GKKWORKS CONSTRUCTION SERVICES | B= | C | 11/24/2014 | All other required Final inspections are complete. (This is a computer generated result) | JOND | JOND | | B= | C | 4859136 |
GKKWORKS CONSTRUCTION SERVICES | B= | P | 11/13/2014 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982). | JOND | JOND | | B= | P | 4853233 |
GKKWORKS CONSTRUCTION SERVICES | BE | C | 07/10/2014 | | MINDY | MINDY | | BE | C | 4773938 |
GKKWORKS CONSTRUCTION SERVICES | BSP | T | 06/26/2014 | PAID (REC#1203707) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN new splice pages see clouds | TCRIPPEN | TCRIPPEN | | BSP | T | 4766568 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 01/23/2014 | room 175 and176 and UPS 171 and 172 fire caulking of through penetrations ok | BERTW | BERTW | | BFR | P | 4676868 |
GKKWORKS CONSTRUCTION SERVICES | BFR | P | 10/07/2013 | H-2 Occ battery storage room 2hr fire barriers rooms framing ok/will need fire caulking inspection @ head of walls both sides,penetrations and visually inspect 2HR rated corridor walls where new conduits are ran through it/need damper framing inspected before Sheetrock | BERTW | BERTW | | BFR | P | 4617792 |
RK MECHANICAL, LLC | BSP | T | 08/30/2013 | PAID (REC#1156893) PLAN SPLICE FEE: $50 by: DALEH for Mechanical | DALEH | DALEH | | BSP | T | 4596582 |
GKKWORKS CONSTRUCTION SERVICES | BSP | T | 08/30/2013 | PAID (REC#1156894) PLAN SPLICE FEE: $50 by: SHELBY for Electrical | SHELBY | SHELBY | | BSP | T | 4595850 |
GKKWORKS CONSTRUCTION SERVICES | BSP | P | 08/29/2013 | PLAN SPLICE: (No Fee) by: JAY for Construction: structural revisions previously approved | JAY | JAY | | BSP | P | 4595682 |
RK MECHANICAL, LLC | BSP | T | 07/10/2013 | PAID (REC#1141771) ADDITIONAL PLAN REVIEW TIME: $50 From: TCRIPPEN new splice pages see clouds | TCRIPPEN | TCRIPPEN | | BSP | T | 4560128 |
GKKWORKS CONSTRUCTION SERVICES | BSP | T | 06/19/2013 | PAID (REC#1156894) PLAN SPLICE FEE: $50 by: JAY for Construction: Structural Sheets updated | JAY | JAY | | BSP | T | 4546538 |
GKKWORKS CONSTRUCTION SERVICES | BE | L | 06/19/2013 | Renewed at 6/19/2013 9:22:26 AM | NELIDA | NELIDA | | BE | L | 4545760 |
RK MECHANICAL, LLC | H= | C | 10/17/2014 | MECHANICAL FINAL OK. | NANCY | NANCY | | H= | C | 4837334 |
RK MECHANICAL, LLC | HWP | C | 06/30/2014 | PIPING COMPLETE. FOR FINAL COMPLETE HEAT TAPE, INSULATION AND LABELING OF PIPING IN MECHANICAL ROOM AND AT COOLING TOWER. | NANCY | NANCY | | HWP | C | 4768299 |
RK MECHANICAL, LLC | H= | P | 06/30/2014 | FOR FINAL COMPLETE HEAT TAPE, INSULATION AND LABELING IN MECHANICAL ROOM AND AT COOLING TOWER. PROVIDE REVISED/APPROVED PRINTS FOR ALL MECHANICAL CHANGES. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4768303 |
