ART C KLEIN CONSTRUCTION, INC. | B= | C | 02/14/2014 | All other required Final inspections are complete. (This is a computer generated result) | JOHNP | JOHNP | | B= | C | 4687329 |
ART C KLEIN CONSTRUCTION, INC. | B= | P | 02/14/2014 | Additional Inspections Required: External Agency Inspection Z= by ZONING is not Completed yet (Contact: dtortorice@springsgov.com or 385-5099). Need zoning sign off | JOHNP | JOHNP | | B= | P | 4687208 |
ART C KLEIN CONSTRUCTION, INC. | BFR | C | 02/14/2014 | | JOHNP | JOHNP | | BFR | C | 4687205 |
ART C KLEIN CONSTRUCTION, INC. | BE | L | 02/14/2014 | Renewed at 2/14/2014 7:35:27 AM | TERRI | TERRI | | BE | L | 4687088 |
HVAC SOLUTIONS, INC. | BSP | T | 03/22/2013 | PAID (REC#1118710) PLAN SPLICE FEE: $50 by: RUSSELL for Mechanical: ElIMINATED O.A. FROM TWO UNTIS | RUSSELL | RUSSELL | | BSP | T | 4492384 |
ART C KLEIN CONSTRUCTION, INC. | B= | P | 02/05/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: kmagargal@springsgov.com or 385-5060), FOSTER ELECTRIC CORP Electrical Final Inspection is not Completed yet, FRONTIER MECHANICAL SYSTEMS IN Mechanical Final Inspection is not Completed yet, HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet. Need fire, mechanical & zoning finals | JOHNP | JOHNP | | B= | P | 4466832 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 11/14/2012 | West side - walls OK | JOHNP | JOHNP | | BFR | P | 4421938 |
ART C KLEIN CONSTRUCTION, INC. | B= | P | 11/13/2012 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: kmagargal@springsgov.com or 385-5060), FOSTER ELECTRIC CORP Electrical Final Inspection is not Completed yet, HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet. East side OK -- Schedule a new Building Final when above items are complete. | JOHNP | JOHNP | | B= | P | 4420830 |
ART C KLEIN CONSTRUCTION, INC. | BFR | P | 11/02/2012 | east side ok to drywall pending other rough inspections | BLAKE | BLAKE | | BFR | P | 4414851 |
FOSTER ELECTRIC CORPORATION | E= | C | 06/28/2013 | | TIMA | TIMA | | E= | C | 4553410 |
FOSTER ELECTRIC CORPORATION | E= | R | 06/27/2013 | NEED POINT OF CONTACT NUMBER | TIMA | TIMA | | E= | R | 4552065 |
FOSTER ELECTRIC CORPORATION | E= | C | 03/29/2013 | FIRE ALARM INSPECTION: | TIMA | TIMA | | E= | C | 4496423 |
FOSTER ELECTRIC CORPORATION | ER | C | 03/29/2013 | FIRE ALARM INSPECTION: FPLP CABLE INSTALLED EAST SECTION OK | TIMA | TIMA | | ER | C | 4496422 |
FOSTER ELECTRIC CORPORATION | ER | C | 03/29/2013 | CEILING OK EAST SIDE-----CONTRACTOR TO CHANGE DISCONNECTS TO FUSED DISCONNECTS FOR AIR HANDLING UNITS CHECK ON FINAL---- | TIMA | TIMA | | ER | C | 4496421 |
FOSTER ELECTRIC CORPORATION | ER | P | 12/27/2012 | WEST CEILINGS OK | TIMA | TIMA | | ER | P | 4445810 |
FOSTER ELECTRIC CORPORATION | E= | P | 11/09/2012 | EAST SIDE OK FOR TEMPORARY OCCUPANCY -----STILL WILL NEED COMPLETE INSPECTION---- | TIMA | TIMA | | E= | P | 4419338 |
FOSTER ELECTRIC CORPORATION | ER | P | 11/05/2012 | WEST EXTERIOR WALLS OK | TIMA | TIMA | | ER | P | 4415643 |
FOSTER ELECTRIC CORPORATION | ER | L | 11/01/2012 | called point of contact twice to voice mail | MATTHEW | MATTHEW | | ER | L | 4413607 |
FOSTER ELECTRIC CORPORATION | ER | P | 10/31/2012 | ALL WALLS EAST SIDE OK | TIMA | TIMA | | ER | P | 4412667 |
HVAC SOLUTIONS, INC. | H= | C | 04/16/2013 | TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4507204 |
