MEMORIAL HOSPITAL | H01 | C | 11/08/2023 | ANNUAL 11/22 -- OTIS W/ TKE SERVICE -- EMERGENCY PHONE IS NONFUNCTIONAL -- COUNTERWEIGHT RUNBY IS 3", MINIMUM ALLOWABLE RUNBY IS 6" -- COVER ABOVE CONTROLLER IN MACHINE ROOM IS LEFT OFF AND WIRES ARE EXPOSED CAUSING A POTENTIAL ELECTRICAL HAZARD -- PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL EMERGENCY PHONES ARE FIXED -- NOTE: ANNUAL TRACTION SAFETY TEST IS DUE BY THE END OF THE MONTH (Receipt #2006354) | BENH | BENH | | H01 | C | 7912773 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2023 | HO2 -- ANNUAL 11/22 -- OTIS W/ TKE SERVICE -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7754396 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - "ELEVATOR EMERGENCY POWER" INDICATOR AT THE DESIGNATED LEVEL IS NON-FUNCTIONAL. EMERGENCY OPERATIONS ON ELEVATOR STATUS PANEL IN FIRE COMMAND CENTER ARE NON-FUNCTIONAL........ THERE WILL NOT BE A COMPLIANCE DATE FOR THESE ITEMS PENDING FURTHER DIRECTION FROM THE STATE OF COLORADO DEPARTMENT OF PUBLIC SAFETY THAT IS PRESENTLY IN PROCESS OF DISCUSSION AND DECISION REGARDING REQUIREMENT FOR ELEVATOR OPERATIONS ON GENERATOR POWER. | ROBERTV | ROBERTV | | HE16 | C | 7657020 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2022 | WITNESSED AT HO1 (Receipt #1914026) | BENH | BENH | | H01 | C | 7580284 |
MEMORIAL HOSPITAL | H06 | C | 11/11/2022 | WITNESSED 5 YEAR TEST W/ TKE -- EMERGENCY PHONE NONFUNCTIONAL --BELT MONITOR IS NOT WORKING PROPERLY -- STILL NEED TO TEST GENERATOR POWER (Receipt #1914025) ITS belt monitor is working properly per discussion with mechanic | BENH | BENH | | H06 | C | 7580279 |
MEMORIAL HOSPITAL | H02 | C | 05/24/2022 | H02 -- 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. CHECK PREVIOUS LISTED ITEMS AT WITNESS TEST | ROBERTV | ROBERTV | | H02 | C | 7387781 |
MEMORIAL HOSPITAL | H01 | C | 11/11/2021 | 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. CHECK BELT MONITOR AS IT IS FLASHING ABNORMALLY. (Receipt #1822136) | ROBERTV | ROBERTV | | H01 | C | 7173482 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 5/21 -- OTIS W/ TKE SERVICE. ELEVATOR EMERGENCY PHONE DOES NOT WORK WHEN CAB 110V CIRCUIT IS DISCONNECTED. | ROBERTV | ROBERTV | | H02 | C | 6980459 |
MEMORIAL HOSPITAL | H01 | C | 11/19/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/ TKE SERVICE. #2 AND #3 OR BELT MONITOR ARE FLASHING ABNORMALLY. NEED EMERGENCY PHONE TESTING LOGS ONSITE (Receipt #1730966) cat 1 1/21 | ROBERTV | ROBERTV | | H01 | C | 6781730 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2020 | 5YR 11/17--ANNUAL 12/19--OTIS W/ TKE SERVICE--HO2 | CALE | CALE | | H02 | C | 6585380 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2019 | 5YR 11/17--ANNUAL 12/18--OTIS W/ TKE SERVICE (Receipt #1644012) (Cat. 1 Performed 12/2019) | CALE | CALE | | H01 | C | 6397177 |
MEMORIAL HOSPITAL | H02 | C | 05/30/2019 | H02 -- 5YR 11/17 -- ANNUAL 12/18 -- ITEMS ADDRESSED PER TKE | ROBERTV | ROBERTV | | H02 | C | 6214121 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2018 | 5YR -- 11/17 -- OTIS W/ TKE SERVICE. #2 BELT ON MONITOR INDICATES REPLACEMENT IS NEEDED IMMEDIATELY, THIS NEEDS DIAGNOSED AS SOON AS POSSIBLE. REINSTALL COTTER PIN AT SAFETY LINKAGE BOLT FOR GOVERNOR ROPE ATTACHMENT. REQUIRED ANNUAL CATEGORY 1 TESTING DUE.......... FOLLOW UP SCHEDULED FOR 30 DAYS (Receipt #1559830)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 6038399 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2018 | 5 YEAR AND ANNUAL 11/17, OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 5851052 |
MEMORIAL HOSPITAL | H06 | C | 11/13/2017 | WITNESSED 5 YEAR SAFETY TEST. NO ISSUES (Receipt #1465304) | ERIC | ERIC | | H06 | C | 5682666 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2017 | ANNUAL INSPECTION AND 5 YEAR SAFETY TEST COMPLETED AT SAME TIME, ONE HOUR OF CREDIT WILL BE GIVEN FOR 5 YEAR TESTING (Receipt #1465303) | ERIC | ERIC | | H01 | C | 5682658 |
MEMORIAL HOSPITAL | H02 | C | 05/11/2017 | H02 - 5 YR CATEGORY 5 TESTING DUE 9/2017 | ROBERTV | ROBERTV | | H02 | C | 5503094 |
MEMORIAL HOSPITAL | H01 | C | 11/30/2016 | 5YR -9--25--OTIS --TKE SERVICE (Receipt #1385779) | JOHNW | JOHNW | | H01 | C | 5355928 |
MEMORIAL HOSPITAL | H02 | C | 05/25/2016 | 5 YEAR 9/12 OTIS. TKE SERVICE HO2 | ERIC | ERIC | | H02 | C | 5207951 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2015 | 5YR 9-12 OTIS (Receipt #1301576) | TOM | TOM | | H01 | C | 5088746 |
MEMORIAL HOSPITAL | H02 | C | 05/21/2015 | HO2 | JOHNW | JOHNW | | H02 | C | 4958503 |
MEMORIAL HOSPITAL | H01 | C | 11/29/2014 | 5YR 9-12 OTIS-TKE SERVICE (Receipt #1234595) | TOM | TOM | | H01 | C | 4861794 |
MEMORIAL HOSPITAL | H02 | C | 05/28/2014 | HO2--9--12--OTIS | JOHNW | JOHNW | | H02 | C | 4746685 |
MEMORIAL HOSPITAL | H01 | C | 11/19/2013 | 5YR 9-12-OTIS (Receipt #1168754) | TOM | TOM | | H01 | C | 4649577 |
MEMORIAL HOSPITAL | H02 | C | 05/13/2013 | 5YR 12-11-TKE-POST FLOOR DESIGNATION NUMBERS AT ALL LANDINGS / CLEAN PIT | TOM | TOM | | H02 | C | 4532080 |
MEMORIAL HOSPITAL | H01 | C | 11/13/2012 | 5YR 9-12-OTIS (Receipt #1097952) | TOM | TOM | | H01 | C | 4432155 |
MEMORIAL HOSPITAL | H06 | C | 09/04/2012 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1077367) | ERIC | ERIC | | H06 | C | 4378124 |