RK MECHANICAL, LLC | H= | P | 05/28/2014 | DUCT PORTION OF THIS PERMIT COMPLETE EXCEPT NEED TEST AND BALANCE REPORT. STILL NEED TO COMPLETE PIPING PORTION. | NANCY | NANCY | | H= | P | 4746752 |
RK MECHANICAL, LLC | HD | C | 05/07/2014 | HVAC ROUGH ALL COMPLETE. PIPING ROUGH NOT COMPLETE. FOR HVAC FINAL INSTALL RETAINING ANGLES ON FIRE/SMOKE DAMPERS 116 AND 117 IN HALLWAY OUTSIDE OF ROOM 171 UPS A. PROVIDE TEST AND BALANCE REPORT. | NANCY | NANCY | | HD | C | 4734422 |
RK MECHANICAL, LLC | HRP | P | 04/14/2014 | SEE RECORD OF TEST DATED 4/14/14/ 100 LB TEST OK ON CHILLED WATER SUPPLY/RETURN IN MECHANICAL ROOM. OK TO INSULATE. | NANCY | NANCY | | HRP | P | 4719826 |
RK MECHANICAL, LLC | H16 | C | 04/14/2014 | LETTER FROM TRANE ALLOWING PVC TO BE USED FOR REFRIGERANT VENT LINE ON CHILLERS RECEIVED AND SCANNED. | NANCY | NANCY | | H16 | C | 4719557 |
RK MECHANICAL, LLC | HWP | R | 04/11/2014 | NOT READY. | NANCY | NANCY | | HWP | R | 4718795 |
RK MECHANICAL, LLC | HWP | P | 04/09/2014 | TANK UNDER HYDROSTATIC PRESSURE, NO VISIBLE LEAKS AT TANK. | NANCY | NANCY | | HWP | P | 4717107 |
RK MECHANICAL, LLC | HV | P | 04/09/2014 | VENT PIPING FOR CHILLERS: PAPERWORK RECEIVED SHOWING MANUFACTURER ALLOWS PVC FOR VENT MATERIAL. PROVIDE INFORMATION REGARDING SIZING AND TERMINATION REQUIREMENTS. PROVIDE GLUE AND PRIMER INFORMATION. | NANCY | NANCY | | HV | P | 4717084 |
RK MECHANICAL, LLC | HWP | P | 04/02/2014 | SEE RECORD OF TEST DATED 4/2/14. 100 LB TEST OK ON CHILLED WATER SUPPLY/RETURN IN MECHANICAL ROOM. OK TO INSULATE.
| NANCY | NANCY | | HWP | P | 4713193 |
RK MECHANICAL, LLC | HWP | L | 03/31/2014 | NO ONE IN JOB TRAILER AT 11:20 AM. CALLED AND LEFT MESSAGE FOR BOBBY. WAITED UNTIL 11:30 AM. PLEASE RESCHEDULE. | NANCY | NANCY | | HWP | L | 4711613 |
RK MECHANICAL, LLC | HD | P | 03/13/2014 | FIELD CANCELED. | NANCY | NANCY | | HD | P | 4702125 |
RK MECHANICAL, LLC | HD | P | 02/11/2014 | SHEET M404. BATTERY ROOM AND UPS ROOM A: OK TO INSTALL REST OF RETAINING ANGLES ON FIRE/.SMOKE DAMPERS. REST OF THIS AREA COMPLETE EXCEPT WAITING TO SEE IF EDH1 GETS REINSTALLED. | NANCY | NANCY | | HD | P | 4685201 |
RK MECHANICAL, LLC | HWP | P | 02/11/2014 | SEE RECORD OF TEST 2/11/14. SHEET M403. SNOW MELT WATER HEATER: 100 LB TEST OK. OK TO INSULATE. BY FINAL NEED REVISED/APPROVED PRINTS SHOWING NEW LOCATION OF WATER HEATER FOR SNOW MELT. | NANCY | NANCY | | HWP | P | 4685184 |
RK MECHANICAL, LLC | H= | P | 01/30/2014 | SHEET M410. ROOM 294: PIPING AND CONDENSATES ALL COMPLETE. | NANCY | NANCY | | H= | P | 4680652 |
RK MECHANICAL, LLC | HWP | P | 01/30/2014 | SEE RECORDS OF TESTS 1/30/14. SHEETS M123 AND M410. RTU'S 1 AND 2: CHILLED WATER SUPPLY/RETURN TO BOTH UNITS UNDER WORKING PRESSURE. NO VISIBLE LEAKS. OK TO INSULATE. SHEET M403. STORAGE TANK: VISUAL INSPECTION OF STORAGE TANK AND TWO PIPE FLANGES. OK TO PARTIALLY COVER TANK. COMPLETE PIPING AND TEST ALL. | NANCY | NANCY | | HWP | P | 4680648 |