HVAC SOLUTIONS, INC. | H= | P | 04/09/2013 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. PLEASE NOTE, ALTHOUGH THE LETTER FROM THE AIRPORT OPERATIONS MANAGER EXEMPTING THE NEW CONDENSERS FROM HAVING RAILING/GUARDS INSTALLED HAS BEEN RECEIVED AND SCANNED ONTO THIS PERMIT (SEE INSPECTION NOTE 1/11/13) IT IS HIGHLY RECOMMENDED BY THE MECHANICAL INSPECTOR THAT ALL GUARDS AND RAILS BE INSTALLED AS PER THE MECHANICAL CODE TO PROTECT ANY PERSONNEL SERVICING THE EQUIPMENT FROM FALLING OFF THE EDGE OF THE BUILDING. | NANCY | NANCY | | H= | P | 4502483 |
HVAC SOLUTIONS, INC. | HD | P | 03/28/2013 | Duct complete above ceiling in east queuing line area only still need TSA east office and room next to east office completed before cover. | JON | JON | | HD | P | 4495393 |
FRONTIER MECHANICAL SYSTEMS INC | H= | C | 03/22/2013 | PIPING FINAL OK. | NANCY | NANCY | | H= | C | 4492026 |
HVAC SOLUTIONS, INC. | HD | P | 03/21/2013 | OK TO WRAP LAST FITTING ON OUTSIDE AIR DUCT. OK TO WRAP LATERALS ON EXISTING VAV'S. | NANCY | NANCY | | HD | P | 4491063 |
HVAC SOLUTIONS, INC. | HD | P | 03/14/2013 | OK TO WRAP OUTSIDE AIR DUCT IN SOFFIT. BY FINAL NEED REVISED/APPROVED PRINTS. | NANCY | NANCY | | HD | P | 4487087 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 03/13/2013 | EAST SIDE: HOT WATER PIPING ABOVE CEILING TO NEW UNITS OK. OK TO INSULATE. STILL NEED TO SEE TIE IN TO ORIGINAL PIPING. | NANCY | NANCY | | HWP | P | 4486200 |
HVAC SOLUTIONS, INC. | HD | P | 03/13/2013 | HAVE APPROVED PRINTS ON SITE AT NEXT INSPECTION. EAST SIDE: ROUGH DUCTS ABOVE CEILING ALL OK EXCEPT STILL NEED TO SEE NEW DUCTS INSTALLED ON EXISTING VAV'S. OK TO WRAP LATERALS. | NANCY | NANCY | | HD | P | 4486189 |
HVAC SOLUTIONS, INC. | H16 | C | 02/05/2013 | LETTER FROM AIRPORT OPERATIONS MANAGER RECEIVED AND SCANNED. LETTER EXEMPTS CONDENSERS ON STAIR TOWERS FROM HAVING RAILINGS INSTALLED AS REQUIRED BY THE IMC SECTION 304.11, GUARDS. | NANCY | NANCY | | H16 | C | 4466516 |
HVAC SOLUTIONS, INC. | H= | P | 01/11/2013 | MECHANICAL FINAL FOR WEST SIDE OK PENDING RECEIPT OF TEST AND BALANCE REPORT AND LETTER FROM ENGINEER APPROVING NO RAILING/GUARDS FOR CONDENSERS. NOTE: CHECK WEST SIDE CONDENSERS WHEN FINAL CALLED IN FOR EAST SIDE. | NANCY | NANCY | | H= | P | 4452937 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 01/02/2013 | WEST SIDE, AHU'S 1 AND 2: VISUAL INSPECTION OF HOT WATER PIPING TO BOTH AHU'S OK. SYSTEM ALREADY IN USE, NO VISIBLE LEAKS. | NANCY | NANCY | | HWP | P | 4447430 |
FRONTIER MECHANICAL SYSTEMS INC | HWP | P | 12/28/2012 | WRONG PERMIT, INSPECTION FOR PERMIT I48708. | NANCY | NANCY | | HWP | P | 4446565 |
HVAC SOLUTIONS, INC. | HD | P | 12/28/2012 | WEST SIDE: ABOVE CEILING FLEX AND DIFFUSERS ALL OK. STILL NEED SMOKE DETECTION, CO2 SENSORS AND SECONDARY DRAIN WET SWITCH INSTALLED FOR BOTH AIR HANDLERS. ALSO LABEL BOTH UNITS. | NANCY | NANCY | | HD | P | 4446481 |
HVAC SOLUTIONS, INC. | HD | P | 12/17/2012 | WEST SIDE: AHU2, OK TO WRAP OUTSIDE AIR DUCT. AHU1: TRUNK LINE AND LATERALS OK, OK TO WRAP LATERALS. NO FLEX OR DIFFUSERS YET. | NANCY | NANCY | | HD | P | 4441145 |
HVAC SOLUTIONS, INC. | HD | P | 11/13/2012 | EAST SIDE: OK TO INSTALL SLOT DIFFUSER GRILLS. MECHANICAL OK FOR TEMPORARY OCCUPANCY. WEST SIDE: SLOT DIFFUSERS ABOVE SOFFIT OK, OK TO COVER. | NANCY | NANCY | | HD | P | 4420380 |
HVAC SOLUTIONS, INC. | HD | P | 11/05/2012 | EAST SIDE: SLOT DIFFUSERS OK, OK TO COVER. | NANCY | NANCY | | HD | P | 4415646 |