GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 08/23/2013 | All other required Final inspections are complete. (This is a computer generated result) | JOHNP | JOHNP | | B= | C | 4591495 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 03/13/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet, OLSON PLUMBING & HEATING CO Mechanical Final Inspection is not Completed yet. Need other sign offs | JOHNP | JOHNP | | B= | P | 4486138 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 02/25/2013 | Firecaulk above grid OK | JOHNP | JOHNP | | BFR | P | 4476456 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 02/11/2013 | framing completed/pending other roughs completed/need friecaulking inspection at firebarrier wall to underside of deck when sheetrock is installed | BERTW | BERTW | | BFR | P | 4470119 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 01/11/2013 | Additional Inspections Required: External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet, GREEN ELECTRIC INC Electrical Final Inspection is not Completed yet. Room 240 OK after other finals -- Schedule a new Building Final when above items are complete. | JOHNP | JOHNP | | B= | P | 4452966 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 12/20/2012 | Room 240A walls
| JOHNP | JOHNP | | BFR | P | 4443668 |
GREEN ELECTRIC INC | E= | C | 03/07/2013 | | BRET | BRET | | E= | C | 4482754 |
GREEN ELECTRIC INC | E= | C | 03/06/2013 | FIRE ALARM INSPECTION: | JOSEPH | JOSEPH | | E= | C | 4482389 |
GREEN ELECTRIC INC | ER | C | 03/06/2013 | FIRE ALARM INSPECTION: | JOSEPH | JOSEPH | | ER | C | 4482388 |
GREEN ELECTRIC INC | E= | R | 03/06/2013 | Circuits 1, 6, 4, 2, & 15 have no power, unable to check outlets. Still need to inspect panel. Boxes mounted in combustible material need to be flush with finished surface NEC 314.20 | JOSEPH | JOSEPH | | E= | R | 4482385 |
GREEN ELECTRIC INC | ER | P | 02/25/2013 | Drop Ceilings ok, | JOSEPH | JOSEPH | | ER | P | 4476739 |
GREEN ELECTRIC INC | ER | P | 02/11/2013 | Walls in pre-op ann nurses station. | JOSEPH | JOSEPH | | ER | P | 4470081 |
GREEN ELECTRIC INC | ER | P | 01/10/2013 | FIRE ALARM INSPECTION: a240 ceiling | BRET | BRET | | ER | P | 4452060 |
GREEN ELECTRIC INC | ER | C | 01/10/2013 | ceiling a240 | BRET | BRET | | ER | C | 4452056 |
GREEN ELECTRIC INC | ER | P | 12/19/2012 | wall between 240 and 241 a | BRET | BRET | | ER | P | 4443015 |
COLORADO SHEET METAL CO., INC. | H= | C | 05/23/2013 | TEST AND BALANCE REPORT RECEIVED. | NANCY | NANCY | | H= | C | 4530129 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 04/30/2013 | THIS CONTRACTOR SCOPE OF WORK COMPLETE | ROBERTV | ROBERTV | | H= | C | 4514805 |
COLORADO SHEET METAL CO., INC. | H= | P | 02/25/2013 | MECHANICAL FINAL OK PENDING RECEIPT OF TEST AND BALANCE REPORT. | NANCY | NANCY | | H= | P | 4476508 |
COLORADO SHEET METAL CO., INC. | HD | P | 02/08/2013 | VAV-01 MEDIUM AND LOW PRESSURE DUCT OK FOR WRAP, REMAINING EF-01 DUCT IN PRE-OP A243 OK, EF-01 ON ROOF OK, CHECK ALL DIFFUSER CONNECTIONS AND VAV ACCESS AT FINAL | ROBERTV | ROBERTV | | HD | P | 4469337 |
OLSON PLUMBING & HEATING COMPANY | HWP | C | 02/07/2013 | VAV1 AND VAV2: VISUAL INSPECTION OF CHILLED WATER SUPPLY/RETURN. NO VISIBLE LEAKS. OK TO INSULATE. | NANCY | NANCY | | HWP | C | 4468177 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/11/2013 | ANESTHESIA STORAGE A240: ABOVE CEILING ALL OK, OK FOR TILES PER MECHANICAL ONLY. CLEARANCE AROUND BOTH FIRE DAMPERS OK, OK FOR ANGLES. | NANCY | NANCY | | HD | P | 4453232 |
COLORADO SHEET METAL CO., INC. | HD | P | 12/19/2012 | TWO FIRE DAMPER FRAMES OK (1 SA, 1 EXHAUST), OK FOR ROCK. CLEARANCE AROUND DAMPERS OK, STILL NEED TO SEE CLEARANCE BEFORE ANGLES ARE INSTALLED ON BOTH SIDES. VAV02: MEDIUM PRESSURE DUCT OK TO WRAP. LOW PRESSURE TRUNK LINE OK TO WRAP. STILL NEED TO SEE FLEX AND DIFFUSERS. EXHAUST DUCT FROM ANESTHESIA STORAGE BACK TO BRICK WALL OK. | NANCY | NANCY | | HD | P | 4442911 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 03/08/2013 | | LYNNIE | LYNNIE | | P= | C | 4484409 |
OLSON PLUMBING & HEATING COMPANY | PTO | C | 02/06/2013 | | LYNNIE | LYNNIE | | PTO | C | 4467458 |