RK MECHANICAL, LLC | HWP | P | 11/14/2013 | SEE SHEET M410. ROOM 294 SECOND FLOOR: FIFTY FOUR 100 LB TESTS OK ON CHILLED WATER SUPPLY/RETURN TO CRAH UNITS. OK TO INSULATE. EVC HUMIDIFIERS AND AISLE HUMIDIFIERS: CONDENSATE DRAINS ALL OK, OK TO INSULATE. | NANCY | NANCY | | HWP | P | 4641662 |
RK MECHANICAL, LLC | HWP | P | 10/24/2013 | CONDENSATE DRAINS UNDER CRAH UNITS OK, OK TO INSULATE. | NANCY | NANCY | | HWP | P | 4628521 |
RK MECHANICAL, LLC | HD | P | 10/24/2013 | SEE SHEET M401. TWO FIRE.SMOKE DAMPERS FROM BATTERY ROOM TO MECHANICAL ROOM A OK, OK TO INSTALL ANGLES. FRAMING FOR TWO FIRE/SMOKE DAMPERS ABOVE DOOR OF BATTERY ROOM OK, OK TO COVER AND INSTALL DAMPERS. OPENINGS IN CMU WALL INTO UPS ROOM OK, OK TO INSTALL DAMPERS. | NANCY | NANCY | | HD | P | 4628514 |
RK MECHANICAL, LLC | HD | P | 10/16/2013 | SEE SHEET M120. ALL CRAH UNITS: OK TO WRAP HIGHLIGHTED DUCTS UP TO WALL. | NANCY | NANCY | | HD | P | 4623326 |
RK MECHANICAL, LLC | HD | P | 10/08/2013 | SEE SHEET M110. FCU12: FRAMING FOR TWO FIRE/SMOKE DAMPERS THROUGH WALL TO NEW BATTERY ROOM OK. OK TO INSTALL DAMPERS. EAST DAMPER WILL NEED WIDE RETAINING ANGLES INSTALLED. | NANCY | NANCY | | HD | P | 4618626 |
RK MECHANICAL, LLC | HD | P | 10/01/2013 | PHASE 2. SHEET M120. CRAH UNITS. 8 UNITS FROM THE WALL LOUVER TO SOUTH END: OK TO WRAP OUTSIDE UP THROUGH HUMIDIFIERS. 6 UNITS FROM LOUVER TO NORTH END: OK TO WRAP OUTSIDE AIR UP TO WHERE HUMIDIFIERS WILL BE INSTALLED, NO HUMIDIFIERS YET. ALL UNITS: OK TO WRAP OUTSIDE AIR/RETURN AIR AT UNITS. OK TO WRAP OUTSIDE AIR DUCT FOR UNIT #3. | NANCY | NANCY | | HD | P | 4613717 |
RK MECHANICAL, LLC | HD | P | 07/15/2013 | SEE SHEET M402 FOR DATE AND SIGNATURE. OK TO WRAP OUTSIDE AIR DUCTS EXCEPT UNITS 3 AND 14 NOT INSTALLED YET. | NANCY | NANCY | | HD | P | 4562721 |
RK MECHANICAL, LLC | P= | C | 06/30/2014 | | LEE | LEE | | P= | C | 4768601 |
RK MECHANICAL, LLC | PTO | C | 06/30/2014 | | LEE | LEE | | PTO | C | 4768600 |
RK MECHANICAL, LLC | PTO | R | 03/28/2014 | made call ahead left message no poc on site | TIM | TIM | | PTO | R | 4710630 |
RK MECHANICAL, LLC | PTO | P | 01/30/2014 | NO APPROVED PLANS ON SITE -- NEED TO VERIFY / SPLICE NEW W/H X-2 LOCATION AND SIZING ISOMETRIC -- ALSO NEW 4" STORM TIED TO EXISTING (ON PLANS ??) | LEE | LEE | | PTO | P | 4681052 |
RK MECHANICAL, LLC | PB | P | 11/04/2013 | CHILLER ROOM -- 3- FLOOR SINKS - 3- STACKS OK | LEE | LEE | | PB | P | 4635479 |
RK MECHANICAL, LLC | PTO | P | 10/31/2013 | FLOOR DRAIN THAT SERVICES MECH ROOM A NUMBER 294, .DRAIN IN CEILING OF BATTERY ROOM A NUMBER 144 PIPED TO THROUGH WALL OF MECH ROOM A NUMBER 145 | DICK | DICK | | PTO | P | 4633451 |