/26/2012 | | JOHNP | JOHNP | | BIN | C | 4349078 |
MURPHY CONSTRUCTORS OF COLORADO SPRINGS, INC. | BFR | P | 07/24/2012 | Walls & drops OK | JOHNP | JOHNP | | BFR | P | 4347691 |
JUST JENN INC | E= | C | 08/24/2012 | RTU's ok | GARYL | GARYL | | E= | C | 4368701 |
JUST JENN INC | ER | P | 08/21/2012 | all ceilings | GARYL | GARYL | | ER | P | 4365816 |
JUST JENN INC | ES | C | 08/01/2012 | Commercial Service: 600 amp., 4/w | GARYL | GARYL | | ES | C | 4352809 |
JUST JENN INC | ES | R | 07/30/2012 | need water tight fittings on conduits above the switch gear | GARYL | GARYL | | ES | R | 4350813 |
JUST JENN INC | ER | P | 07/23/2012 | walls and hard lids ok | JOSEPH | JOSEPH | | ER | P | 4346357 |
JUST JENN INC | ESL | P | 06/15/2012 | 4-floor recept's | GARYL | GARYL | | ESL | P | 4326879 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 08/30/2012 | TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4373482 |
CONTRACT MECHANICAL SVC INC | H= | C | 08/29/2012 | GAS FINAL OK. | NANCY | NANCY | | H= | C | 4371876 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 08/28/2012 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4370843 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 08/27/2012 | REMOVE ALL FIRE CAULKING FROM AROUND FIRE DAMPERS. COMPLETE WATER HEATER T&P AND CONDENSATE DRAIN. PROVIDE LADDER FOR ROOF ACCESS. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4370291 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 08/20/2012 | ENSURE ALL DAMPER ANGLES ARE INSTALLED AND CEILING IS LABELED, WATER HEATER TO BE SET AND VENTED, DID LOOK AT VENT ABOVE HARD LID AND OK. DETECTORS ARE INSTALLED. NEED ROOF INSPECTION AND BALANCE REPORT AS WELL. | JON | JON | | H= | P | 4365598 |
CONTRACT MECHANICAL SVC INC | H16 | C | 08/16/2012 | WATER HEATER PVC VENT TO BE ISOLATED FROM RETURN AIR PLENUM. | NANCY | NANCY | | H16 | C | 4363166 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 08/16/2012 | INSTALL SMOKE DETECTORS, INSTALL FIRE DAMPER ANGLES, COMPLETE MINI-SPLIT CONDENSATE DRAIN. DRYER VENT CLEAN OUT ACCESS? PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4363163 |
CONTRACT MECHANICAL SVC INC | HC | C | 07/31/2012 | RELEASE METER | LYNNS | LYNNS | | HC | C | 4351883 |
CONTRACT MECHANICAL SVC INC | HI | C | 07/31/2012 | 10# TEST AND DESIGN OK. | LYNNS | LYNNS | | HI | C | 4351878 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 07/27/2012 | Ok to wrap. fire damper framing ok on five dampers. | JON | JON | | HD | P | 4350472 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HV | C | 07/27/2012 | bath exhaust | JON | JON | | HV | C | 4350470 |
CONTRACT MECHANICAL SVC INC | P= | C | 09/04/2012 | | LYNNIE | LYNNIE | | P= | C | 4374731 |
CONTRACT MECHANICAL SVC INC | P= | R | 08/31/2012 | WAQIVE TRIP FEE, NOT READY | JOEL | JOEL | | P= | R | 4373720 |
CONTRACT MECHANICAL SVC INC | PTO | C | 07/20/2012 | | LYNNIE | LYNNIE | | PTO | C | 4345378 |
CONTRACT MECHANICAL SVC INC | PTO | P | 07/19/2012 | TESTS OKAY--FIRST SINK INSIDE FRONT LACKS SCREW PROTECTION ON BOTH DWV AND WATER LINES--REST OKAY | LYNNIE | LYNNIE | | PTO | P | 4344818 |
CONTRACT MECHANICAL SVC INC | PB | C | 06/11/2012 | | LYNNIE | LYNNIE | | PB | C | 4324360 |