GERALD H PHIPPS INC | B= | C | 12/17/2012 | | BLAKE | BLAKE | | B= | C | 4441916 |
GERALD H PHIPPS INC | B= | C | 12/17/2012 | | BLAKE | BLAKE | | B= | C | 4441913 |
GERALD H PHIPPS INC | BFR | C | 12/17/2012 | | BLAKE | BLAKE | | BFR | C | 4441912 |
GERALD H PHIPPS INC | BSP | T | 11/09/2012 | PAID (REC#1094607) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN NEW SPLICE PAGE RE ROUTED SUPPY AND RETURN LINES | TCRIPPEN | TCRIPPEN | | BSP | T | 4419823 |
GERALD H PHIPPS INC | BSP | P | 10/26/2012 | PLAN SPLICE: (No Fee) by: SHELLEY for Construction: revised rated walls around break/corridor | SHELLEY | SHELLEY | | BSP | P | 4410322 |
NIELSEN MECHANICAL CONTRACTORS, INC. | BSP | P | 10/26/2012 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical: splice to add f/s/d | DALEH | DALEH | | BSP | P | 4410309 |
GERALD H PHIPPS INC | BSP | T | 10/26/2012 | PAID (REC#1090468) ADDITIONAL PLAN REVIEW TIME: $50 From: SHELBY | SHELBY | SHELBY | | BSP | T | 4410274 |
GERALD H PHIPPS INC | BSP | T | 10/11/2012 | PAID (REC#1090468) PLAN SPLICE FEE: $50 by: SHELLEY for Construction: changed horizontal assembly for break/hall area | SHELLEY | SHELLEY | | BSP | T | 4399905 |
GERALD H PHIPPS INC | BFR | P | 10/11/2012 | met with tony 466-7370 walls ok, need to inspect ceiling/lids | BLAKE | BLAKE | | BFR | P | 4399744 |
GERALD H PHIPPS INC | BSP | T | 10/05/2012 | PAID (REC#1085424) PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 4396000 |
NIELSEN MECHANICAL CONTRACTORS, INC. | BSP | P | 10/05/2012 | PLAN SPLICE: (No Fee) by: DALEH for Mechanical: splice to clean up plan | DALEH | DALEH | | BSP | P | 4395974 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 12/04/2012 | FIRE ALARM INSPECTION: | CRAIGS | CRAIGS | | E= | C | 4433930 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | E= | C | 10/31/2012 | ceiling in basement break area OK --no fire alarm installed at this time | CRAIGS | CRAIGS | | E= | C | 4413351 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EP | C | 10/31/2012 | sub panel for new basement break area OK---- | CRAIGS | CRAIGS | | EP | C | 4413348 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 10/12/2012 | walls | BRET | BRET | | ER | P | 4400319 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | EE | C | 10/08/2012 | | MINDY | MINDY | | EE | C | 4433024 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | R | 04/09/2012 | cancelled at time of call ahead wrong permit number | BRET | BRET | | ER | R | 4433023 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 01/12/2012 | inspections of gen nameplates amps only gen 1 2255, gen 2 2255, gen 3 2255.3 and gen 4 2423.7 | BRET | BRET | | ER | P | 4433022 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 12/15/2011 | all conduit 2nd floor ok | BRET | BRET | | ER | P | 4433021 |
GUARANTEE ELECTRICAL CONTRACTING, LLC | ER | P | 12/13/2011 | all conduits except 2nd floor. install ground bushings on gen conduits. conductors installed in control conduits only. | BRET | BRET | | ER | P | 4433020 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | C | 12/14/2012 | TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4440958 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 12/12/2012 | HOT WATER PIPING FINAL OK. | NANCY | NANCY | | H= | C | 4438413 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | C | 12/12/2012 | HOT WATER PIPING FINAL OK. | NANCY | NANCY | | H= | C | 4438402 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 12/12/2012 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4438401 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 12/11/2012 | PROPERLY SUPPORT HOT WATER SUPPLY/RETURN LINES FROM BALL VALVES TO VAV. SUPPORT LINES FROM STRUCTURE NOT CONDUIT. BALL VALVE DOES NOT COMPLETELY OPEN DUE TO HANGER. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4437633 |
OLSON PLUMBING & HEATING COMPANY | HWP | C | 12/11/2012 | 100 LB TEST OK ON HOT WATER SUPPLY/RETURN PIPING TO BREAK ROOM VAV. OK TO FILL. OK TO INSULATE. | NANCY | NANCY | | HWP | C | 4437629 |
NIELSEN MECHANICAL CONTRACTORS, INC. | H= | P | 10/30/2012 | BREAK ROOM: ABOVE CEILING ALL OK FOR DUCTS. STILL NEED TO SEE PIPING FOR NEW VAV. FIRE/SMOKE DAMPER CLEARANCES OK, OK TO INSTALL ANGLES. FIRE/SMOKE DAMPER FUNCTION OK. FOR FINAL COMPLETE PIPING TO NEW VAV, PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4411617 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | C | 10/26/2012 | BREAK ROOM: ROUGH ABOVE CEILING OK INCLUDING FLEX AND DIFFUSERS. OK TO WRAP ROUND SUPPLY. MAINTENANCE AREA: INSTALLATION ALL OK. FOR FINAL NEED ANGLES REMOVED ON ONE SIDE TO SEE DAMPER CLEARANCES. PIPE VAV. LABEL DAMPER ACCESS DOOR. HAVE APPROVED PRINTS ON SITE. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | HD | C | 4409762 |
NIELSEN MECHANICAL CONTRACTORS, INC. | HD | P | 10/19/2012 | FRAMING FOR TWO NEW FIRE/SMOKE DAMPERS OK. OK TO COVER. NEED TO SEE DAMPER CLEARANCE BEFORE ALL ANGLES ARE INSTALLED. QUESTION REGARDING EXISTING DUCT THROUGH NEW ONE HOUR RATED WALL. | NANCY | NANCY | | HD | P | 4405031 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | C | 12/14/2012 | | LYNNIE | LYNNIE | | P= | C | 4440439 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | R | 12/13/2012 | CALLED AHEAD--LEFT MESSAGE FOR ACCESS--NO CALL BACK | LYNNIE | LYNNIE | | P= | R | 4439331 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | C | 10/15/2012 | WE NEED A POC NUMBER FOR ACCESS | LYNNIE | LYNNIE | | PTO | C | 4401342 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | P | 10/12/2012 | DWV AND H2O LOST TEST | JOEL | JOEL | | PTO | P | 4400329 |
HARMON - BONDED PLUMBING & HEATING, INC. | PB | P | 10/05/2012 | STILL NEED THRU WALL AND TIE IN, REST O.K | JOEL | JOEL | | PB | P | 4395726 |