HI-POINT HOME BUILDERS, LLC | B= | C | 05/02/2013 | All other required Final inspections are complete. (This is a computer generated result) | JOND | JOND | | B= | C | 4516116 |
HI-POINT HOME BUILDERS, LLC | B= | P | 04/22/2013 | Additional Inspections Required: External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977). | JOND | JOND | | B= | P | 4509957 |
HI-POINT HOME BUILDERS, LLC | B= | P | 03/12/2013 | Additional Inspections Required: External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977). final grade West and East side of house -- Schedule a new Building Final when above items are complete. | JIMP | JIMP | | B= | P | 4485880 |
HI-POINT HOME BUILDERS, LLC | B= | R | 03/05/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977). smoke covers still on; guard rail not replaced; fire final not cleared; grade on both sides not corrected | JIMP | JIMP | | B= | R | 4482012 |
HI-POINT HOME BUILDERS, LLC | B= | R | 03/01/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: enijkamp@springsgov.com or 385-5977). remove covers from smokes; ladders in wells with bedrooms; final grade | JIMP | JIMP | | B= | R | 4480357 |
HI-POINT HOME BUILDERS, LLC | BIN | C | 12/18/2012 | Finished basement. Garage insulated with r19. Ceiling insulation at B=. Ok to rock. | ROGER | ROGER | | BIN | C | 4442746 |
HI-POINT HOME BUILDERS, LLC | BFR | C | 12/17/2012 | per Jim P. | JOND | JOND | | BFR | C | 4440991 |
HI-POINT HOME BUILDERS, LLC | BFR | R | 12/13/2012 | Do not insulate; add studs in walls where removed; block joist with walls above; strap bearing walls where mech., electrical, and plumbing was installed; engineers fix on colulmn not contunous; fasten firestop; firestop tv chase. | JIMP | JIMP | | BFR | R | 4439998 |
HI-POINT HOME BUILDERS, LLC | BSP | R | 12/07/2012 | no approved plans on site | JIMP | JIMP | | BSP | R | 4436611 |
HI-POINT HOME BUILDERS, LLC | BSP | P | 11/08/2012 | front porch framing for vault lid ok | JIMP | JIMP | | BSP | P | 4418507 |
HI-POINT HOME BUILDERS, LLC | BFI | C | 10/18/2012 | | JIMP | JIMP | | BFI | C | 4404292 |
HI-POINT HOME BUILDERS, LLC | BFD | C | 10/18/2012 | | JIMP | JIMP | | BFD | C | 4404290 |
HI-POINT HOME BUILDERS, LLC | BFN | C | 10/15/2012 | drain usable space; isolate pads and float walls; 5% grade at final; eufer ground installed | JIMP | JIMP | | BFN | C | 4401903 |
HI-POINT HOME BUILDERS, LLC | BFT | C | 10/10/2012 | | JIMP | JIMP | | BFT | C | 4399074 |
WINTERS ELECTRIC, INC. | E= | C | 02/25/2013 | | BRET | BRET | | E= | C | 4477034 |
WINTERS ELECTRIC, INC. | E= | R | 02/08/2013 | EXPOSE UFER,MASTER BEDROOM ARC FAULT WON'T SET,NEED BUFFET COUNTER IN DINING/KITCHEN TO HAVE COUNTER TOP LAYOUT 2' - 4',NEED DECK OUTLET ON UPSTAIRS DECK,NEED LOW VOLT LIGHTING INSTALLED IN KITCHEN TO VERIFY CLASS 1 XMR,NEED PAPER WORK FOR FRONT EXTERIOR FAN FOR DAMP LOCATION RATING,BREAKER LOCK FOR RANGE,NM CABLE WITH CORD CAP HANGING OUT OF WALL IN REC ROOM,-----A/C INSTALLED 30 AMP---- | TIMA | TIMA | | E= | R | 4469316 |
WINTERS ELECTRIC, INC. | ES | C | 12/06/2012 | Residential Underground: new 200 amp service | MIKEC | MIKEC | | ES | C | 4435696 |
WINTERS ELECTRIC, INC. | ER | C | 12/06/2012 | | MIKEC | MIKEC | | ER | C | 4435676 |
GENE'S HEATING AND AIR LLC | H= | C | 02/25/2013 | CORRECTIONS MADE | DAVIDH | DAVIDH | | H= | C | 4476623 |
GENE'S HEATING AND AIR LLC | H= | P | 02/22/2013 | Seal face of coil to furnace as noted at HRR, connect cooktop with regulator, Rest ok. Note: full a/c installed. | MICHAELS | MICHAELS | | H= | P | 4475742 |
GENE'S HEATING AND AIR LLC | HC | C | 12/13/2012 | RELEASE METER | MICHAELS | MICHAELS | | HC | C | 4439443 |
GENE'S HEATING AND AIR LLC | HRR | C | 12/13/2012 | Correction made. | MICHAELS | MICHAELS | | HRR | C | 4439439 |
FOREST PLUMBING | HI | C | 12/12/2012 | 10# test ok. 1 1/4" main to furn, w/h, c-top, fp, bbq, 3/4" future pit. | MICHAELS | MICHAELS | | HI | C | 4438895 |
FOREST PLUMBING | HI | P | 12/11/2012 | Field cancelled by contractor, not ready. | MICHAELS | MICHAELS | | HI | P | 4438001 |
GENE'S HEATING AND AIR LLC | HRR | P | 12/11/2012 | Missing 2-supply in loft area, Rest ok. Note: FB, direct vent furnace, NO osa, a/c rough(coil and lineset) BY FINAL: seal face of coil to furnace. | MICHAELS | MICHAELS | | HRR | P | 4437996 |
GENE'S HEATING AND AIR LLC | HRR | R | 12/07/2012 | No duct design paperwork found, need fireplace framed. | MICHAELS | MICHAELS | | HRR | R | 4436304 |
FOREST PLUMBING | P= | C | 02/26/2013 | | LEE | LEE | | P= | C | 4477807 |
FOREST PLUMBING | P= | P | 02/22/2013 | INSULATE P-TRAP WITH SOMETHING WITH R-VALUE AND INSTALL P-TRAP WITH C/O PLUG ON BOTTOM AS WE DISCUSSED -- ALSO PVB TOO LOW (SEE HIGH CORNER IN BACK YARD) | LEE | LEE | | P= | P | 4476182 |
FOREST PLUMBING | P= | P | 02/08/2013 | LACKS FREEZE PROTECTION AT GARAGE SINK P-TRAP -- MASTER AND UPPER BATHS INCOMPLETE, IRRIGATION STUB LACKS BACKFLOW | LEE | LEE | | P= | P | 4469521 |
FOREST PLUMBING | PTO | C | 12/11/2012 | | LEE | LEE | | PTO | C | 4438308 |
FOREST PLUMBING | PB | C | 10/29/2012 | | LEE | LEE | | PB | C | 4411371 |
FOREST PLUMBING | PB | P | 10/26/2012 | 4" FLAT BETWEEN COMBO'S, COMPLETE BACKFILL AND BED PIPE TO CODE | LEE | LEE | | PB | P | 4410338 |